Bypass input
|
| 10 kVA |
|
UPS ratings | 380 V | 400 V | 415 V |
|
|
|
|
Input frequency (Hz)4 | 50±10 or | 50±10 or | 50±10 or |
| 60±10 | 60±10 | 60±10 |
Nominal input current (A)1 | 15.2 | 14.4 | 13.9 |
|
| 15 kVA |
|
| 20 kVA |
|
UPS | 380 V | 400 V | 415 V | 380 V | 400 V | 415 V |
ratings | ||||||
|
|
|
|
|
|
|
Input | 50±10 or | 50±10 or | 50±10 or | 50±10 or | 50±10 or | 50±10 or |
frequency 60±10 | 60±10 | 60±10 | 60±10 | 60±10 | 60±10 | |
(Hz)4 |
|
|
|
|
|
|
Nominal | 22.8 | 21.7 | 20.9 | 30.4 | 28.9 | 27.8 |
input |
|
|
|
|
|
|
current
(A)1
|
| 30 kVA |
|
| 40 kVA |
| |
UPS | 380 V | 400 V | 415 V | 380 V | 400 V | 415 V | |
ratings | |||||||
|
|
|
|
|
| ||
|
|
|
|
|
|
| |
Input | 50±10 or | 50±10 or | 50±10 or | 50±10 or | 50±10 or | 50±10 or | |
frequency 60±10 | 60±10 | 60±10 | 60±10 | 60±10 | 60±10 | ||
(Hz)4 |
|
|
|
|
|
| |
Nominal | 45.6 | 43.3 | 41.7 | 60.8 | 57.7 | 55.6 | |
input |
|
|
|
|
|
|
current
(A)1
Notes
1Input current based on rated load and batteries fully charged.
2Input current based on full battery recharge, nominal voltage and rated load.
3Current limitation through electronic current limiting is based on full battery recharge and low input voltage.
4Synchronization adjustable: ± 10Hz, ± 3Hz or ± 0.1Hz.
Recommended current protection
Note: AC input/output
| Q11 | Q3 | Q2 |
| Utility input | Bypass input | Output |
10 kVA | 16 | 16 | 16 |
15 kVA | 25 | 25 | 25 |
20 kVA | 35 | 35 | 35 |
30 kVA | 50 | 50 | 50 |
40 kVA | 63 | 63 | 63 |
1Required upstream current protection, mains input: gL type fuse.
.
Recommended cable sizes
Note: The recommended cable sizes are based on an environment with an ambient temperature of 30°C.
| Mains input | AC output | Battery input | Bypass input | |
| 2 | ] 75ºC | |||
| [mm2] | [mm2] | [mm | [mm2] | |
|
|
| Wire |
|
|
|
|
|
|
|
|
10 kVA | 2.5 | 2.5 | 50 |
| 2.5 |
15 kVA | 6 | 6 | 50 |
| 6 |
20 kVA | 10 | 10 | 50 |
| 10 |
30 kVA | 16 | 16 | 50 |
| 16 |
40 kVA | 25 | 25 | 50 |
| 25 |
Note: Use Molex lug type or equivalent, and crimp to manufacturer’s specifications.
Warning: At 100% switch mode load, the neutral must be rated for 200% phase current.
Minimum breaker settings
|
| 150% | 125% |
|
| 800% | overload | overload |
|
| overload | normal/ | normal/ |
|
| bypass | battery | battery |
|
| operation | operation | operation | Continuously |
|
|
|
|
|
10 kVA |
|
|
|
|
Mains input | – | – | 16.4 A | |
Bypass input | 121.5 A | – | – | 16.7 A |
Output | 121.5 A | 22.8 A | 19 A | 16.7 A |
Duration | 500 ms | 60 s | 10 min. | ∞ |
15 kVA |
|
|
|
|
Mains input | – | – | 24.6 A | |
Bypass input | 182 A | – | – | 25.1 A |
Output | 182 A | 34.2 A | 25.4 A | 25.1 A |
Duration | 500 ms | 60 s | 10 min. | ∞ |
20 kVA |
|
|
|
|
Mains input | – | – | 32.5 A | |
Bypass input | 244 A | – | – | 33.4 A |
Output | 244 A | 45.6 A | 38 A | 33.4 A |
Duration | 500 ms | 60 s | 10 min. | ∞ |
30 kVA |
|
|
|
|
Mains input | – | – | 49.1 A | |
Bypass input | 364 A | – | – | 50.1 A |
Output | 364 A | 68.4 A | 57 A | 50.1 A |
Duration | 500 ms | 60 s | 10 min. | ∞ |
40 kVA |
|
|
|
|
Mains input | – | – | 65.6 A | |
Bypass input | 487 A | – | – | 66.9 A |
Output | 487 A | 91.2 A | 76 A | 66.9 A |
Duration | 500 ms | 60 s | 10 min. | ∞ |
1At single feed use the higher value of mains and bypass.
Recommended lug size and torque value
Note: Power terminal lug diameter: 6 mm. Torque value: 7 Nm.
5