Toshiba E3 specifications Operating Panel and Monitor Functions

Page 5

3)Over current during normal run trip

4)Over current on the DC Bus during acceleration trip

5)Over current on the DC Bus during deceleration trip

6)Over current on the DC Bus during normal run trip

7)Load end over current trip detected at start-up (output terminals, motor wiring, etc.)

8)U-phase short circuit trip detected at start-up

9)V-phase short circuit trip detected at start-up

10)W-phase short circuit trip detected at start-up

11)Overvoltage during acceleration trip

12)Overvoltage during deceleration trip

13)Overvoltage during normal (constant speed) run trip

14)Inverter overloaded trip

15)Motor overloaded trip

16)Inverter overheat trip

17)Emergency off trip message.

18)EEPROM failure during write cycle

19)EEPROM abnormality during initial reading

20)RAM error

21)ROM error

22)CPU error

23)Communication interruption error

24)Gate array error

25)Output current detection circuit error

26)Option PCB error trip

27)Low operating current trip

28)Main circuit under voltage trip

29)Over torque trip

30)Software detected earth fault trip

31)Hardware detected earth fault trip

32)Inverter type form mismatch error

33)EEPROM type form mismatch error

2.7Operating Panel and Monitor Functions

A. The drive digital display shall be capable of monitoring the following 18 functions:

1)Post Compensation Output Frequency

2)Frequency Command Setting

3)Output Current

4)Input Voltage

5)Output Voltage

6)Torque Current

7)Excitation Current

8)PID Feedback Value

5

Image 5
Contents References ScopeSubmittal GeneralRatings and overload capability of the VFD Control FeaturesOperational Functions Input / Output Capabilities Protective FeaturesOperating Panel and Monitor Functions Communication options to include Optional featuresDrive Environmental Conditions Part 3 Start-up, Training and Warranty