FieldServer FS-8700-73 instruction manual UINT16

Page 19

FS-8700-73 BACnet MSTP Driver Manual

Page 19 of 24

 

 

Appendix B.4. BACnet State Text Preload

Method 1 – Using a Single Data Array:

Data_Arrays

 

 

 

 

 

Data_Array_Name,

Data_Format,

Data_Array_Length

 

 

 

DA_MI_01,

UINT16,

100

 

 

 

DA_STATE_TXT,

BYTE,

200

 

 

 

 

 

 

 

 

 

Preloads

 

 

 

 

 

Data_Array_Name,

Preload_Data_Value,

Preload_Data_Format,

Preload_Data_Index

DA_STATE_TXT,

MyState1 MyState2 MyState3 MyState4 MyState5 MyState6,

String,

0

 

 

 

 

 

 

Map_Descriptors

 

 

 

 

 

 

 

 

Map_Descriptor_Name, Data_Type,

Object_ID,

Function,

Data_Array_Name,

Data_Array_Index,

Node_Name,

Length,

State_Text_Array

CMD_MI_01,

MI,

1

Server

DA_MI_01,

0,

N1 11,

1,

Da_State_Txt

Method 2 – Using an Offset/User Table:

 

//set up a look up table

 

 

 

 

 

Offset_Table,

 

 

 

 

 

 

Offset_Table_Name,

 

Table_String,

 

Table_Index_Value

 

FIRE_ALRM_TEXT,

 

SYSTEM READY,

0

 

 

FIRE_ALRM_TEXT,

 

ALARM,

 

1

 

 

FIRE_ALRM_TEXT,

 

MAINTENANCE,

2

 

 

FIRE_ALRM_TEXT,

 

OFF-LINE,

 

3

 

 

FIRE_ALRM_TEXT,

 

IN SERVICE,

 

4

 

 

FIRE_ALRM_TEXT,

 

OTHER,

 

5

 

 

 

 

 

 

 

 

 

Data_Arrays

 

 

 

 

 

 

Data_Array_Name,

Data_Format,

Data_Array_Length

 

 

DA_MI_01,

UINT16,

100

 

 

 

 

 

 

 

 

 

Map_Descriptors

 

 

 

 

 

 

 

 

Map_Descriptor_Name, Data_Type,

Object_ID,

Function,

Data_Array_Name,

Data_Array_Index,

Node_Name,

Length,

State_Text_Array

CMD_MI_01,

MI,

1

Server

DA_MI_01,

1,

N1 11,

1,

Fire_Alrm_Text

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com

Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: support@fieldserver.com

Image 19
Contents Effective for all systems manufactured after August Sierra Monitor CompanyTable of Contents Max Nodes Supported BACnet Mstp DescriptionBuilding control unit BCU Server Server n Hardware ConnectionsHardware connection Tips/Hints Data Arrays/Descriptors Configuring the FieldServer as a BACnet Mstp ClientClient Side Connection Descriptions Client Side Node Descriptors AI, AO, AV, BI, BV, MI, MO Rdbc Driver Specific FieldServer Parameters Configuring the FieldServer as a BACnet Mstp Server255 Server Side Node Descriptors14 Page Driver Specific Map Descriptor Parameters Map Descriptor Example FS-8700-73 BACnet Mstp Driver Manual Appendix B.2. BACnet Priority Arrays UINT16 FS-8700-73 BACnet Mstp Driver Manual Appendix A.1. Network Number Appendix C.2 BACnet Specific StatisticsAppendix D. Units KVA GPM