APC URTA48XLBPJ, RT SURTA48XLBP Terminal Mode Configuration, Operation and Troubleshooting

Page 9

Terminal Mode Configuration

Terminal Mode Configuration

This configuration affects the accuracy of the runtime calculations that the UPS performs while run- ning on battery power.

Settings are made through supplied PowerChute® Business Edition or Terminal Mode.

Terminal mode can only be used with the serial cable provided with the UPS. If using a USB cable, disconnect the USB cable from the UPS, and connect the serial cable to

Note the UPS before using the terminal program.

Shown below is an example of how to use terminal mode to configure the number of battery packs.

1.Exit the PowerChute Business Edition software.

a.From the windows PC desktop, select START => Settings => Control Panel => Administrative Tools => Services.

b.Select APC PCBE Server and APC PCBE Agent. Right click the mouse and select Stop.

2.Open a terminal program. Example: HyperTerminal

From the computer desktop, select START => Programs => Accessories => Communication => HyperTerminal.

3.Double-click the HyperTerminal icon.

a.Follow the prompts to choose a name and select an icon. Disregard the message, “...must install a modem,” if it is displayed. Click OK.

b.Select the COM port that is connected to the UPS. The port settings are:

Bits per second - 2400

data - bits 8

parity - none

stop bit - 1

flow control - none

c.Press Enter.

4.Once the terminal window is open, follow these steps to set the number of battery packs (SURTA48XLBP or SURTA48XLBPJ):

a.Press Enter to initiate terminal mode. Follow the prompts.

b.Press 1 to modify UPS settings. Press e (or E) to modify the number of battery packs.

c.Enter the number of battery packs, including the internal UPS battery (Number of packs: 1 = internal UPS battery, 2 = one SURTA48XLBP or SURTA48XLBPJ, 3 = two SURTA48XLBP or SURTA48XLBPJ, etc.)

d.Press Enter.

e.Follow the prompts.

5.Exit the terminal program.

Operation and Troubleshooting

Refer to the “Operation” section in the UPS user manual for instructions on how to operate the UPS and battery pack.

Smart-UPS RT SURTA48XLBP/SURTA48XLBPJ External Battery Pack User Manual

9

Image 9
Contents Contact Information Safety Information Introduction/Before InstallationUnpacking and Equipment Placement About this ManualPre-installation Procedure   Tower InstallationTower Installation Rack-mount Installation Rack-mount Installation Connectors Type Description Battery Pack and UPS Connection ProcedureTvss GND Operation and Troubleshooting Terminal Mode ConfigurationTo Install a Replacement Battery Storage, Transport, and ServiceTransporting the Battery Pack to Another Location StorageService Limited Warranty Copyright Notice990-1857 06/2004

URTA48XLBPJ, RT SURTA48XLBP specifications

The APC URTA48XLBPJ and RT SURTA48XLBP represent advanced solutions in the realm of uninterruptible power supplies (UPS) designed for critical applications in data centers, telecommunications, and other industrial settings. These models are part of APC by Schneider Electric's commitment to delivering high-quality power management solutions that ensure maximum uptime for sensitive equipment.

One of the main features of the URTA48XLBPJ is its compact design, which allows for efficient space utilization in areas where real estate is at a premium. This model's versatility makes it suitable for both rack-mounted installations and floor-mounted applications, catering to a variety of operational needs. Furthermore, it is designed to support high-performance loads, ensuring stability during fluctuations in power.

The RT SURTA48XLBP is known for its robust battery management technology, which extends the life of the batteries while ensuring reliability. The intelligent battery management system helps to optimize battery performance by continually monitoring battery health and providing proactive alerts, allowing for timely maintenance or replacement before issues arise.

Both models are equipped with advanced features such as automatic voltage regulation (AVR) technology which stabilizes output voltage and protects connected equipment from surges and drops in power. The low total harmonic distortion (THD) provides clean power that is essential for sensitive electronics, ensuring that devices operate within their specifications, thus extending their lifespan.

Scalability is another key characteristic of the URTA48XLBPJ and RT SURTA48XLBP. These UPS systems can be easily expanded to accommodate growing power requirements, making them ideal for businesses that anticipate future expansion. This feature ensures that users do not have to invest in entirely new units as their infrastructure evolves.

Users will appreciate the user-friendly interface with an easy-to-read LCD display that delivers essential information such as load levels, battery status, and event logs. This real-time data empowers users to make informed decisions regarding power management, thereby optimizing efficiency.

Moreover, both models feature advanced communication options including USB and RS-232 ports, allowing for seamless integration with various monitoring and control systems. Additionally, they offer compatibility with APC's PowerChute software, further enhancing management capabilities through centralized control.

In summary, the APC URTA48XLBPJ and RT SURTA48XLBP are powerful, reliable UPS solutions that bring together cutting-edge features, robust technology, and user-friendly interfaces. These systems are designed to protect critical infrastructure, ensuring that operations remain uninterrupted, while providing flexibility and scalability for future demands.