Technical information
Technical characteristics
Table of Gemini switchboards’ technical characteristics
Size |
| 1 | 2 | 3 | 4 | 5 | 6 |
| |
Gemini with transparent door |
| 1SL0211A00 | 1SL0212A00 | 1SL0213A00 | 1SL0214A00 | 1SL0215A00 | 1SL0216A00 |
| |
Gemini with opaque door |
| 1SL0201A00 | 1SL0202A00 | 1SL0203A00 | 1SL0204A00 | 1SL0205A00 | 1SL0206A00 |
| |
External dimensions WxHxD (mm) 335x400x210 | 460x550x260 | 460x700x260 | 590x700x260 | 590x855x360 | 840x1005x360 |
| |||
Internal dimensions WxHxD (mm) | 250x300x180 | 375x450x230 | 375x600x230 | 500x600x230 | 500x750x330 | 750x900x330 |
| ||
IP degree |
| IP66 | IP66 | IP66 | IP66 | IP66 | IP66 |
| |
Double isolation |
| Yes | Yes | Yes | Yes | Yes | Yes |
| |
IK degree |
| 10 | 10 | 10 | 10 | 10 | 10 |
| |
GWT (°C) |
| 750 | 750 | 750 | 750 | 750 | 750 |
| |
Operating temperature |
| ||||||||
No. of DIN modules |
| 24 (12x2) | 54 (18x3) | 72 (18x4) | 96 (24x4) | 120 (24x5) | 216 (36x6) | 3 | |
No. of vertical modules (H=150 mm) | 2 | 3 | 4 | 4 | 5 | 6 | |||
Material | Thermoplastic | Thermoplastic | Thermoplastic | Thermoplastic | Thermoplastic | Thermoplastic | |||
Color | Grey RAL7035 | Grey RAL7035 | Grey RAL7035 | Grey RAL7035 | Grey RAL7035 | Grey RAL7035 |
| ||
Fast wiring system |
| Unifix L | Unifix L | Unifix L | Unifix L | Unifix L | Unifix L |
| |
No. of locks |
| 2 | 2 | 2 | 2 | 3 | 3 |
| |
Rated current In |
| ≤ 400 A | ≤ 400 A | ≤ 400 A | ≤ 400 A | ≤ 400 A | ≤ 400 A |
| |
Rated frequency |
|
| |||||||
Maximum dissipation power (1) |
| 45 W | 72 W | 85 W | 102 W | 156 W | 248 W |
| |
STANDARD CEI EN |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
| ||
| - Max. dispersible power with |
|
|
|
|
|
|
|
|
|
| 40 W | 65 W | 77 W | 91 W | 133 W | 205 W |
| |
|
|
|
|
|
|
|
|
|
|
| - Max. dispersible power with |
|
|
|
|
|
|
|
|
|
| 45 W | 72 W | 85 W | 102 W | 156 W | 248 W |
| |
|
|
|
|
|
|
|
|
|
|
| - Max. dispersible power with |
|
|
|
|
|
|
|
|
|
| 52 W | 85 W | 100 W | 121 W | 187 W | 299 W |
| |
|
|
|
|
|
|
|
|
|
|
| - Max. dispersible power with |
|
|
|
|
|
|
|
|
|
| 62 W | 100 W | 118 W | 143 W | 221 W | 355 W |
| |
|
|
|
|
|
|
|
|
| |
Impulse withstand (par. 8.2.2) |
|
|
|
|
|
|
|
| |
| - Rated service voltage |
| ≤ 690 V | ≤ 690 V | ≤ 690 V | ≤ 690 V | ≤ 690 V | ≤ 690 V |
|
|
|
|
|
|
|
|
|
|
|
| - Rated insulation voltage |
| ≤ 800 V | ≤ 800 V | ≤ 800 V | ≤ 800 V | ≤ 800 V | ≤ 800 V |
|
|
|
|
|
|
|
|
|
| |
| - Rated impulse withstand voltage | 8 kV | 8 kV | 8 kV | 8 kV | 8 kV | 8 kV |
| |
|
|
|
|
|
|
|
|
| |
Short circuit withstand (par. 8.2.3) |
|
|
|
|
|
|
|
| |
| - Rated peak |
| - | - | - | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
(1)Maximum dissipation power data was obtained following the indications of Standard CEI
(2)Note to paragraph 8.2.1 of Standard CEI EN
The table gives the thermal dissipation values of Gemini switchboards when they are
ABB | 25 |