Liebert PS250-60S, PS600-60S, PS400-60S user manual Specifications, Fcc Id #

Page 11

SPECIFICATIONS

FCC ID #

N/A

 

BHKAF400T-60

 

BKAF600T-60

Model # / Stock #

PS250-60/PS250-60S

 

PS400-60 / PS400-60S

 

PS600-60 / PS600-60S

Model Rating

250 VA / 150 W

 

400 VA / 240 W

 

600 VA / 360 W

Dimensions

 

 

 

 

 

Unit (W x D x H)

3.51 x 10.18 x 6.79 in

 

4.25 x 10.18 x 7.02 in

 

4.84 x 10.18 x 8.15 in

 

(90 x 262 x 175 mm)

 

(109 x 262 x 186 mm)

 

(124 x 262 x 216 mm)

Shipping (W x D x H)

7.13 x 14.37 x 11.93 in

 

8.35 x 18.98 x 11.5 in

 

9.33 x 18.98 x 13.15 in

 

(181 x 365 x 303 mm)

 

(212 x 482 x 292 mm)

 

(237 x 482 x 334 mm)

Weight

 

 

 

 

 

Unit

8.8 lb. (4 kg)

 

12.5 lb. (5.7 kg)

 

19.8 lb. (9 kg)

Shipping

10.1 lb. (4.6 kg)

 

15.4 lb. (7 kg)

 

23.1 lb.(10.5 kg)

AC Parameters

 

 

 

 

 

Receptacles

(2) NEMA 5-15

 

(4) NEMA 5-15

 

(4) NEMA 5-15

Input Voltage Range

90-135 VAC, Single Phase, 2 Wire Plus Ground

Low Voltage Transfer Point

95 VAC, User Selectable to 90 or 100 VAC

High Voltage Transfer Point

135 VAC

 

135 VAC, User Selectable to 140 VAC

Input Frequency Range

 

 

47 – 53 Hz, 57 – 63 Hz

 

Output Voltage (on battery)

 

 

115 VAC, ± 5%

 

Output waveform (on battery)

 

 

Stepped Sine Wave

 

Max. Output Current at 120 V

2.1 A

 

3.3A

 

5 A

Output Frequency

 

 

50 or 60 Hz, ±5%

 

Max. Overload Capacity

 

 

115% of Power Rating

 

Battery

 

 

 

 

 

Type

Sealed, Valve-Regulated Lead Acid, Maintenance-Free

Qty x Voltage x Rating

1 x 12 V x 4.5 AH

 

1 x 12 V x 7 AH

 

2 x 12 V x 7 AH

Back-up Time

 

 

6 minutes at full load

 

Time from Low Battery Alarm

Approximately 2 Minutes, depending on load

to Shutdown

 

 

 

 

 

Recharge Time

 

 

8 – 10 Hours to 90% Capacity

 

Battery Life

 

 

3 – 5 Years Typical

 

Transfer Time to/from Inverter

 

 

2 – 6 msec. Typical

 

Agency Approvals

 

 

 

 

 

Safety

 

 

UL, C-UL Listed

 

EMI / RFI

Meets FCC Part 15, Subpart B, Class B

Surge Protection

Meets IEEE 587, Category A and B

MTBF (Bellcore Method)

 

100,000 Hours (Excluding Battery)

Environmental Standards

 

 

 

 

 

Operating Temperatures

 

50° F to +104° F (10° C to +40° C)

Storage Temperatures

 

0° F to +104° F (-20° C to +40° C)

 

(High Temperatures Reduce Battery Life)

Cooling

 

 

Convection

 

Audible Noise

 

 

Less than 40 dB @ 1 meter

 

Operating Elevation

 

 

Up to 9,900 ft. (3,000 m)

 

Storage Elevation

 

 

Up to 33,000 ft. (10,000 m)

 

11

Image 11
Contents PowerSure Important Safety Instructions Introduction & System Description 600 VA / 115 General InstallationOperating Instructions Adapter COMPUTER/LAN Interface 400/600 VA onlyBattery Test Button Option Switch SettingsTo Replace the Battery Battery Care and USEAlarm Conditions Resetting the Circuit BreakerVA LED & Alarm Indications FCC ID # SpecificationsLimited Warranty Technical Support

PS400-60S, PS250-60S, PS600-60S specifications

The Liebert PS600-60S, PS250-60S, and PS400-60S are advanced power supply units designed to provide reliable power protection for critical equipment. These systems are vital for industries that require an uninterrupted power supply, such as data centers, telecommunications, and healthcare.

One of the standout features of the Liebert PS series is its robust design and high efficiency. The PS600-60S, with its 600VA capacity, offers a compact solution for smaller environments while still delivering reliable performance. The PS250-60S, with a 250VA capacity, caters to applications with less demanding power requirements, making it ideal for point-of-sale systems or telecommunications equipment. The PS400-60S, on the other hand, balances size and power, providing 400VA to meet moderate power needs effectively.

All models in the Liebert PS series leverage advanced technologies to ensure top-tier performance. They are equipped with sine wave output, which is crucial for sensitive electronic devices as it minimizes electrical noise and enhances performance. Additionally, the units feature automatic voltage regulation (AVR) that stabilizes output voltage, protecting equipment from surges and dips in power.

Another significant characteristic of the Liebert PS600-60S, PS250-60S, and PS400-60S is their user-friendly interface. Each model includes LED indicators that provide real-time information regarding the operational status, battery health, and load level. This feature allows users to monitor the unit easily, ensuring they can respond promptly to any potential issues.

Battery management is also a key feature in these models. They are equipped with intelligent charging technology that prolongs battery life and optimizes performance. The hot-swappable batteries allow for maintenance without disrupting the power supply, which is essential in critical environments.

In conclusion, the Liebert PS600-60S, PS250-60S, and PS400-60S power supply units are designed to offer reliable, efficient, and user-friendly solutions for power protection. Their combination of compact design, advanced technologies, and essential features makes them ideal for a vast array of applications, ensuring a stable power supply for sensitive equipment while enhancing overall operational efficiency.