AR - 1215 AC LINE VOLTAGE REGULATOR

convenience outlets on the rear panel, and one on the front panel. All are functionally interchangeable. The outlets are regulated, spike-suppressed, and fi l- tered against RFI with a 3-pole fi lter, making the unit a full-function power conditioner. The AR-1215 has no controls except an on-off switch. (The AR-1215J and AR-2306 also have an output voltage selector switch.)

Note: The AR-1215 and AR-2306 are for use with AC voltage only. DC voltages should never be ap- plied to them. Also, they do not change or regulate line frequency. The output frequency will always be the same as the incoming frequency.

MAXIMUM AND MINIMUM LOAD

The AR-1215 and AR-1215J can handle loads total- ling up to 15 amperes as long as the input voltage is equal to or above 124 volts (or 104 volts if using AR-1215J set to 100 volt output). For voltages below that level, its capacity must be derated at approxi- mately 113 milliamperes per volt. (See graphs on back page.) As a practical matter, therefore, to cope successfully with worst-case brownout conditions,

you should plan your total load so that it does not exceed 12 amps, or 1400 watts. Please note that this refers to the aggregate power requirement of all equipment plugged into the Voltage Regulator, not to each individual item.

The AR-2306 can handle loads totalling up to 6 amperes as long as the input voltage is equal to or above the selected output voltage. For voltages below that level, its capacity must be derated at ap- proximately 23 milliamperes per volt. (Again, please see graphs on back page.) As a practical matter, therefore, to cope successfully with worst-case brownout conditions, you should plan your total load so that it does not exceed 5 amps, or 1100 watts. Please note that this refers to the aggregate power requirement of all equipment plugged into the Volt- age Regulator, not to each individual item.

NOTE: While there is no minimum load require- ment for the AR1215 or AR-2306, you may experience an audible mechanical hum coming directly from the unit when the POWER switch is on with nothing plugged in. This effect will disappear as soon as you plug in any equipment

 

INPUT VOLTAGE

IN

EXTREME

A.C. LINE VOLTAGE

VOLTAGE

 

REGULATOR

75-98��101105110115120125131137140-150

REGULATION

SHUTDOWN

MODEL AR-1215

 

 

 

15A 120V 50-60HZ

ON

OFF

REGULATED OUTLET

POWER

AR-1215 front view

W

15 AMP

100 V120 V

A

15

R

 

A

75-140 VAC

N

M

I

P

 

N

 

 

G

 

 

FOR CONTINUED

 

PROTECTION AGAINST

ATTENTION:

FIRE HAZARD REPLACE

WITH SAME TYPE AND

REMPLACER LE FUSIBLE

RATING OF FUSE

AVEC MEME TYPE

DISCONNECT SUPPLY

 

BEFORE CHANGING FUSE.

 

COUPER L'ALIMENTATION

 

AVANT DE CHANGER LE FUSIBL

E

REGULATEDOUTPUTS120 VAC15 AMPS

AR-1215J rear view (the switch above the AC cord is not present in the AR-1215)

 

220230240

N’OUVREZ PAS—RISQUE

CIRCUIT

 

DE CHOC ELECTRIQUE

OUTPUT VOLTAGE

174-288 VAC

6 A

BREAKER

 

 

6AMP

AR-2306 rear view. NOTE: The three models in the AR-Series differ in their nominal AC output voltages. Model AR-1215

produces 120 VAC: AR-1215J produces either 100 or 120 VAC; and AR-2306 produces either 220, 230, or 240 VAC.

3

Image 4
Contents Voltage Regulators AR-SERIES Features Safety InformationImportant Safety Instructions Please Read Prior to InstallationNominal Output Voltages VS. Input IN-REGULATION Ranges First Select the Correct VOLT- AGEMaximum and Minimum Load RegulatorExtreme Voltage Protection DefinitionsFuses and Circuit Breakers Installation Input Voltage MonitoringOutput Voltage Monitoring DesignONE Limited Warranty ServiceSpecifications Output Current Rating