Eco-POWER METER KW4S
System Diagram
Up to 99 Eco-POWER METERs can be connected!
or
PC used for data
gathering and management
Installation is easy using a CT even
for the power lines of existing equipment and machinery.
Power line
CT
•Please see the catalog (ARCT1E208E) for details on the Web Datalogger Unit.
•Please see the “FP series Programmable Controllers” catalog (ARCT1B230E) for details on the
Dimensions
●Eco-POWER METER KW4S
Display: Integrated electrical energy, Voltage, Current and Electricity charge
☐48
☐1.890
MODE |
| V | kWh |
S E T | CHARGE |
| A |
|
|
|
1) Pin type | 2) Screw terminal type |
| 87.5 |
|
|
5.5 | 3.445 | 14.5 | 5.5 |
| |||
.217 |
| .571 | .217 |
|
|
| (☐44.5) |
|
|
| (☐1.752) |
| 73 |
| 81.9 |
| 2.874 |
| 3.224 |
mminch
(☐44.5) (☐1.752)
Types and Specifications
●Types
|
| Current | Changes | |
| Communication protocol | Only dedicated protocol | Dedicated protocol and MEWTOCOL | |
Features added |
|
|
| |
Station number setting | 1 to 31 | 1 to 99 (Note) | ||
| ||||
|
|
|
| |
| Communication format setting | Setting start → | Setting start → Protocol switch (dedicated or MEWTOCOL) → | |
| Communication format change | Communication format change | ||
Change |
| |||
|
|
| ||
Instruction Manual | — | Above content and communication procedure added. | ||
| ||||
|
|
|
|
Note: You must use 1 to 31 when selecting the dedicated protocol
●Communication specifications
Interface |
| Conforming to RS485 | |
Protocol |
| Our method | |
Isolation status |
| Isolated with internal circuit | |
No. of connected units | 99 units* | ||
Transmission distance | 1,200m | ||
Transmission speed (Baud rate) | 2,400, 4,800, 9,600, 19,200 bps (In each setting mode, settings can be made with front panel keys.) | ||
Transmission | Data length | ||
Parity | Not available/Odd/Even (In each setting mode, settings can be made with front panel keys.) | ||
data format | |||
Stop bit | 1 bit (Fix) | ||
| |||
Communication method | Half duplex | ||
Synchronous method | |||
Terminating resistor | Approx. 120Ω (internal) |
●MEWTOCOL-COM commands
The
RD: Data area read command
WD: Data area write command
MD: Monitor data save and save reset command
MG: Monitor execute command
RT: Status read command
*We recommend the
01/2005