System Sensor M500S installation manual 47K EOL Resistor ELR-47K Control Module

Page 2

Figure 3. Typical notification appliance circuit configuration, NFPA Style Y:

24 VDC CIRCUIT

DO NOT LOOP WIRE ON TERMINALS 10 & 11. BREAK WIRE

RUN TO PROVIDE SUPERVISION OF CONNECTIONS.

CONNECT MODULES TO

LISTED COMPATIBLE

CONTROL PANELS ONLY

24 VDC POWER SUPPLY ISOLATED, REGULATED, POWER LIMITED PER NFPA 70. LISTED FOR FIRE PROTECTION WITH BATTERY BACKUP.

MODULE POLARITIES ARE

SHOWN IN ALARM

(−) (−)

47K EOL

RESISTOR

ELR-47K

(+)

(+)

CONTROL

MODULE

(−)

(−) (+)

(+)

(−)

FROM

(+)

PANEL OR

 

PREVIOUS

 

DEVICE

SIGNAL LINE CIRCUIT (SLC)

32 VDC MAX.

TWISTED PAIR

IS RECOMMENDED

ALL WIRING SHOWN IS SUPERVISED

AND POWER LIMITED

(−)

TO NEXT

(+)

DEVICE

 

UL LISTED EOL RELAY SHOWN ENERGIZED 24 VDC COIL EOLR-1

TO NEXT CONTROL MODULE OR END-OF-LINE RELAY. ONE RELAY REQUIRED FOR EACH CIRCUIT. SOME CONTROL PANELS HAVE RELAY BUILT IN AND DO NOT REQUIRE EXTERNAL WIRING. REFER TO PANEL MANUAL.

*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.

 

 

 

 

 

C0913-05

Figure 4. Typical fault tolerant notification appliance circuit configuration, NFPA Style Z:

 

 

 

 

24 VDC CIRCUIT

CONNECT MODULES TO LISTED

 

 

DO NOT LOOP WIRE ON TERMINALS 10 & 11.

24 VDC POWER SUPPLY

 

BREAK WIRE RUN TO PROVIDE SUPERVISION

COMPATIBLE CONTROL PANELS ONLY

 

)–(

OF CONNECTIONS.

 

FROM

ISOLATED, REGULATED, POWER

 

)–(

LIMITED PER NFPA 70. LISTED

 

 

CONTROL

PANEL OR

 

 

(+)

FOR FIRE PROTECTION WITH

 

(+)

MODULE

PREVIOUS

 

 

BATTERY BACKUP.

 

 

 

 

DEVICE

MODULE POLARITIES ARE

)–(

SIGNAL LINE CIRCUIT (SLC)

SHOWN IN ALARM

 

 

 

 

 

 

(+)

32 VDC MAX. TWISTED PAIR

 

 

 

IS RECOMMENDED

 

)–(

)–(

 

EOL RESISTOR

 

 

 

 

 

 

 

 

IS INTERNAL AT

 

 

 

ALL WIRING SHOWN IS SUPERVISED

TERMINALS

 

 

 

AND POWER LIMITED

 

8 & 9

 

 

 

 

 

UL LISTED EOL RELAY SHOWN ENERGIZED

24 VDC COIL EOLR-1

(+)(+)

TO NEXT CONTROL MODULE OR END-OF-LINE RELAY. ONE RELAY REQUIRED FOR EACH CIRCUIT.

SOME CONTROL PANELS HAVE RELAY BUILT IN AND DO NOT REQUIRE EXTERNAL WIRING. REFER TO PANEL MANUAL.

(–)

TO

(+)

NEXT

DEVICE

 

*NOTE: ANY FAULT IN THE POWER SUPPLY IS LIMITED TO THAT ZONE AND DOES NOT RESULT IN A FAULT IN A SEPARATE ZONE.

C0914-05

SS-460-001

2

I56-3850-002

Image 2
Contents M500S Supervised Control Module 47K EOL Resistor ELR-47K Control Module Amplifier Must Provide Wiring SS-460-001 I56-3850-002 System Sensor