FieldServer X30, FS-8700-122 instruction manual Map Descriptor Example

Page 9

FS-8700-122 X30 Profibus DP Master Manual

Page 9 of 16

4.6.Map Descriptor Example.

This example demonstrates the transfer of I/O data with Remote Profibus DP Slaves using Station Addresses of 1 and 125.

Map Descriptor

 

 

 

 

 

 

 

 

Map_Descriptor_Name, Data_Array_Name,

Data_Array_Offset,

Function,

Node_Name,

Profibus_Data_Type,

Address,

Length,

Scan_Interval

Word_In_003,

Word_Input,

0,

RDBC,

PDP_SLV003,

WORD

0,

50,

1s

Word_Out_003,

Word_Output,

0,

WRBC,

PDP_SLV003,

WORD

0,

50,

1s

Byte_In_125,

Byte_Input,

0,

RDBC,

PDP_SLV125,

BYTE,

0,

120,

1s

Byte_Out_125,

Byte_Output,

0.

WRBC,

PDP_SLV125,

BYTE,

0,

120,

1s

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com

Image 9
Contents FS-8700-122 X30 Profibus DP Master Table of Contents X30 Profibus DP Master Description Max Nodes Supported FieldServer Mode CommentsRequired 3rd Party Configuration Hardware Connection Tips / Hints Hardware ConnectionsData Arrays/Descriptors FieldServerClient Side Node Descriptors Client Side Connection DescriptionsTiming Parameters Driver Related Map Descriptor ParametersMap Descriptor Example Configuring the Embedded Profibus Database FS-8700-122 X30 Profibus DP Master Manual FS-8700-122 X30 Profibus DP Master Manual FS-8700-122 X30 Profibus DP Master Manual FS-8700-122 X30 Profibus DP Master Manual Important Note FS-8700-122 X30 Profibus DP Master Manual This page Intentionally Left Blank