HIGH TEMPERATURE VENT LIMIT SWITCH
Models: LS-140A, LS-550A
Items Included: | 1) | High temperature vent limit switch | 1) | |
| 2) | 1) | 6 foot length of 12/2 wire | |
| 1) | Tube of high temperature sealant | 2) | Wire hold down clips |
| 4) | Wiring quick connect terminals | 1) | ROMEX connector |
Installation of a High temperature vent limit switch is recommended for LP and Natural gas fired power vented and natural draft water heaters. This device is installed to limit the vent temperature in either plastic pipe (1400 F temperature limit) or B vent installations (5500 F temperature limit) caused by scaled up tanks and/or inadequate venting. Wiring MUST be in accordance with the National Electrical Code and applicable local codes.
The Field Controls High temperature vent limit switch MUST be installed by a qualified agency in accordance with the manufacturer’s installation instructions.
The definition of a qualified agency is: any individual, firm, corporation or company which either in person or through a representative is engaged in, and is responsible for, the installation and operation of gas appliances, who is experienced in such work, familiar with all the precautions required, and has complied with the requirements of the authority having jurisdiction.
Before and after adding this safety control on existing appliances, an installation inspection in accordance with the National Fuel Gas Code 54, Z223.1 Appendix H should be performed and a combustion analysis is recommended to determine the operating condition of the appliance.
CAUTION: Disconnect Electrical Power When Wiring High temperature vent limit switch
MODEL | P/N | CONTACT | LOAD RATING | LIMIT | RESET | SWITCH | APPLICATION | ||
|
| ||||||||
MATERIAL | AMPS | VOLTS | SETPOINT °F | TYPE | |||||
|
|
|
|
46564100 | SILVER | 15 A | 120 AC | 140 | AUTOMATIC | SPDT | PLASTIC VENT APPLICATIONS | |
46564200 | SILVER | 15 A | 120 AC | 550 | AUTOMATIC | SPDT |
2630 Airport Road · Kinston, NC 28504
Phone: