Liebert GXT2-10000RT208 user manual Auto-Learning Battery Run Times

Page 49

Troubleshooting

13.1Auto-Learning Battery Run Times

As batteries age, the estimated run times may become less accurate. The Liebert GXT2-10000RT208 is programmed to “learn” from a full battery discharge and modify the estimated run time for the measured battery capacity. This can improve accuracy and compensate for aging batteries or batter- ies that operate at different ambient temperatures.

The UPS will update the anticipated run time calculation only under certain conditions.

The UPS must have a steady load that is greater than 20%.

The UPS must be at 100% charge at the start of a battery discharge.

The battery discharge must continue uninterrupted until the batteries reach their end-of-dis- charge voltage.

If all conditions are not met, the run time calculation will not be modified.

If the configuration program is used to change the number of battery cabinets, then the values in Table 6 will be restored. This will override any value that is automatically learned.

43

DISCONTINUED

 

PRODUCT

Image 49
Contents Liebert GXT2-10000RT208 DIS Product Table of Contents Modes of Operation Controls and IndicatorsTroubleshooting MaintenanceSpecifications CommunicationsFigures Important Safety Instructions Product Glossary of Symbols Introduction and System Description Battery Charger Rectifier/Power Factor Correction PFC CircuitInverter System DescriptionDC to DC Converter BatteryStatic Bypass Main Frame and Electronics Internal Battery PackMajor Components PD-102 Power Distribution Option PD-103 PD-101 Power Distribution Option with Internal ConnectorWHAT’S Included Installation and Configuration Install the Main CabinetTower UPS Installation Attach Bezels to TopQuantity Installing the Adjustable Rack-Mount Kit-Sold SeparatelyReturn flanges Retaining Latches Front Innermembers members Rack Depth M4 nuts M4 nutsSupport Base With Spacers for External Battery Cabinets External Battery Cabinet InstallationUPS External Battery Cabinet Distribution Module Electrical Connections Connect Input/Output PowerElectrical requirements Input & Output Terminal Block Connections208 or Output to Load See Note 120 Input to UPS See NoteHardwire Terminal Block Cover Add an Output Power Distribution Module-OptionalOutput Distribution Cover Plate Screw holes To attach to UPSControls and Indicators horizontal overlay Install the Internal Battery PacksInitial Startup and Electrical Checks Hardwire Input ConnectionsOutput Receptacle Distribution Options Hardwire terminal connectionsConfiguration Program Liebert GXT2-10000RT208 Configuration Program FeaturesWhat You Will Need Establishing Communication Link with Configuration Program-InstallationRead/Confirm UPS Configuration Settings Configuration Program-OperationCancel Without Changing UPS Settings Changing UPS SettingsOn-Screen Reminders Programming Rejected When UPS is OffPartial Rejection Output Voltage UPS TabOutput Voltage Selection Notes N Reverse Detection-120V UPS Models OnlyFrequency Selection Options TabOptions Tab Used With Earlier Liebert GXT2 Models Low Battery Time Warning Battery TabAuto Battery Test Time Battery Cabinets NumberAbout Tab Controls and Indicators ON/Alarm Silence/Battery Test ButtonOFF/Bypass Button Horizontal overlay for rack mountingFault Indicator Red Battery Level Indicators 5 GreenBypass Indicator Amber UPS on Indicator GreenBattery Mode Operation Normal Mode OperationBattery Recharge Operation Modes of OperationCommunications Communications Interface Port11.1.1 DB-9 Interface Port DB-9 pin assignmentUPS Intelligent Communications Pin 4 Remote Shutdown on BatteryCommunications-Liebert SNMP/OCWEBCARD Snmp Adapter Wrap network cable around ferrite beadKey to Repo switch connections 1 VDC Sense Common Remote Emergency Power OffRepo Connection Maintenance Battery ReplacementInternal Battery Replacement Procedures BatteryUPS Power Module Replacement UPS back panel-control location Fault indicators Indicator status Diagnosis/Audible alarm TroubleshootingCondition Alarm Alarm conditionsTroubleshooting guide Problem Cause Solution See 12.2 UPS Power Module Replacement Battery/External 10000VA Run Time Cabinets Load% Minutes Battery run timesAuto-Learning Battery Run Times UPS specifications SpecificationsOptional output distribution specifications-PD-101 Battery specificationsSee Battery run times Model Number PD-101 DIMENSIONS, W x D x HOptional output distribution specifications-PD-103 Optional output distribution specifications-PD-102Model Number PD-102 DIMENSIONS, W x D x H Model Number PD-103 DIMENSIONS, W x D x HExternal battery cabinet specifications Product Warranty RegistrationModel Number Product DIS Product Environmental Systems Web SiteNit Etwo

GXT2-10000RT208 specifications

The Liebert GXT2-10000RT208 is a highly sophisticated uninterruptible power supply (UPS) designed to deliver reliable power protection for critical IT infrastructure and business operations. With a power capacity of 10,000 VA, this UPS ensures the continuous operation of essential devices, safeguarding them from potential damage caused by power interruptions, surges, or sags.

One of the standout features of the Liebert GXT2-10000RT208 is its online double conversion technology. This technology provides a consistent, high-quality power output by converting incoming AC power to DC and then back to AC. This process eliminates voltage fluctuations and offers a stable energy supply, ensuring that connected equipment operates smoothly, regardless of the condition of the utility power.

The UPS is designed to support a wide range of applications, making it an ideal choice for data centers, telecommunications setups, and other critical environments. Its advanced microprocessor control ensures precise monitoring and regulation of power conditions. The Liebert GXT2-10000RT208 also features an impressive input voltage range, which is beneficial in areas where power quality is inconsistent.

Equipped with an LCD display, users can easily access vital information regarding the UPS’s operational status, battery health, and power protection levels. This user-friendly interface simplifies monitoring and management, allowing for quick assessments and troubleshooting.

Another key characteristic of the Liebert GXT2-10000RT208 is its modular design. This allows for easy installation and maintenance, as well as the opportunity to expand the power capacity by adding external battery cabinets. This scalability ensures that businesses can adapt their power protection solutions to meet evolving needs without significant changes to their existing setups.

The UPS also includes advanced battery management features that optimize battery lifespan and performance. The Liebert GXT2-10000RT208 employs intelligent charging algorithms and battery testing functions to ensure reliable performance when needed most. Furthermore, support for various communication protocols enhances compatibility with other management systems, enabling seamless integration into existing infrastructure.

In summary, the Liebert GXT2-10000RT208 is a powerful and versatile UPS solution that combines advanced technology with robust features. Its online double conversion technology, extensive monitoring capabilities, and scalable design make it an excellent choice for organizations seeking reliable protection for their critical systems. With the GXT2-10000RT208, businesses can operate confidently, knowing their power supply is secure from unexpected disruptions.