Liebert Extender/Adapter installation manual Liebert NX UPS to Liebert NX UPS, Power on COM1

Page 6

Installation

2.0INSTALLATION

2.1Liebert NX UPS to Liebert NX UPS

! WARNING

Installation by qualified electrical personnel only—hazardous voltage may be present at the UPS output connectors.

1.Connect the power cables of the adapter to the Phase A, Neutral and Ground output of each UPS.

2.Connect the LBS cable to COM1 of each LBS Signal Adapter.

3.Connect the other end of each LBS cable to X4 on the parallel board (UHW241M3) in the

NX UPS.

4.Connect the communication cable (up to 492 ft. [150m]) to the COM2 interface of each LBS Signal Adapter.

5.The switch of both LBS signal adapters should be in the right position (see Figure 4).

Figure 4 Connecting a Liebert NX to a Liebert NX

Power ON COM1

COM2 SWITCH

 

 

 

 

 

LED1

Power ON COM1

COM2 SWITCH

 

 

 

 

 

 

LED1

Power Cable

Connect to NX UPS

LBS

Power Cable

Connect to NX UPS

LBS

Cable

Cable

Communication Cable

up to 492 ft. (150m)

2

Image 6
Contents Load Bus Sync Extender/Adapter for Dual Bus UPS Page Figures Page General Liebert NX UPS to Liebert NX UPS Power on COM1Power Cable Connect to NX UPS Cable Communication Cable Up to 492 ft mDescription Rating Liebert NX UPS to Non-Liebert NX UPSDescription Description Part NumberUPS NicSite Netwo