The Base Network may contain a combination of up to 92 subnetworks or nodes, providing Repeaters are used between segments of 32 RS485 drivers.
Universal |
LINC485 |
Router
Subnetwork
|
|
|
| Each segment may contain up to 32 nodes. |
|
| ||
LINC485 | Universal | Repeater |
| Each subnetwork may contain 3 segments. |
|
| ||
Node 1 | Node 30 | Node 32 | Node 61 | Node 63 | Node 91 | |||
|
|
Base Network 99
Universal |
LINC485 |
Universal |
LINC485 |
Subnetwork
Router
Subnetwork
Universal | Universal |
LINC485 | LINC485 |
Node 31 | Node 62 |
Repeater | Repeater |
Nodes on the incoming side of a repeater must be lower than the repeater node. Nodes on the outgoing side of a repeater must be higher than the repeater node.
LINC485 | Universal | Repeater |
|
|
Typical LAN Configuration utilizing Universal LINC485
Connection
To provide simple connection the Universal LINC485 uses the same connectors as all YORK ISN control-
Mounting Configurations
The Universal LINC485 provides several mounting methods for greater installation flexibility. Shipped in a housing with a DIN rail mounting clip, the unit can be attached to any open DIN rail space within an existing controller. If the controller does not use DIN rail, the Universal LINC can be removed from the housing and secured inside the controller with small screws (1/8 in./4 mm or smaller).
If space is unavailable inside the controller enclosure, a small, auxiliary enclosure is available. The auxiliary enclosure includes a DIN rail to mount the Universal LINC and an accompanying 5 VDC Power Supply. (It also accepts the TDCE controllers.)
2 | YORK INTERNATIONAL |