APC AP9810 manual Form C relay ratings

Page 3

Connecting a device to the Output terminals on the screw terminal block

Note: The Form C relay is not intended to switch AC loads directly (see the ratings below).

Form C relay ratings

Normal switching capacity

1

A at 30 VDC

Maximum switching power

30 W

Maximum switching voltage

60 VDC

Maximum switching current

2

Adc

Maximum carrying current

2

Adc

Surge ratings

2 kV per Bellcore; TA-NWT-001089

 

1.5 kV per FCC part 68

If you are connecting two Dry Contact I/O Accessories to a

Management Card 2, you have two options:

• Connect a device to the Output terminals for each Dry Contact I/O Accessory separately.

• Connect the Dry Contact I/O Accessories in the same circuit to implement AND or OR logic (see the diagram to the right). For example, if one Output changes state when the host reports a Replace Battery alarm and the other Output changes state when the host reports a Fault alarm, you can connect the Dry Contact I/O Accessories so that the device detects a change in state when only one alarm occurs (OR logic) or when both alarms occur simultaneously (AND logic).

Dry Contact I/O Accessory (AP9810) Technical Guide

3

Image 3
Contents Installation OverviewDescription Dry Contact I/O Accessory AP9810 Technical Guide Form C relay ratings Environmental SpecificationsElectrical Physical