Overview
Overview
Module Description
The Modbus TCP (MBTCP) Gateway Module provides a control link between a Modbus TCP fieldbus and a sys- tem that uses Graco Control Architecture (GCA). This link provides the means for remote monitoring and con- trol by an external automation system.
Data provided by the MBTCP Gateway Module to the fieldbus depends on the
Data Exchange
Data is available by block transfer or by explicit access to individual attributes as defined by the fieldbus specifi- cation.
Module Status LED Signals
Signal | Description |
|
|
Green on | The system is powered up. |
|
|
Yellow | Internal communication is in prog- |
| ress. |
|
|
Red | MBTCP hardware failure |
Solid |
|
|
|
Red Flashing | The red LED (F) will flash a code, |
| pause, then repeat. See MBTCP |
| Module Errors on page 7 for |
| details. |
|
|
3 flashes | The host device of the mapped |
| property is not responding. |
|
|
4 flashes | No valid mapping is set by the |
| host. |
|
|
5 flashes | MBTCP is not connected or the |
| system has an invalid network |
| configuration. |
|
|
NOTE:
If you get a “No Valid Map” error, disable and
Module Requirements
Power Supply
The MBTCP Gateway Module requires a
0.2A power supply. Refer to the system manual for sys- tem level power supply guidelines.