Emerson Process Management ControlWave Express Process I/O, All I/O, Pulse/Digital Inputs

Page 4

Product Data Document

420DS-6c / D301311X012

January 29, 2009 - Page 4

Bristol® ControlWave® Express

 

 

ControlWave Express Process I/O

ControlWave Express I/O module is designed to maximize usability while minimizing installation and maintenance.

The I/O module (bottom card) provides a mix of analog and digital inputs and outputs that are a perfect fit for small RTU applications.

•2 DI/PI (on CPU)

•1 RTD input on 14 MHz CPU

•4 DI

•2 DO

•2 selectable DI or DO

•2 selectable DI or HSC

•Optional 3 AI or 3 AI and 1 AO

Features

•Convenient pluggable local terminations

•All configuration jumpers and switches accessible without disassembly of circuit boards

•Termination points for external loop power supply

Specifications

All I/O

•I/O access: 50 ms with 33 MHz CPU, 250 ms with 14 MHz CPU

•1 second for 2 DI/PI inputs on CPU board

•Surge protection: Meets C37.90-1978

•30 Vdc transorb between signal and ground

•Terminations are pluggable and accept a maximum wire size of 16 gauge

•Power consumption is stated for each I/O module type measured at the input supply and does not include loop power

Pulse/Digital Inputs

•Inputs located on base CPU board

•Number of points: up to 2 non-interrupting inputs

•Internally sourced, dry contact single ended inputs

•Scan rate: Once per second

•Input filter: 20 microSec

•Voltage Range: Internally sourced dry contact input - 3.3 Vdc

•On state: >1.6 V, Off state <1.3V

•Input current : 200 µA for low power applications

•Power consumption:

200 µA input, all inputs ON: 0.002 watt

Used as Pulse Input:

•Frequency Range: 0-10 kHz

•Debounce: None

•Accumulator: 16 bit

RTD Input

•Input available on 14 MHz Ultra Low Power

CPU only

Specifications are for the interface only, not includ- ing the RTD probe or wiring

•RTD Conversion Accuracy: ± 0.1°C, or ± 0.1% of reading, whichever is greater

Remote Automation Solutions

Website: www.EmersonProcess.com/Remote

Image 4
Contents Features Remote Automation SolutionsProduct Data Document Application SuitabilityScalability ControlWave Designer with AccolSpecifications ControlWave Express Process I/O All I/OPulse/Digital Inputs RTD InputDigital Inputs Digital OutputsAnalog Inputs Analog OutputOpenBSI High Speed CountersSimply Creative OpenBSI UtilitiesLocal Configuration Wizard allows local commu Real-time ActiveX ControlsHistorical Data Collection ActiveX ControlsRequired Software High Historical Data IntegrityControlWave Open Network Connectivity Communication ProtocolsBsap Protocol Modbus ProtocolMulti-user Security Access Generic Serial InterfaceSecure Data Advantage Bridge Between SystemsModel Specification Model Specification, cont’d Preconfigured P/NsBristol ControlWave Express