Liebert PS250-50S, PS400-50S, PS600-50S user manual Specifications, Dimensions mm

Page 10

SPECIFICATIONS

Model # / Stock #

PS250-50/PS250-50S

 

PS400-50 / PS400-50S

 

PS600-50 / PS600-50S

Model Rating

250 VA / 150 W

 

400 VA / 240 W

 

600 VA / 360 W

Dimensions: mm

 

 

 

 

 

Unit (W x D x H)

90 x 262 x 175

 

109 x 262 x 186

 

124 x 262 x 216

Shipping (W x D x H)

181 x 365 x 303

 

212 x 482 x 292

 

237 x 482 x 334

Weight: Kg

 

 

 

 

 

Unit

4

 

5.7

 

9

Shipping

4.6

 

7

 

10.5

AC Parameters

 

 

 

 

 

Receptacles

(2) CEE-22

 

(4) CEE-22

 

(4) CEE-22

Input Voltage Range

180-300 VAC, Single Phase, 2 Wire Plus Earth

Low Voltage Transfer Point

190 VAC, User Selectable to 180 or 200 VAC

High Voltage Transfer Point

270 VAC

 

270 VAC, User Selectable to 280 VAC

Input Frequency Range

 

 

47 – 53 Hz, 57 – 63 Hz

 

Spike Protection

 

 

80 Joules

 

Output Voltage (on battery)

 

 

230 VAC, ± 5%

 

Output waveform (on battery)

 

 

Stepped Sine Wave

 

Max. Output Current at 230 V

1.1 A

 

1.7A

 

2.6A

Output Frequency

 

 

50 or 60 Hz, ± 5%

 

Max. Overload Capacity

 

 

115% of Power Rating

 

Battery

 

 

 

 

 

Type

 

 

Valve-Regulated Lead Acid

 

Qty x Voltage x Rating

1 x 12 V x 4.5 AH

 

1 x 12 V x 7 AH

 

2 x 12 V x 7 AH

Back-up Time

 

 

6 minutes at full load

 

Time from Low Battery Alarm

Approximately 2 Minutes, depending on load

to Shutdown

 

 

 

 

 

Recharge Time

 

 

8 – 10 Hours to 90% Capacity

 

Battery Life

 

 

3 – 5 Years Typical

 

Transfer Time to/from Inverter

 

 

2 – 6 msec. Typical

 

Agency Approvals

 

 

 

 

 

Safety

 

 

EN 50091-1

 

RFI

Meets EN 55022 Class B, IEC 801-2, 3, 4

Surge Protection

 

 

Meets IEC 801-5 (Draft)

 

MTBF (Bellcore Method)

 

100,000 Hours (Excluding Battery)

Environmental Standards

 

 

 

 

 

Operating Temperatures

 

 

+10° C to +40° C

 

Storage Temperatures

-20° C to +40° C (High Temperatures Reduce Battery Life)

Cooling

 

 

Convection

 

Audible Noise

 

 

Less than 40 dB @ 1 meter

 

Operating Elevation

 

 

Up to 3,000 m

 

Storage Elevation

 

 

Up to 10,000 m

 

10

Image 10
Contents PowerSure Important Safety Instructions Installation Instructions Operating Instructions Option Switch Settings COMPUTER/LAN Interface 400/600 VA onlyBattery Test Button Battery Care and USEResetting the Circuit Breaker Alarm ConditionsProblem Cause Solution VA LED & Alarm Indications Specifications Dimensions mmLimited Warranty Technical Support