AR - 1215 AC LINE VOLTAGE REGULATOR
convenience outlets on the rear panel, and one on the front panel. All are functionally interchangeable. The outlets are regulated, spike-suppressed, and fi l- tered against RFI with a 3-pole fi lter, making the unit a full-function power conditioner. The AR-1215 has no controls except an on-off switch. (The AR-1215J and AR-2306 also have an output voltage selector switch.)
Note: The AR-1215 and AR-2306 are for use with AC voltage only. DC voltages should never be ap- plied to them. Also, they do not change or regulate line frequency. The output frequency will always be the same as the incoming frequency.
MAXIMUM AND MINIMUM LOAD
The AR-1215 and AR-1215J can handle loads total- ling up to 15 amperes as long as the input voltage is equal to or above 124 volts (or 104 volts if using AR-1215J set to 100 volt output). For voltages below that level, its capacity must be derated at approxi- mately 113 milliamperes per volt. (See graphs on back page.) As a practical matter, therefore, to cope successfully with worst-case brownout conditions,
you should plan your total load so that it does not exceed 12 amps, or 1400 watts. Please note that this refers to the aggregate power requirement of all equipment plugged into the Voltage Regulator, not to each individual item.
The AR-2306 can handle loads totalling up to 6 amperes as long as the input voltage is equal to or above the selected output voltage. For voltages below that level, its capacity must be derated at ap- proximately 23 milliamperes per volt. (Again, please see graphs on back page.) As a practical matter, therefore, to cope successfully with worst-case brownout conditions, you should plan your total load so that it does not exceed 5 amps, or 1100 watts. Please note that this refers to the aggregate power requirement of all equipment plugged into the Volt- age Regulator, not to each individual item.
NOTE: While there is no minimum load require- ment for the AR1215 or AR-2306, you may experience an audible mechanical hum coming directly from the unit when the POWER switch is on with nothing plugged in. This effect will disappear as soon as you plug in any equipment
| | INPUT VOLTAGE� | IN� | EXTREME � |
| A.C. LINE VOLTAGE� | VOLTAG�E� |
| |
| REGULATOR� | �75-98���101� 105� 110� 115� 120� 125� 131� 137� 140-150� | REGULATION� | SHUTDOWN � |
| MODEL AR-1215 � | | | |
15A 120V 50-60HZ�
ON�
OF�F�
AR-1215 front view
W� | 15 AMP� | 100 �V� 120 �V� |
A� | 15� |
R� | |
A� | 75-140 VAC� |
N� | M� |
I� | P� | |
N� | | |
G� | | |
FOR CONTINUED � | |
PROTECTION AGAINST� | ATTENTION:� |
FIRE HAZARD REPLACE� |
WITH SAME TYPE AND� | REMPLACER LE FUSIBL� E� |
RATING OF FUSE� | AVEC MEME TYPE� |
DISCONNECT SUPPLY � | |
BEFORE CHANGING FUSE.� | |
COUPER L'ALIMENTATION � | |
AVANT DE CHANGER LE FUSIBL� | E� |
REGULATED� OUTPUTS� 120 VAC� 15 AMPS�
AR-1215J rear view (the switch above the AC cord is not present in the AR-1215)
| 220� 230� 240� | N’OUVREZ PAS—RISQUE� |
CIRCUI� T� | | DE CHOC ELECTRIQUE� |
OUTPUT VOLTAGE� | 174-288 VAC | 6 � A� |
BREAKER� | | |
6� A� M� P�
AR-2306 rear view. NOTE: The three models in the AR-Series differ in their nominal AC output voltages. Model AR-1215
produces 120 VAC: AR-1215J produces either 100 or 120 VAC; and AR-2306 produces either 220, 230, or 240 VAC.