American Power Conversion APC Silcon 240-320kW 400V manual

Page 12

Stop/Start UPS and Operating the External Service Bypass

Action

1.Set the input switch (Q001) to position 1

2.Wait 5 sec. Open the front door of the UPS and press the green ON key

3.Press on the keyboard

4.

Press

or

on the keyboard until

5.

Press

on the keyboard

6.Press on the keyboard

7.Check light indication on the bypass panel

8.Set the output switch (Q002) to position 1

9.Set the bypass switch (Q003) to position 0

10.Press on the keyboard

11.Press or on the keyboard until

12. Press

on the keyboard

13.Press on the keyboard

14.Press on the keyboard

15. Press

on the keyboard

Display shows

**System OFF**

Normal operation

load power 0%

Bypass operation

: NO

Bypass operation

: YES

Lamp indication on Bypass Panel

Green light (H002) above the output switch handle (Q002) lights up

Green light (H003) above the bypass switch handle (Q003) lights up

Only the light (H003) above the bypass switch handle (Q003) is now on

Display shows

Bypass operation

: YES

Bypass operation

: NO

Normal operation

load power 0%

All lights on the bypass panel switched off

NOTICE!

If battery has been disconnected, please refer to section 2.4.1 UPS start-up.

990-4037

12

User Guide APC Silcon 240-320kW 400V UPS

Image 12
Contents 240-320kW 400V UPS User Guide Copyright 2000 APC Denmark ApSSafety Symbols used in this manual User Guide APC Silcon 240-320kW 400V UPSThank You Contents Introduction IntroductionDisplay Unit Stop/Start UPS and Operating the External Service Bypass Normal operation Load power xx%Stop UPS for stand-by Start UPS from stand-byStop UPS for complete power down Switching off the UPSBlank Start UPS from complete power down UPS start-upSystem OFF Normal operation load power XX% Display showsOperating the External Service Bypass Switch single systems Bypassing the Single System UPSBypass operation Stop/Start UPS and Operating the External Service Bypass System OFF Normal operation Load power 0% Bypass operation Bypass operation Normal operation Load power 0%Bypassing the Parallel UPS System All UPSs Acoustic alarm sounds for 30 secs Stop/Start UPS and Operating the External Service Bypass Set input switches Q001 to position Press the green on button on all systemsPress On the keyboard Isolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Operation OperationKeyboard Using the Remote Display Display of Measured ValuesBatt. load Batt. tank Economy Mode Parameter Settings Parameter SettingsParameter Settings Switching to Bypass Operation Programming KeysProgramming Example Load power xx% Alarms and Events Alarms and EventsDisplaying the Alarm Stack Mode CommentsPossible Alarms Alarms Description ActionDisplay will show invalid UPS data Rectifying Alarm Messages Parallel Operation AlarmsCorrection of false alarm situations during service Maintenance & Testing Maintenance & TestingBattery Monitoring Test Battery Capacity TestBattery capacity Test UntilTest Xxx Press Test PressWarranty WarrantyAPC Silcon UPS Limited Factory Warranty How to Contact APC How to Contact APCAPC Corporate APC Denmark

APC Silcon 240-320kW 400V specifications

The American Power Conversion (APC) Silcon 240-320kW 400V is a cutting-edge uninterruptible power supply (UPS) system designed for high-performance applications in data centers, telecommunications, and industrial environments. This model offers a blend of advanced technology and robust design, ensuring reliability and efficiency under demanding conditions.

One of the standout features of the APC Silcon is its modular architecture, which provides flexibility in scaling power capacity to meet evolving needs. This modularity not only simplifies maintenance but also allows for hot-swappable components, minimizing downtime during service interventions. Users can easily upgrade or expand the system without the need for extensive reconfiguration.

The UPS incorporates Digital Signal Processing (DSP) technology, which enhances its performance and efficiency. By utilizing real-time monitoring and control, the Silcon UPS optimizes energy consumption, prolongs battery life, and ensures a stable output voltage. This level of sophistication contributes significantly to operational continuity and enhanced power quality.

Another vital characteristic is the high efficiency rating of the APC Silcon, typically exceeding 95%, leading to lower operational costs and reduced carbon footprint. This efficiency is particularly advantageous for large-scale operations where energy consumption can become a significant expense.

The system also features built-in battery management capabilities, improving the health and longevity of the batteries used during outages. APC Silcon employs advanced algorithms to monitor battery performance actively, ensuring timely maintenance alerts and optimizing charge cycles to prolong battery life.

To enhance user experience, the UPS is equipped with a comprehensive monitoring and management suite. This includes an intuitive graphical user interface (GUI) that provides real-time visibility into system performance, alarms, and diagnostics. Remote management capabilities allow users to monitor and control the UPS from virtually anywhere, facilitating proactive decision-making.

Moreover, the APC Silcon's robust design and high-quality components ensure exceptional reliability, making it a preferred choice in mission-critical applications where system failure is not an option. Its ability to withstand harsh environmental conditions and provide consistent power protection makes it an essential investment for businesses reliant on uninterruptible power systems.

Overall, the APC Silcon 240-320kW 400V stands out as a superior choice for organizations seeking a reliable, efficient, and flexible UPS solution to safeguard their critical operations against power disturbances and outages.