Liebert IntelliSlot® OC-485 Card
Quick Start Guide
INSTALL
•Locate the Intellislot option bay for your Liebert equipment. You might need to remove a plastic cover.
•Insert the Liebert IntelliSlot
•Secure the card with the supplied screws.
•Connect
IGM: The card ships with IGM service enabled. (No configuration is required for IGM communications.)
Modbus: To assign a server ID address, use the Service Terminal to con- figure the card. Proceed to Steps 2 & 3.
CONNECT THE CABLE
•Locate the blue serial configuration cable (null modem) that shipped with the card.
•Connect the configuration cable to the
CONFIGURE THE CARD
•Use terminal emulation soft- ware, such as HyperTerminal™, to open a direct connection to the card.
Baud Rate: | 9600 |
Data Bits: | 8 |
Parity: | None |
Stop Bits: | 1 |
Flow Control: | None |
•Press ENTER for the Main Menu, above right.
•Select option 1 and press Enter to access the communications settings, shown at right.
•Enter 1 and press enter to enable the Modbus application.
•At the next screen, enter 3 to access the screen to set the server ID for the Liebert IntelliSlot
•Press Esc to return to the main Menu.
•Enter X and press Enter to exit HyperTerminal, save your changes and reboot the card.
NOTE
When installing the card in a Liebert NX™, configure the communication port of the Liebert NX to 2400 baud. Refer to the Liebert NX user manual for instructions.