APC 990-2258B-001 Bypass input, Recommended current protection, Recommended cable sizes

Page 5

Bypass input

 

 

10 kVA

 

UPS ratings

380 V

400 V

415 V

 

 

 

 

Input frequency (Hz)4

50±10 or

50±10 or

50±10 or

 

60±10

60±10

60±10

Nominal input current (A)1

15.2

14.4

13.9

 

 

15 kVA

 

 

20 kVA

 

UPS

380 V

400 V

415 V

380 V

400 V

415 V

ratings

 

 

 

 

 

 

 

Input

50±10 or

50±10 or

50±10 or

50±10 or

50±10 or

50±10 or

frequency 60±10

60±10

60±10

60±10

60±10

60±10

(Hz)4

 

 

 

 

 

 

Nominal

22.8

21.7

20.9

30.4

28.9

27.8

input

 

 

 

 

 

 

current

(A)1

 

 

30 kVA

 

 

40 kVA

 

UPS

380 V

400 V

415 V

380 V

400 V

415 V

ratings

 

 

 

 

 

 

 

 

 

 

 

 

 

Input

50±10 or

50±10 or

50±10 or

50±10 or

50±10 or

50±10 or

frequency 60±10

60±10

60±10

60±10

60±10

60±10

(Hz)4

 

 

 

 

 

 

Nominal

45.6

43.3

41.7

60.8

57.7

55.6

input

 

 

 

 

 

 

current

(A)1

Notes

1Input current based on rated load and batteries fully charged.

2Input current based on full battery recharge, nominal voltage and rated load.

3Current limitation through electronic current limiting is based on full battery recharge and low input voltage.

4Synchronization adjustable: ± 10Hz, ± 3Hz or ± 0.1Hz.

Recommended current protection

Note: AC input/output over-current protection and AC input/output disconnect must be provided by the customer

 

Q11

Q3

Q2

 

Utility input

Bypass input

Output

10 kVA

16

16

16

15 kVA

25

25

25

20 kVA

35

35

35

30 kVA

50

50

50

40 kVA

63

63

63

1Required upstream current protection, mains input: gL type fuse.

.

Recommended cable sizes

Note: The recommended cable sizes are based on an environment with an ambient temperature of 30°C.

 

Mains input

AC output

Battery input

Bypass input

 

2

] 75ºC

 

[mm2]

[mm2]

[mm

[mm2]

 

 

 

Wire

 

 

 

 

 

 

 

 

10 kVA

2.5

2.5

50

 

2.5

15 kVA

6

6

50

 

6

20 kVA

10

10

50

 

10

30 kVA

16

16

50

 

16

40 kVA

25

25

50

 

25

Note: Use Molex lug type or equivalent, and crimp to manufacturer’s specifications.

Warning: At 100% switch mode load, the neutral must be rated for 200% phase current.

Minimum breaker settings

 

 

150%

125%

 

 

800%

overload

overload

 

 

overload

normal/

normal/

 

 

bypass

battery

battery

 

 

operation

operation

operation

Continuously

 

 

 

 

 

10 kVA

 

 

 

 

Mains input

1

16.4 A

Bypass input

121.5 A

16.7 A

Output

121.5 A

22.8 A

19 A

16.7 A

Duration

500 ms

60 s

10 min.

15 kVA

 

 

 

 

Mains input

1

24.6 A

Bypass input

182 A

25.1 A

Output

182 A

34.2 A

25.4 A

25.1 A

Duration

500 ms

60 s

10 min.

20 kVA

 

 

 

 

Mains input

1

32.5 A

Bypass input

244 A

33.4 A

Output

244 A

45.6 A

38 A

33.4 A

Duration

500 ms

60 s

10 min.

30 kVA

 

 

 

 

Mains input

1

49.1 A

Bypass input

364 A

50.1 A

Output

364 A

68.4 A

57 A

50.1 A

Duration

500 ms

60 s

10 min.

40 kVA

 

 

 

 

Mains input

1

65.6 A

Bypass input

487 A

66.9 A

Output

487 A

91.2 A

76 A

66.9 A

Duration

500 ms

60 s

10 min.

1At single feed use the higher value of mains and bypass.

Recommended lug size and torque value

Note: Power terminal lug diameter: 6 mm. Torque value: 7 Nm.

5

Image 5
Contents Level the Enclosure Prepare for CablesFloor Anchoring if applicable Bottom cable entryConnect the AC Input and AC Output Cables Connect the DC Battery CablesConnect the Communication Cables If applicableConnect APC communication options Battery input SpecificationsAC input AC outputBypass input Minimum breaker settingsRecommended current protection Recommended cable sizesContact Information Appendix Wiring diagrams