FieldServer FS-8700-128 Configuring the FieldServer as a Safetran-SCS-128 Server

Page 11

FS-8700-128 Safetran SCS-128 Manual

Page 11 of 15

5.Configuring the FieldServer as a Safetran-SCS-128 Server

For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer (See “.csv” sample files provided with the FieldServer).

This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a Safetran-SCS-128 Client. When configured as a Server, the FieldServer is unable to keep synchronism with other Servers and Clients on the network if it is being polled using ‘Poll’ Function (i.e. single byte message). Therefore the FieldServer must be polled with ‘Recall’ request for indication statuses. The FieldServer will always respond with the current statuses.

The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for Safetran-SCS-128 communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the FieldServer virtual Node(s) needs to be declared in the “Server Side Nodes” section, and the data to be provided to the clients needs to be mapped in the “Server Side Map Descriptors” section. Details on how to do this can be found below.

Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.

5.1.Server Side Connection Descriptors

Section Title

 

 

 

 

 

Connections

 

 

 

 

 

Column Title

Function

 

Legal Values

Port

Specify which port the device is connected to the

P1-P82

 

 

 

FieldServer

 

 

 

 

 

 

SCS-128

 

 

Protocol

Specify protocol used

SCS128

 

 

 

 

Safetran SCS-128

 

 

 

75,

150,

300

,600,

Baud*

Specify baud rate

1200, 2400,

9600

 

 

(Vendor limitation)

 

Parity*

Specify parity

Even

(Vendor

limitation)

 

 

 

 

 

 

Data_Bits*

Specify data bits

8 (Vendor limitation)

 

 

 

Stop_Bits*

Specify stop bits

1 (Vendor limitation)

 

 

 

 

 

Handshaking*

Specify hardware handshaking

None

 

 

 

Specifies time FieldServer will reserve Server

 

 

 

 

Server_Hold_Timeout

side connection while waiting for the Client side to

>1.0s

 

 

 

update data in Data_Array (if necessary)

 

 

 

 

2Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware.

FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com Tel: 408 262-2299 Fax: 408-262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com

Image 11
Contents FS-8700-128 Safetran SCS-128 Table of Contents Safetran-SCS-128 Description FS-8700-128 Safetran SCS-128 Manual Vhlc Hardware ConnectionsData Arrays/Descriptors Configuring the FieldServer as a Safetran-SCS-128 ClientClient Side Node Descriptors Client Side Connection DescriptionsTiming Parameters Driver Related Map Descriptor ParametersMap Descriptor Example Read Indications CMDDO4 Map Descriptor Example Write ControlsServer Side Connection Descriptors Configuring the FieldServer as a Safetran-SCS-128 ServerServer Side Node Descriptors Driver Specific Map Descriptor Parameters Map Descriptor Example Appendix A. Advanced Topics Appendix A.1. Data Format