Liebert PowerSure Personal user manual 115V Specifications, Weight lbs kg

Page 10

115V SPECIFICATIONS

Model Number

PSP300-115

 

PSP500-115

Model Rating VA / W

300 / 180

 

500 / 300

DIMENSIONS: in (mm)

 

 

 

Unit￿H x W x D

7.0 x 3.0 x 9.4

 

7.0 x 3.0 x 9.4

 

(178 x 76 x 238)

 

(178 x 76 x 238)

Shipping￿H x W x D

10.6 x 4.3 x 12.3

 

10.6 x 4.3 x 12.3

 

(270 x 110 x 312)

 

(270 x 110 x 312)

WEIGHT: lbs (kg)

 

 

 

Unit

6.2 (2.8)

 

8.0 (3.6)

Shipping

7.7 (3.5)

 

9.5 (4.3)

INPUT AC PARAMETERS

 

 

 

Voltage Range

90-132 VAC

 

without Battery Operation

 

Low Line Transfer

90 VAC

 

High Line Transfer

132 VAC

 

Frequency

45-55 Hz or 54-66 Hz; auto sensing

Input Power Cord

6 ft. detachable, w/ NEMA 5-15 P

OUTPUT AC PARAMETERS

 

Output Receptacles

(4) 5-15R

 

Voltage (Battery Mode)

115 VAC + 5%

 

Output Current

2.6 A

 

4.3 A

Waveform (Battery Mode)

Stepped

Sinewave

 

Frequency

50 Hz or 60 Hz; auto sensing

Overload Warning

101 – 120%

 

(Utility and Battery Modes)

 

 

 

 

Overload Shutdown

Overload Warning

 

Overload Warning

(Utility and Battery Modes)

+ (15 – 25 W)

 

+ (20 – 45 W)

BATTERY PARAMETERS

 

 

 

Type

Valve-regulated, nonspillable, lead acid

 

Quantity x Voltage x

(1) x 12V x 4.5 Ah

 

(1) x 12V x 7.0 Ah

Rating

 

 

 

Approved Battery

CSB, Panasonic, BB Battery, and

Yuasa

 

Manufacturers:

 

 

 

Transfer Time

2 – 6 ms typical

 

Back-up Time:

At 77°F (25°C), resistive loading, with fully charged batteries:

Full load

> 4 minutes

 

Half load

12 minutes

 

Recharge Time

7-10 hours to 90% capacity, after full discharge into 100% resistive

 

load

 

ENVIRONMENTAL

 

 

 

Operating Temperature

+32° F to + 104° F (0° C to +40° C)

 

Storage Temperature

+5° F to + 122° F (-15° C to +50° C)

 

Relative Humidity

0% to 90%, non-condensing

 

Operating Elevation

Up to 10,000 ft. (3000 m) at 95° F (35° C) without derating

Audible Noise

< 40 dBA, at 1 meter

 

AGENCY

 

 

 

Safety

UL 1778, c-UL Listed

 

Surge

IEEE C62.41 Category A

 

ESD

IEC 801-2, Level 3, Criterion< 2

 

Susceptibility

IEC 801-3, Level 3, Criterion< 2

 

Electrical Fast

IEC 801-4, Level 4, Criterion< 2

 

Transient/Burst

 

 

 

Emissions

FCC Part 15, Subpart B, Class B

 

Transportation

ISTA Project 1A

 

 

10

 

 

Image 10
Contents English Important Safety Instructions Introduction & System Description Major ComponentsPowerSureTM Personal General Installation Maintenance Fuse Replacement ProceduresCommunications Collector to EmitterTroubleshooting Problem Cause SolutionBattery Mode LED & Alarm IndicationsAC Mode Startup115V Specifications Weight lbs kgLimited Warranty Powersure Personal 300- 500 VA 115V Technical Support