ADTRAN Quad BNC specifications Installation, Connections, Maintenance

Page 3

3. INSTALLATION

C A U T I O N !

SUBJECT TO ELECTROSTATIC DAMAGE

OR DECREASE IN RELIABILITY.

HANDLING PRECAUTIONS REQUIRED.

After unpacking the unit, inspect it for damage. If damage is discovered, file a claim with the carrier, then contact ADTRAN. Refer to Warranty and Customer Service.

Two phillips-head captive screws are provided with the Quad BNC Adapter Module. Use the screws and a phillips screwdriver to attach the Quad BNC Adapter Module to the back of the Total Access 3000 or Total Access 3010 chassis with the screw spacer between the Quad BNC Adapter and the chassis surface.

CAUTION

This module should never be installed while power is present on the chassis. Doing so can cause damage to the backplane during installation.

To be UL 1950 certified, ADTRAN requires that these installation guidelines be followed:

The Quad BNC Adapter Module is intended for installation in Restricted Access Locations Only.

The Quad BNC Adapter Module must be installed in accordance with the requirements of NEC NFPA 70.

4. CONNECTIONS

Coax cable is easily connected to the Quad BNC Adapter Module. The RX connectors on the Quad BNC Adapter Module connect to the two EC-1 signals coming from the network. Similarly, the TX connectors on the Quad BNC Adapter Module connect to the two EC-1 signals going to the network.

To be UL 1950 certified, ADTRAN requires that the following connection guidelines be observed:

The Total Access chassis must be connected to a reliably grounded -48 VDC source which is electrically isolated from the AC source.

The frame ground stud located on the chassis must be connected to a reliable frame ground source.

A readily accessible disconnect device that is suitably approved and rated must be incorporated into the fixed power wiring (e.g., Fuse and Alarm Panel).

The branch circuit overcurrent protection

must be a properly sized fuse or circuit breaker rated for −48 V.

5.MAINTENANCE

The ADTRAN Total Access Quad BNC Adapter Module does not require any routine maintenance for normal operation. ADTRAN cautions against performing major repairs in the field. Repair services may be obtained by returning the defective unit to ADTRAN. (Refer to the Warranty and Customer Service section of this practice.)