4- Maximum power allowed in parallel mode :
= 1 x Pn
+ | = 1 x Pn |
4-2 With external by-pass cubicle :
+ |
| = 2 x Pn |
|
+ | + | = 3 x Pn |
|
+ | + | + | = 3 x Pn |
Maximum power allowed with 4 UPS in parallel is 3 x Pn 5/ Parallel mode restrictions:
| G3000 single unit | G3000 parallel system |
|
EMC Level | Class B | Class A |
|
ECO mode | Yes | No |
|
Frequency converter | Yes | No |
|
Synchronisation module | No | No |
|
compatibility |
|
|
|
Remote Power Off function | Yes with UPS NT>10 | No |
|
through SolutionPac / Wan |
|
|
|
or AS4i (*) |
|
|
|
Operating system shut down | Yes with UPS NT>10 | No |
|
and UPS shut off through |
|
|
|
MGE communication |
|
|
|
products (*) |
|
|
|
Schedule UPS and systems | Yes with UPS NT>10 | No |
|
on/off through PSP or |
|
|
|
SolutionPac / Wan (*) |
|
|
|
(*) with the exception of G 3000 operating under eco mode or | |||
MGE UPS SYSTEMS |