GE TR5451, TR5452 operation manual Voltage Ratings & Power Source Configurations, Mounting

Page 2

PRE-INSTALLATION REQUIREMENTS (CONT.):

system. Refer to the VOLTAGE RATINGS & POWER SOURCE CONFIGURATIONS” chart below. The TVSS model number can be found on the front of the unit.

Verify that an NEC (National Electrical Code) compliant X0 bond has been made at the upstream transformer that feeds the electrical supply panel. Per NEC 250.30, this bond must be in place on all grounded electrical systems.

The TR5451 or TR5452 model TVSS must be installed on a dedicated branch circuit breaker. The maximum allowable rating for the circuit breaker is 30A / 22kAIC.

Do not attempt to install the TVSS on the upstream (line) side of the Main Breaker or

Fuse.

The TVSS should only be installed indoors in NEMA 1 type locations. Do not install the TVSS outside or in wet locations.

VOLTAGE RATINGS & POWER SOURCE CONFIGURATIONS

MODEL

NOMINAL

MAXIMUM

 

SYSTEM

SOURCE

CONTINOUS RMS

VOLTAGE

TYPE

OPERATING

 

TYPE

CONFIGURATION

(50/60hZ)

 

 

 

VOLTAGE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L1

TR5451ACT451--120

120V

150V (L-N / L-G)

 

 

 

 

 

 

 

Single Phase

 

 

 

 

 

 

2 Wire + Ground

N

ACT 451-240

240V

270V (L-N / L-G)

 

TR5451-240

 

 

 

 

 

ACT452-120

 

150V (L-N / L-G)

 

L1

 

 

 

ACTTR5452-120

120V

150V (L-N / L-G)

Split Phase

N

3 Wire + Ground

 

 

 

 

 

 

ACT452-240

240 / 480V

270V (L-N / L-G)

 

L2

INSTALLATION:

 

 

 

 

 

 

 

 

 

POWER MUST BE PROVEN DISCONNECTED BEFORE

 

 

 

STARTING INSTALLATION, INSPECTION OR MAINTENANCE!

 

 

 

FAILURE TO DO SO MAY CAUSE SERIOUS INJURY, DEATH

 

 

 

AND/OR PROPERTY DAMAGE.

 

 

903-640-0555

Before attempting installation, make sure that the pre-

 

800-950-2281

installation requirements of this manual have been satisfied.

FOR INDOOR USE ONLY

 

If the status of the pre-installation requirements are not

LISTED (48E6)

 

 

 

 

 

UL 1449, 2ND EDITION

 

known, do not attempt to continue.

 

NOTE: If lamp is out, replace unit

 

 

DUAL PHASE TVSS

 

 

 

 

 

 

120 VAC 50/60HZ

 

 

MOUNTING

 

 

330 L-N

 

 

 

 

SUPPRESSION VOLTAGES

 

 

 

 

 

600 L-L

 

 

 

 

 

 

TVSS

 

 

1.

TR5451 and TR5452 TVSS units are designed to be

PART# ACT452120210N

 

 

DATE CODE: WO#

 

 

 

 

 

 

 

 

 

mounted directly to the electrical panel through a ½”

 

 

 

knockout. Mounting feet are also supplied for instances

 

 

Spacer

where direct connection to the panel is not practical. Select

Electrical

 

a location that will allow the closest proximity to the breaker

 

Threaded

that the TVSS will be connected to.

Panel

 

2. Use the ½” threaded fitting and spacer to secure the

 

 

Fitting

 

 

 

TVSS to the Electrical Panel that is to be protected.

2020003701

(08/06)

 

 

 

Page 2 of 4