MGE UPS Systems 3000 user manual = 1 x Pn, = 2 x Pn = 3 x Pn, With external by-pass cubicle

Page 4

4- Maximum power allowed in parallel mode :

4-1 Without external by-pass cubicle :

= 1 x Pn

+

= 1 x Pn

4-2 With external by-pass cubicle :

+

 

= 2 x Pn

 

+

+

= 3 x Pn

 

+

+

+

= 3 x Pn

Maximum power allowed with 4 UPS in parallel is 3 x Pn 5/ Parallel mode restrictions:

 

G3000 single unit

G3000 parallel system

 

EMC Level

Class B

Class A

 

ECO mode

Yes

No

 

Frequency converter

Yes

No

 

Synchronisation module

No

No

 

compatibility

 

 

 

Remote Power Off function

Yes with UPS NT>10

No

 

through SolutionPac / Wan

 

 

 

or AS4i (*)

 

 

 

Operating system shut down

Yes with UPS NT>10

No

 

and UPS shut off through

 

 

 

MGE communication

 

 

 

products (*)

 

 

 

Schedule UPS and systems

Yes with UPS NT>10

No

 

on/off through PSP or

 

 

 

SolutionPac / Wan (*)

 

 

 

(*) with the exception of G 3000 operating under eco mode or by-pass mode

MGE UPS SYSTEMS

 

4

Addenda du manuel d’installation

 

 

5103056000_AB

 

 

 

Image 4
Contents Earth wiring between parallel units Galaxy 3000 10-30 kVA N 5103037500BARJ45 RJ12Plastic nail ScrewMax .5 mm² Addenda du manuel d’installation 5103056000AB = 1 x Pn= 2 x Pn = 3 x Pn With external by-pass cubicleDe Galaxy 3000 10-30 kVA N 5103037500BA Addenda du manuel d’installation et d’utilisationRaccordement de la masse entre appareils parallèles Plot MGE UPS Systems Avec coffret By-Pass externe