NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OR OPTIONAL SMART SLOT
ACCESSORY CARDS.
FUNCTION |
| FACTORY |
| USER SELECTABLE | DESCRIPTION | |||
| DEFAULT |
| CHOICES | |||||
|
|
|
| |||||
Low Battery Warning. |
|
|
| Brightly lit: Low battery | The low battery warning | |||
|
|
| ||||||
PowerChute interface |
|
|
| warning interval is about | beeps are continuous when | |||
|
|
| ||||||
|
|
| two minutes. | two minutes of run time re- | ||||
software provides auto- |
|
|
| |||||
|
|
| Dimly lit: | Low battery | main. | |||
matic, unattended shut- |
|
|
| |||||
|
|
| warning interval is about |
| ||||
down when approximately |
|
|
| You can change the warning | ||||
|
|
| five minutes. | |||||
two minutes (by default) of |
|
|
| interval default setting | ||||
|
|
| Off: | Low battery | ||||
battery operated run time |
|
|
| through PowerChute soft- | ||||
|
|
| warning interval is about | |||||
remains. |
|
|
| ware. | ||||
|
|
| eight minutes. | |||||
|
|
|
|
| ||||
|
|
|
|
|
| |||
|
|
|
|
|
|
|
| |
|
|
|
| Possible interval settings: |
| |||
|
|
|
| 5, 7, 10, 12, 15, 18 min- |
| |||
|
|
|
| utes. |
|
| ||
|
|
|
| |||||
Synchronized | 0 seconds | 20, 60, 120, 240, 480, | The UPS will wait the speci- | |||||
Delay |
|
|
| 720, 960 seconds | fied time after the return of | |||
|
|
|
|
|
|
|
| utility power before |
|
|
|
|
|
|
|
| (to avoid branch circuit over- |
|
|
|
|
|
|
|
| load). |
|
|
|
|
| ||||
High Transfer Point | 100V: | 100V: |
| To avoid unnecessary battery | ||||
| 108VAC | 110, 112, 114VAC | usage, set the high transfer | |||||
| 120V: | 120V: |
| point higher if the utility volt- | ||||
|
| age is chronically high and | ||||||
| 127VAC | 130, 133, 136VAC | the connected equipment is | |||||
| 230V: | 230V: |
| known to work under this | ||||
|
| condition. | ||||||
| 253VAC | 257, 261, 265VAC | ||||||
|
| |||||||
|
|
|
|
| ||||
Low Transfer Point | 100V: | 100V: |
| Set the low transfer point | ||||
| 92VAC | 86, 88, 90VAC | lower if the utility voltage is | |||||
| 120V: | 120V: |
| chronically low and the con- | ||||
|
| nected equipment can tolerate | ||||||
| 106VAC | 97, 100, 103VAC | this condition. | |||||
| 230V: | 230V: |
|
| ||||
| 208VAC | 196, 200, 204VAC |
| |||||
|
|
|
|
|
|
|
|
|