Meets or Exceeds Your Specifications
W7 Specifications
Standard Specifications
Item |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Voltage Class |
|
|
|
|
|
|
|
|
|
| 460V |
|
|
|
|
|
|
|
|
|
| |||
Maximum HP | 60 |
| 75 |
| 100 |
| 125 |
| 150 | 200 |
| 250 |
| 300 |
| 400 |
| 500 |
| 600 |
| 700 | 800 | |
Drive Rating (A) | 77 |
| 96 |
| 124 |
| 156 |
| 190 | 240 |
| 302 |
| 370 |
| 480 |
| 628 |
| 753 |
| 879 | 1004 | |
Dimensions |
|
| 100”H x 30”W x 24”D |
|
|
| 100”H x 42”W x 24”D |
|
|
| Consult Factory |
| ||||||||||||
|
|
|
|
|
|
| Power Requirements |
|
|
|
|
|
|
|
|
|
|
|
| |||||
Output Frequency | 0 – 400 Hz |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Main Circuit | Three Phase 460V input |
|
|
|
|
|
| |||||||||||||||||
Control Power | DC bus control power |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
Tolerance | Voltage: ±10% Frequency: ±2% |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
| Control Specifications |
|
|
|
|
|
|
|
|
|
| |||||||
Control Method | Sine Wave PWM System – Flux Field Current Vector Control |
|
|
|
|
|
|
|
|
|
|
|
| |||||||||||
V/Hz Control | Constant Torque, Variable Torque, Open Loop Vector, Auto or Manual Torque Boost, 5 point V/Hz custom curves |
|
| |||||||||||||||||||||
Overload Rating | 120% for 60 seconds, 100% continuous |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
Frequency Setting | Encoder Potentiometer integrated into EOI, |
|
| |||||||||||||||||||||
Frequency Precision | Analog Input: ±0.2% of maximum output frequency. Digital Input: ±0.01% of maximum output frequency |
|
| |||||||||||||||||||||
Frequency Resolution | 0.01 Hz – Operation Panel. 0.1 Hz – Analog Input. |
|
|
|
|
|
|
|
| |||||||||||||||
Acceleration / Deceleration | 0.1~6000 seconds |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
Speed Regulation | Up to 0.1%, 60:1 speed range |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
Torque Regulation | 10%; less than 3% ripple from 50 to 100% range |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
Set Point Control (PID) | Proportional Gain, Integral Gain, Feedback Settings Upper/Lower Deviation Limits, Feedback Source Delay Filter, Feedback | |||||||||||||||||||||||
Settings Differential Gain |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||
Analog Inputs | Four programmable: (1) |
|
| |||||||||||||||||||||
Analog Outputs | Two programmable to 31 functions |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
Digital Inputs | Eight programmable to 67 functions |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
Output Contacts | Three output terminals, programmable to 52 functions. Form C contacts rated 250V AC, 2 amps inductive |
|
| |||||||||||||||||||||
Signal Isolation | Available (3) channel signal isolation for AM/FM outputs and II terminal input, rated at 750V |
|
|
|
|
|
| |||||||||||||||||
Control Board | RS232 / 485 and TTL ports standard |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
Communication Ports |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Data Transmission | Profibus, Devicenet, Modbus RTU, Modbus+, Metysys, TCP/IP Ethernet. (Some devices are external) |
|
|
|
| |||||||||||||||||||
Main Protective | Current limit, overcurrent, overvoltage, undervoltage, overtorque, load side short circuit, load side ground fault, heatsink |
| ||||||||||||||||||||||
Functions | overheat, ASD overload, motor overload, armature short, CPU error, open output phase, communications error, loss of feedback | |||||||||||||||||||||||
Soft Stall | Automatic load reduction control during overload |
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
Retry | Can automatically clear fault upon trip. Programmable to 10 tries, with up to 10 seconds between tries. |
|
| |||||||||||||||||||||
Restart | Restart into a rotating motor |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
|
| Interface |
|
|
|
|
|
|
|
|
|
|
|
| |||
LCD EOI (Liquid Crystal | 4 lines x 20 characters. Backlit LCD Display. Ability to display multiple parameters on one screen. Keypad may be operated from | |||||||||||||||||||||||
Display / Electronic | ||||||||||||||||||||||||
an external power source. Software is flash upgradeable. Includes |
|
|
|
| ||||||||||||||||||||
Operator Interface) |
|
|
|
| ||||||||||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
LED Indicators | Run (Red) / Stop (Green), Remote / Local (Green), DC bus charge indication (red) |
|
|
|
|
|
|
|
| |||||||||||||||
Keys | Local /Remote, Monitor / Program, Run, Enter, ESC, Stop / Reset, Up, Down |
|
|
|
|
|
|
|
| |||||||||||||||
Monitoring | Main display shows two monitored items continuously, or scrolls up to 40 items. |
|
|
|
|
|
|
|
| |||||||||||||||
Selectable Display Units | User selectable and configurable, along with scaling factor multiplier. Voltage display selectable: Amps or %, |
|
| |||||||||||||||||||||
Current display selectable: Amps or %. |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||||||
EOI Communication Ports | RS232 / 485 and TTL ports standard |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
Remote Mount Display | Remote mountable up to 1000ʼ |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
|
|
|
|
|
|
|
| Construction |
|
|
|
|
|
|
|
|
|
|
|
| ||||
Enclosure | NEMA 1, IP20, Gasketed and Filtered |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
Panel Construction | Free standing, front maintenance type, top or bottom access for motor and power cables |
|
|
|
|
|
| |||||||||||||||||
Cooling | Forced air cooled. |
|
|
|
| |||||||||||||||||||
Color |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||||
|
|
|
|
|
|
| Ambient Conditions |
|
|
|
|
|
|
|
|
|
|
|
| |||||
Ambient Temperature | 0 - 40°C, 32 - 104°F |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
Humidity | Max. 95% |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||
Altitude | 1000 m (3300 ft) above sea level or less |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||||||||
Installation | Indoor, no direct sunlight, protect for corrosive gases, explosive gases |
|
|
|
|
|
|
|
|
|
|
Standards
Electrical Performance
NEC, ANSI