Toshiba VF-PS1, VF-AS1 instruction manual 

Page 9

E 6 5 8 1 3 6 4

2.1.1.Switching circuit connection diagram, Time chart, Parameter settings

 

Inverter protective

 

Commercial power switching

 

 

F L

 

frequency hold time

 

 

action signal

Commercial power

Speed detection time

 



 

switching frequency

 

FLA

FLC

 

 

 

 



 

 

 

 

 

FLX

 

Frequency after speed is

 

 

 

Setting frequency

 

detected

 

 

(Commercial

 

 

 

 

 

(Inverter)

0Hz

 

 

 

 

power)

 

Inverter-side switching

 

S3

 

 

 

 

P24-OUT1(RY1)

 

 

 

 

 

wait time *2

 

 

 

 

for inverter run

ON

 

 

ON

S3

 

output

Commercial power

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P24-OUT2(RY2)

 

switching wait time 

 

 

 

 

 

 

 

RY1(Inverter)

MC2

for commercial

 

ON

 

 

 

power run output

 

 

 

 

 

 

Commercial power

 

 

 

 

MC2

MC3

run switching signal

 

ON

 

 

 

S3-CC

 

 

 

 

RY2(Commercial

 

Run signal

ON

 

 

ON

power)

 

F-CC

 

 

MC1

 

 

 

 

 

 

 

 

 

 

 

 

Stand-by signal

ON

 

 

 

MC3

 

ST-CC

 

 

 

F

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Inverter run

Commercial power run

Inverter run

Title

Function

Adjustment range

Setting value



Output signal selection of commercial

0 to 3

2 or 3

 

power/inverter switching

 

 



Commercial power/inverter switching

0 to 

Power supply frequency

 

frequency

 

 

*3

Inverter side switching waiting time

0.1 to 10.0 seconds

Different for each model

*3

Commercial power side switching waiting

0.37 to 10.0 seconds

0.62

 

time

 

 



Commercial power switching frequency

0.1 to 10.0 seconds

2.0

holding time

*1

Input terminal selection #6 (S2)

0 to 135

20

 

 

 

(Emergency stop)

 

 

 

102



Input terminal selection #7 (S3)

0 to 135

(Commercial power run

 

 

 

switching)

 

 

 

46



Output terminal selection #1 (OUT1)

0 to 119

(Commercial power/inverter

 

 

 

switching output 1)

 

 

 

48



Output terminal selection #2 (OUT2)

0 to 119

(Commercial power/inverter

 

 

 

switching output 2)

*1:Be careful about Items 5 and 7 in 2.2, “Precautions.”

*2:Due to internal processing timing, inverter-side wait time become 0.5 second longer than the setting value of  *3: and  are included the operation time of the relay and the magnet contactor.

In almost all cases, it is not necessary to change these parameter settings.