APC 2AP9604S manual Alarms and Events, Displaying the Alarm Stack, Displaying the Event Stack

Page 24

Alarms and Events

5.0 Alarms and Events

Alarms are indicated by the red lamp (above the left hand corner of the keyboard) and a 30 seconds acoustic signal. An alarm is registered in the alarm stack as long as it is present, and if more in the same order as they arise.

Certain alarms, such as battery alarms, need resetting. See section 4.0 Parameter Settings.

All alarms are also registered in an event logger and remains there in a stack with room for 250 events. The events are stored in the same order as they arose - showing the latest first.

Besides the alarms the following operational modes are also stored in the event logger.

Mode

Comments

MPU is reset

UPS has been completely switched off

Stand-by

UPS has been in stand-by mode by parallel system

Normal operation

UPS has been in normal operation

Battery operation

UPS has been in battery operation

Bypass operation

UPS has been in bypass operation

System off

UPS has been off

5.1Displaying the Alarm Stack

Action

 

Description

1.

Press

 

Access to the alarm stack.

2.

Press

or

Scroll up or down through the alarm stack

 

 

 

messages.

 

 

 

Last message is "No (further) alarm".

3.

Press

 

Exits the alarm stack. If not operated the system

 

 

 

will exit the alarm stack automatically after 30

 

 

 

seconds.

 

 

 

 

5.2Displaying the Event Stack

Action

1.Press

2.Press

3.Press

4.Press

 

Description

and

Press the two keys simultaneously to get access

 

to the events stack

or

Scroll up or down through the event stack

 

(last message is "No (further) event").

 

Displays the time where the event happened.

 

Exits the event stack. If not operated the system

 

will exit the event stack automatically after 30

 

seconds.

990-4055

24

User Guide APC Silcon 120-160kW 400V UPS

Image 24
Contents 120-160kW400V UPS User Guide Copyright 2001 APC JapanUser Guide APC Silcon 120-160kW 400V UPS Thank YouIntroduction IntroductionDisplay Unit Stop/Start UPS and Operating the External Service Bypass Stop UPS for stand-byStart UPS from stand-by Stop UPS for complete power down Switching off the UPSSystem OFF Start UPS from complete power down UPS start-upSystem start-up now completed Operating the External Service Bypass Switch single systems Bypassing the Single System UPSStop/Start UPS and Operating the External Service Bypass System OFF Normal operation Load power 0% Bypass operation Bypassing the Parallel UPS System All UPSs Press On the keyboard until Stop/Start UPS and Operating the External Service Bypass Set input switches Q001 to position Isolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Operation OperationKeyboard Using the Remote Display Display of Measured ValuesEconomy Mode Parameter Settings Parameter SettingsParameter Settings Switching to Bypass Operation Programming KeysProgramming Example To return to normal operation Alarms and Events Alarms and EventsDisplaying the Alarm Stack Mode CommentsPossible Alarms Alarms Description ActionAlarms and Events Rectifying Alarm Messages Parallel Operation AlarmsCorrection of false alarm situations during service Maintenance & Testing Maintenance & TestingBattery Monitoring Test Battery Capacity TestUntil Battery capacity Test Xxx Press Data stored Warranty WarrantyAPC Silcon UPS Limited Factory Warranty How to Contact APC How to Contact APCAPC Corporate APC DenmarkHow to Contact APC