York H4CE180A40 installation instructions Supplemental Installation Instructions, Scope

Page 1

035-17392-000 REV. A (0401)

SUPPLEMENTAL INSTALLATION INSTRUCTIONS

MODEL H4CE180A40 (380V-3-60 Hz Electrical Supply)

SPLIT-SYSTEM CONDENSING UNITS (EXPORT)

Scope

This installation Instruction Supplement provides information specific to Model H4CE180A40. For all other information regarding the installation and operation of this unit, refer to Installation Instruction Form 035-17384-000.

Approvals

As unit is for Export, it is not certified by ETL or CGA.

TABLE 3: Electrical Data

Model

Voltage

Power

 

Compressor

 

Condensing Fan

Minimum Cir-

Maximum Fuse Size.

 

 

 

 

 

 

Sys. #1

Sys. #2

 

 

HCE

Code

Supply

HP

FLA (See Notes)

cuit Ampacity

Amps (See Note 2)

 

 

 

 

 

 

 

RLA

LRA

RLA

LRA

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

180

40

380-3-60

16.7

123

16.7

123

1.0 EA.

2.5 EA.

42.6

50

 

 

 

 

 

 

 

 

 

 

 

NOTES:1. Condenser Fan Motors are supplied by one (1) autotransformer (p/n 025-32756-000) used to elevate 380 volt supply to 475 volt. Full load Amp rating at 460-3-60 supply is 2.4 amp rating at 380 volt supply terminals of autotransformer is 2.6.

2.Dual Element time delay type fuses or HACR circuit breakers. Refer to NEC/NFPA No. 70, Articles 440-11 & 12 for information on disconnect size.

J￿

Subject to change without notice. Printed in U.S.A.

 

035-17392-000 REV. A (0401)

Copyright © by Unitary Products Group 2000. All rights reserved.

 

Supersedes: 035-17318-000 Rev. A (10/00)

Unitary

5005

Norman

Product

York

OK

Group

Drive

73069

Image 1
Contents SPLIT-SYSTEM Condensing Units Export Supplemental Installation InstructionsScope Approvals