Fortinet manual FortiGate-5020 Chassis Guide 01-30000-0043-20061207

Page 2

Warnings and cautions

Only trained and qualified personnel should be allowed to install or maintain FortiGate-5000 series equipment. Read and comply with all warnings, cautions and notices in this document.

!

!

CAUTION: Risk of Explosion if Battery is replaced by an Incorrect Type. Dispose of Used Batteries According to the Instructions.

Caution: You should be aware of the following cautions and warnings before installing FortiGate-5000 series hardware

Turning off all power switches may not turn off all power to the FortiGate-5000 series equipment. Except where noted, disconnect the FortiGate-5000 series equipment from all power sources, telecommunications links and networks before installing, or removing FortiGate-5000 series components, or performing other maintenance tasks. Failure to do this can result in personal injury or equipment damage. Some circuitry in the FortiGate-5000 series equipment may continue to operate even though all power switches are off.

An easily accessible disconnect device, such as a circuit breaker, should be incorporated into the data center wiring that connects power to the FortiGate-5000 series equipment.

Install FortiGate-5000 series chassis at the lower positions of a rack to avoid making the rack top-heavy and unstable.

Do not insert metal objects or tools into open chassis slots.

Electrostatic discharge (ESD) can damage FortiGate-5000 series equipment. Only perform the procedures described in this document from an ESD workstation. If no such station is available, you can provide some ESD protection by wearing an anti-static wrist or ankle strap and attaching it to an ESD connector or to a metal part of a FortiGate chassis.

Some FortiGate-5000 series components may overload your supply circuit and impact your overcurrent protection and supply wiring. Refer to nameplate ratings to address this concern.

Make sure all FortiGate-5000 series components have reliable grounding. Fortinet recommends direct connections to the branch circuit.

If you install a FortiGate-5000 series component in a closed or multi-unit rack assembly, the operating ambient temperature of the rack environment may be greater than room ambient. Make sure the operating ambient temperature does not exceed the manufacturer's maximum rated ambient temperature.

Installing FortiGate-5000 series equipment in a rack should be such that the amount of airflow required for safe operation of the equipment is not compromised.

This equipment is for installation only in a Restricted Access Location (dedicated equipment room, service closet or the like), in accordance with the National Electrical Code.

Per the National Electrical Code, sizing of a Listed circuit breaker or branch circuit fuse and the supply conductors to the equipment is based on the marked input current rating. A product with a marked input current rating of 25 A is required to be placed on a 40 A branch circuit. The supply conductors will also be sized according to the input current rating and also derated for the maximum rated operating ambient temperature, Tma, of the equipment.

FortiGate-5000 series equipment shall be installed and connected to an electrical supply source in accordance with the applicable codes and regulations for the location in which it is installed. Particular attention shall be paid to use of correct wire type and size to comply with the applicable codes and regulations for the installation / location. Connection of the supply wiring to the terminal block on the equipment may be accomplished using Listed wire compression lugs, for example, Pressure Terminal Connector made by Ideal Industries Inc. or equivalent which is suitable for AWG 10. Particular attention shall be given to use of the appropriate compression tool specified by the compression lug manufacturer, if one is specified.

FortiGate-5020 Chassis Guide

01-30000-0043-20061207

Image 2
Contents A s s i s G u i d e FortiGate-5020 Chassis Guide 01-30000-0043-20061207 Contents Contents FortiGate-5020 Chassis Guide 01-30000-0043-20061207 FortiGate-5020 chassis FortiGate-5020 front panelFortiGate-5020 back panel Physical description of the FortiGate-5020 chassisMounting the FortiGate-5020 chassis FortiGate-5020 hardware proceduresConnecting the FortiGate-5020 chassis to AC power Air flowTurning on FortiGate-5020 chassis power FortiGate-5020 base backplane interfaces Changing the HA heartbeat interface configuration FortiGate HA between two FortiGate-5020 chassisFortiGate-5001SX HA heartbeat interface configuration FortiGate HA between two FortiGate-5020 chassis Fortinet documentation Customer service and technical supportFor more information Regulatory compliance