4200FA XT 15/25/30/50/80 kVA UPS

Model Number

T42X3X150XAMXN

T42X3X250XAMXN

T42X3X300XAMXN

T42X3X500XAMXN

T42X3X800XAXXN

Capacity

kVA/kW

15/12

25/20

30/24

50/40

80/64

Topology

 

True On-line, Double Conversion, IGBT PWM, with Active Input Power Factor Correction

 

 

Voltage

 

208 V, 220 V, 240 V, 380 V, 415 V, 480 V, 600 V, 3 Phase, 3 w + Gnd

 

 

Voltage Range

 

+10% to -30%; +20% to -30% Online (Without Utilizing Battery)

 

Input

Power Factor

 

 

Greater than 0.99

 

 

Current THD

 

 

Less than 3%

 

 

 

 

 

 

 

 

Frequency

 

 

50/60 Hz (range 45 to 65 Hz)

 

 

 

Current Limit

 

 

115% maximum

 

 

 

Voltage

 

208 V, 220 V, 240 V, 380 V, 415 V, 480 V, 600 V, 3 Phase, 4 w + Gnd

 

 

Frequency

 

50/60 Hz ± 0.01% (Can be Used as a Frequency Converter)

 

Output

Voltage Regulation

 

< 1% balanced, 100% load step; < 2% unbalanced, 100% load step

 

 

Overload (inverter)

 

125% for 90 sec, 150% for 30 sec

 

 

 

Overload (bypass)

 

125% for 10 min, 1,000% for 10 ms

 

Battery

DC Link

 

 

288 VDC

 

 

Ripple Voltage

 

 

<.5% DC

 

 

 

 

 

 

 

 

Temperature Range

 

0 to 40°C (operating)/-20 to +50°C (storage)

 

Environment

Relative Humidity

 

 

0 to 95% non condensing

 

 

Heat Rejection

5,733 BTUs

7,600 BTUs

9,100 BTUs

17,737 BTUs

24,270 BTUs

 

 

Efficiency

 

AC/DC/AC 87.7%, DC/AC 90%

AC/DC/AC 88.5%

AC/DC/AC 90%

Dimensions

Dimensions (L x D x H)

 

20” x 36.3” x 59.8”

 

35.6” x 37.6” x 59.8”

44” x 31” x 74”

(1 / 2) Transformer(s)

UPS Weight (lb)

1,275/1,475

1,275/1,475

1,275/1,475

1,581/1,941

2,450

 

Altitude

 

6,600 ft (2000 m) (Maximum Without Derating)

 

 

Audible Noise

 

< 60 dBA at 1 m

 

< 65 dBA at 1 m

< 65 dBA at 1 m

Features

 

Internal Make-before-break Maintenance Bypass Switch*, RS232 and Dry Contact Interface

 

Options

 

 

Dual Input Feed, Air Filters for Door, RemotEye II®

 

 

Standards

 

UL 1778, cUL, NEC, ISO9001, ISO14001, ANSI C62.41 (IEEE 587), NEMA PE1-1993

 

Warranty

 

 

(See Toshiba Warranty Policy for Full Details.)

 

 

Service

 

7 x 24 Technical Support 1-877-867-8773 (1-UPS-TOS-UPS3)

 

* Not available on 80 kVA

AC Input

208-600 V,

3 Ph/3 W,

50/60 Hz

Isolation

Transformer

D

Y

Maintenance Bypass Switch

Static Bypass Switch

 

 

SYNC

 

 

MCCB

Contactor

Converter

Inverter

Contactor

 

 

 

High

 

 

High

 

Freq.

 

 

Freq.

 

Filter

 

DC Chopper/

Filter

 

 

 

Charger

 

-BeforeBreak-

Output

Make

Transformer

 

 

Y

Y

UPS Cabinet

AC Output

208-600 V

3 Ph/4 W,

50/60 Hz

External Battery Cabinet(s) or Rack(s) with DC Breaker

UPS ADJUSTABLE SPEED DRIVES MOTORS CONTROLS INSTRUMENTATION PLC

Available Through:

INDUSTRIAL DIVISION

13131 West Little York Road, Houston, Texas 77041

Tel 713/466-0277

Fax 713/466-8773

US 800/231-1412

Canada 800/872-2192 Mexico 001/800/527-1204

www.toshiba.com/ind

Copyright 11/2006

*UPS4200FAXT061118*

Image 2
Contents 4200FA Series Features BatteryDimensions Warranty