DIN-191 & DIN-192 USERS MANUAL 8

FIGURE 4. DIN-192 jumper locations.

FACTORY RS-485 TERMINATION SETTINGS

Each DIN-191 and DIN-192 contains internal pin strips for enabling the internal termination and biasing resistors. Each pc board is clearly marked with the jumper designators adjacent to each row of pins. The jumper designators are +1K, 220 and -1K. To enable any resistor, place a jumper over the pins next to the required designator. The factory switch and jumper settings are outlined below.

DIN - 191:

Baud Rate: 300 baud switch up.

Biasing Resistors: +1K, -1K jumpers installed.

Termination Resistor: 220 jumper installed.

DIN - 192:

Baud Rate: 300 baud switch up.

RS-485 (J3): Biasing Resistors: +1K, -1K jumpers installed. Termination Resistor: 220 jumper installed.

Isolated RS-485 (J2): Biasing Resistors: +1K, -1K jumpers installed. Termination Resistor: 220 jumper not installed.

Image 9
Contents User’s Guide Servicing North America Converter Boxes General Description Specification S Mechanicals and DimensionsDIN 191 Connectors Page RS 485 Terminations Baud RateRS-485 biasing & termination resistors RS-485 Termination & Biasing SettingsDIN Factory RS-485 Termination SettingsWARRANTY/DISCLAIMER Shop online at omega.com