For replacement parts information or an application guide, visit our website at www.sea.siemens.com or contact your local Siemens sales office.
Instructions |
| |
| IMPORTANT |
|
May, 2002 | THESE INSTRUCTIONS DO NOT PURPORTTO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT, NOR TO PROVIDE FOR EVERY POSSIBLE | Class 87 |
CONTINGENCY TO BE MET IN CONNECTION WITH INSTALLATION, OPERATION OR MAINTENANCE. SHOULD FURTHER INFORMATION BE | ||
Supersedes Issue of | DESIRED OR SHOULD PARTICULAR PROBLEMS ARISE WHICH ARE NOT COVERED SUFFICIENTLY FOR THE PURCHASER’S PURPOSES,THE |
|
MATTER SHOULD BE REFERRED TO THE LOCAL SIEMENS SALES OFFICE. |
| |
April, 2002 | THE CONTENTS OF THIS INSTRUCTION MANUAL SHALL NOT BECOME PART OF OR MODIFY ANY PRIOR OR EXISTING AGREEMENT, COM- |
|
| MITMENT OR RELATIONSHIP. THE SALES CONTRACT CONTAINS THE ENTIRE OBLIGATION OF SIEMENS. THE WARRANTY CONTAINED IN |
|
| THE CONTRACT BETWEEN THE PARTIES IS THE SOLE WARRANTY OF SIEMENS. ANY STATEMENTS CONTAINED HEREIN DO NOT CREATE |
|
| NEW WARRANTIES OR MODIFY THE EXISTING WARRANTY. |
|
Description
Class 87 pump control panels include a Class 14 magnetic starter with either a circuit breaker or a fusible disconnect switch, a START push button and a
The Class 87 pump control panel can be supplied with either Class 10 ESP100 quick trip solid state overload or a ambient temperature compensated bimetal overload.
Enclosures for Sizes 1 through 4 are furnished with pole mount- ing brackets: Size 5 with floor mounting legs. Size 6 is base mounted.
Pump panel optional accessories include
Installation
1.Examine each device on the panel for shipping damage and if any is noted, notify carrier for claim. Do not apply power
| to any damaged device. | 11. | Make a final installation check of steps 1 through 10 and |
|
| ||
2. | Operate disconnect switch or circuit breaker with external |
| remove any foreign material from the enclosure. |
| handle to verify operation. | 12. | Close and latch door before applying power. |
|
| ||
3. | Manually operate magnetic starter to determine that moving | 13. | Apply power by placing the disconnect handle in the ON |
| parts do not bind. | ||
|
| position. | |
|
|
| |
4. | Check horsepower and current rating of motor or other load | 14. | Rotate selector switch to HAND position and depress |
| with pump control panel rating. | ||
|
| START button. | |
|
|
| |
5. | Install in conformance with National Electric Code and any | 15. | Check for proper pump motor rotation. Motor rotation can |
| applicable local electric codes. Install the proper size dual | ||
|
| be reversed by interchanging any two (motor) leads at the | |
| element fuses in the disconnect switch (fuses are not sup- |
| |
|
| starter load connections. | |
| plied as part of pump control panels). |
| |
|
|
| |
6. | Firmly fasten enclosure to solid mounting surface. | General Maintenance |
7.Install conduits and necessary grounding means and wire pump control panel in accordance with the wiring diagram
| supplied. Joint compound or the equivalent is recommend- | Hazardous voltage. | |
| ed on conduit threads to prevent water from entering pump | Can cause death, serious personal | |
| control panel. If top conduit hub is not used, be sure to plug | injury, or property damage. | |
| it securely to prevent entrance of water. | Disconnect power before working on | |
8. | Check that all wiring is secure and does not interfere with | this equipment. | |
|
| ||
|
| ||
| proper operation of any devices. | In many applications, the magnetic control can be expected to | |
|
| ||
9. | Check that all wiring connections are tight, including factory | be trouble free during the entire operating life of the pump. | |
| connections. | Routine inspection and maintenance as follows will help to | |
10. | Refer to the heater table on the door of the enclosure and | insure this. | |
|
| ||
| install the proper overload heaters for the specific motor | 1. Periodically clean the inside of the enclosure by blowing out | |
| being controlled (heaters are not supplied as part of pump | dust, etc. which may have accumulated. | |
| control panels). |
|
|
|
| (For Engineering Reference Only - Rev. E) |