Liebert Power Supply important safety instructions MINI-TOWER Battery Replacement, VA Model

Page 9

MINI-TOWER BATTERY REPLACEMENT

CAUTION- A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed before replacing the batteries:

Turn off and disconnect the UPS from utility power prior to opening the battery replacement door.

Remove rings, watches, and other metal objects.

Use a Phillips (cross head) screwdriver with insulated grips.

Do not lay tools or other metal objects on top of the batteries.

If the battery replacement kit is damaged in any way or shows signs of leakage, contact your dealer immediately.

Do not dispose of batteries in a fire, the batteries may explode.

If you feel unqualified to replace the battery, do not open the battery door. Call Liebert Technical Support (LTS). World Wide Technical Support numbers are located at the end of this section.

1.Grasp the front bezel near the top and pull forward.

2.Rotate the bezel upward and lay it on top of the UPS.

3.Loosen the (2) screws at top of the battery door and remove door by pulling it forward slightly and lifting it off. Lay battery door and screws aside for reassembly.

4.700/1000/1400 VA models: gently pull battery wiring out and disconnect the red wire (+) and black wire (-).

2200 VA models: pull apart connectors A and B.

5.Grasp white pull-tabs located on sides of the front battery, and pull batteries out of the UPS.

6.Unpack new batteries taking care not to destroy the packing.

7.Slide new batteries into the cavity, noting the white pull-tabs are facing outward.

8.700/1000/1400 VA models: connect the battery wires; first red to red, then black to black.

2200 VA models: first connect top battery connector A to bottom battery connector A; then connect UPS connector B to the top battery connector B.

NOTE: There will be a small spark when connecting the black connectors on 700-1400 VA models, and connector B on the 2200 VA model. This is normal and will not harm you or the UPS.

9.Replace battery door by inserting the (2) metal tabs into the slots at the base of the UPS, and pushing it closed at the top. Tighten the (2) screws to lock the battery door closed.

10.Flip the bezel back into place, and align bottom clips to the lower slots in the battery door. Once aligned, push bezel back onto the UPS until it latches into position. This may require a gentle tap.

11.Recycle/Dispose of old batteries in accordance with your local laws and regulations.

Pull bezel forward

Rotate bezel on top

Remove battery door

700 VA Model

To Disconnect: Gently pull wiring away

To Connect: Connect red wire to red terminal, then black wire to black terminal by pushing towards connector

1000/1400 VA Model

To Disconnect: Gently pull wiring away

To Connect: Connect red wire to red terminal, then black wire to black terminal by pushing upward

2200 VA Model

A

 

B

To Disconnect: Pull apart connections A & B

To Connect: Push connections A together & connections B together

17

18

Image 9
Contents Important Safety Instructions Introduction & System Description Glossary of SymbolsEMI/RFI Filters Regulator Battery Bi-Directional Converter MINI-TOWER InstallationMajor Components Automatic VoltageRackmount Installation Load/Battery Level Indicators ALL Green Controls and IndicatorsRackmount Powersure Interactive MINI-TOWER Powersure InteractiveUtility High/Low Utility Alarm silence/Test On/Off Alarm silence/Test On/OffOperation 51% to 75% load 26% to 50% load To 25% loadCommunications Interface Port MaintenanceUPS Monitoring UPS Intelligent CommunicationsVA Model MINI-TOWER Battery ReplacementRackmount Battery Replacement Troubleshooting Guide TroubleshootingIndicator a indicator Problem Cause SolutionFuse Replacement Procedures for 700 VA Powersure Interactive Typical Battery Discharge CurvesDischarge times are at 25 C ambient Two minutes of run time remainingRackmount Specifications MINI-TOWER SpecificationsEnvironmental AgencyLife Support Policy Limited Warranty