Features and Benefits

ƒOutlet level, phase level, and strip level current/voltage/power metering with threshold/alert capabilities*. Provides preemptive notifi cation of any impending overload issues before they occur, and simplifi es the task of installing new equipment. *(Note- measurement resolution +/- %5)

ƒCapability to remotely switch outlets through onboard web interface, DSView 3 management software (Not available on PM2000). Allows power to hung up IT equipment to be recycled, turned on or turned off remotely for faster resolution time.

ƒOn board web interface. Can be installed for direct access right out of the box or it can be confi gured as part of a larger integrated solution using the DSView 3 software.

ƒIP and Serial interface options. Options to install by connecting directly to the network or save IP connections by using the serial interface to connect directly to Avocent appliances already connected to the network.

ƒDaisy chaining. Saves the number of IP addresses or console / KVM ports that are required to manage all power distribution needs.

ƒIntegration with DSView 3 software. Single interface for management of IT equipment and IPDUs simplifi es mapping of outlets to servers and other equipment to reduce and minimize power cycling the wrong equipment.

ƒIntegration with DSView 3 Power Manager. Track historical trends to measure and monitor IT power consumption, capacity, and cost to understand what issues exist and to make more informed decisions in the future.

ƒElectronic Overcurrent Protection. Electronic Overcurrent Protection is an added layer of protection that is activated in the event of minor overloads. During such events, outlets are turned off fi rst instead of the primary overcurrent protection (OCP) tripping.

ƒSequential Startup. Protects integrity of all upstream electrical infrastructure by staggering the inrush current draw of all plugged in devices.

ƒInternal temperature sensor and two optional external sensors. These sensors can measure environmental factors at several different points within the rack.

PM2000

PM3000

 

Part Numbers

Part Numbers

Description

 

 

Ordering Details

 

 

 

 

North America

 

 

 

 

 

PM2001H-401

PM3001H-401

Horizontal 1-ph 24A 200-240V with L6-30, 3 C19 ports

 

 

 

PM2002H-401

PM3002H-401

Horizontal 3-ph 24A 200-240V with L15-30, 6 C19 ports

 

 

 

PM2005H-403

PM3005H-403

Horizontal 3-ph 40A 200-240V with Hubbell® CS8365C, 6 C19 ports

 

 

 

PM2005H-404

PM3005H-404

Horizontal 3-ph 48A 200-240V with IEC 309 60A, 6 C19 ports

 

 

 

PM2001V-401

PM3001V-401

Vertical 1-ph 24A 200-240V with L6-30, 21 C13 & 3 C19 ports

 

 

 

PM2002V-401

PM3002V-401

Vertical 3-ph 24A 200-240V with L15-30, 21 C13 & 3 C19 ports

 

 

 

PM2005V-403

PM3005V-403

Vertical 3-ph 40A 200-240V with Hubbell CS8365C, 21 C13 & 3 C19 ports

 

 

 

PM2005V-404

PM3005V-404

Vertical 3-ph 48A 200-240V with IEC 309 60A, 21 C13 & 3 C19 ports

 

 

 

 

 

 

International

 

 

 

 

 

PM2003H-401

PM3003H-401

Horizontal 1-ph 32A 220/230/240V with IEC 309 32A, 3 C19 ports

 

 

 

PM2004H-401

PM3004H-401

Horizontal 3-ph 16A 380/400/415V with IEC 309 16A, 6 C19 ports

 

 

 

PM2005H-406

PM3005H-406

Horizontal 3-ph 32A 380/400/415V with IEC 309 32A, 6 C19 ports

 

 

 

PM2003V-401

PM3003V-401

Vertical 1-ph 32A 220/230/240V with IEC 309 32A, 21 C13 & 3 C19 ports

 

 

 

PM2004V-401

PM3004V-401

Vertical 3-ph 16A 380/400/415V with IEC 309 16A, 21 C13 & 3 C19 ports

 

 

 

PM2005V-406

PM3005V-406

Vertical 3-ph 32A 380/400/415V with IEC 309 32A, 21 C13 & 3 C19 ports

 

 

 

 

 

 

Specifications

Mechanical

Size: 17 x 8.272 x 1.719 in (horizontal), 2.2 x 66 x 3.15 in (vertical)

Weight: 7.3 lbs (horizontal without power cord), 14.8 lbs (vertical without power cord)

Environmental

Operating Temperature: 50 to 122 F (10 to 50 C)

Storage Temperature: -40 to 149 F (-40 to 65 C)

Network Connection

Number: 1

Type: 10/100/1000 Ethernet

Accessories Included Rackmount kit, toolless mounting hardware with vertical models and outlet retention clips

Standards

Approved Agency:

UL, FCC, cUL, CE, VCCI, C-Tick, CB

Warranty

Two Year

PM3000

Intelligent Power Distribution Unit

External Sensors

PMHD-THS

Temperature, Humidity, Air Flow and dry contact combo sensor

PMHD-TS

Temperature only sensor

 

 

Note: PM2000 models include per outlet metering capabilities

PM3000 models include per outlet metering and switching capabilities

AMP values listed on the North American models are rated at 80% based on national electric codes.

www.avocent.com/contacts

Avocent, the Avocent logo, DSR and DSView are registered trademarks of Avocent Corporation or its affi liates in the U.S. and other countries. All other marks are the property of their respective owners.

Copyright © 2008. Avocent Corporation.

1208-PM2K3K-DS-EN

Image 2
Contents Alarms and monitoring Measure power at the Outlet levelMetering/Switching capabilities Flexible management optionsSpecifications Features and BenefitsOrdering Details

PM3000, PM2000 specifications

Avocent PM2000 and PM3000 are cutting-edge power management devices designed specifically for data centers, offering advanced monitoring and management capabilities for IT infrastructure. These products are part of Avocent’s extensive range of power management solutions that aim to enhance operational efficiency and reliability.

One of the standout features of the Avocent PM2000 and PM3000 is their real-time monitoring capability. Both models provide detailed insights into power usage, including voltage, current, power factor, and energy consumption. This information is crucial for data center managers looking to optimize energy efficiency and reduce operational costs. By capturing this valuable data, the PM series assists in identifying trends, peak usage times, and potential inefficiencies that can be addressed.

Another highlight of the PM2000 and PM3000 models is their advanced network connectivity options. They can be integrated into existing IT infrastructure with ease, utilizing protocols such as SNMP and HTTP, allowing for seamless communication with other network monitoring tools. This integration is pivotal for managing large-scale data centers, where centralized control and oversight of multiple devices are required.

The PM2000 and PM3000 also incorporate intelligent alerting features that notify administrators of any irregularities in power usage or equipment failures. These alerts can be scheduled or triggered by specific thresholds, ensuring that issues can be addressed proactively before they escalate into more significant problems. This not only enhances response times but also contributes to overall system reliability.

In terms of physical design, both models are built with a compact form factor, allowing for easy mounting in standard racks. Their robust metal casing ensures durability, making them suitable for the stringent conditions often found in data centers.

Power redundancy is also a significant aspect of the PM series. The devices are designed to support redundant power supplies, ensuring continuous operation even in the event of a power failure. This feature is critical in environments where uptime is paramount.

In summary, the Avocent PM2000 and PM3000 represent a sophisticated approach to power management in data centers. With their advanced monitoring capabilities, robust connectivity options, intelligent alerting system, durable design, and focus on redundancy, these devices contribute significantly to improving energy efficiency and operational reliability in critical IT environments. Adopting Avocent PM series solutions can lead to more effective data center management and operational excellence.