Toshiba T1 manual Configure T-PDS

Page 3

Click on the “Computer Link” button in the System Parameters screen, and the “ComputerLink Setup” menu will appear. Select a station number for the PLC, then click the “Communication Parameter” button . Select “NON” parity setting, and then click the “OK” buttons. When the “Write OK” screen appears, click “OK.”

Now go to the PLC/Memory Management menu and select “Write to EEPROM.” The Computer Link parameters will now be stored in EEPROM memory. If you have a T2E, set the “COM” dip switch on the front of the module to the right-hand position and then cycle power on the PLC. This will set the T2E programming port up for no parity.

STEP 2: CONFIGURE T-PDS:

Now that the PLC configuration is done, we will now do the T-PDS configuration on the PC. We will need to go “Offline” and set the T-PDS communication parameters as follows:

Go to the Options/Communication menu and set the above parameters. Remember that we set the PLC Computer Link station address as 1 on the previous page. Be sure to select “NON” parity here. Check the “Use Modem” box and click the “Control” button to get to the next screen.

Page 3

Image 3
Contents Toshiba International Corporation Modem Communications with the T1 and T2E/T2NConfigure the PLC Configure T-PDS Page Configure the PLC’s Modem