GE A016-1CG manual Configuration the C3000/C0300 DPA A016ACC Table, A016ACC Table Fields

Page 29

Chapter 9: Configuration the C3000/C0300 DPA A016_ACC Table

This chapter describes entries the user must provide in the A016_ACC table found in the C3000/C0300 DPA configuration.

The A016_ACC table provides information for system accumulator input points, which are used by the C3000/C0300 DPA. The table contains one record for each system accumulator input point to customize the usage of the point. The fields contained in the table are described in the following table:

Field

 

 

Range

 

 

Description

 

 

 

 

 

 

 

 

 

ACC Point

 

 

Any valid system

 

 

The system accumulator input point number, which is used as the source for a

 

 

 

Accumulator Input point

 

 

scan section. The high entry limit is confined to the highest system accumulator

 

 

 

 

 

 

 

 

 

 

or Undefined (-1).

 

 

input point configured in the system. Entering -1 causes the LRU to always

 

 

 

 

 

 

 

return a zero value for this point as it is not mapped to a real system

 

 

 

 

 

 

 

accumulator input point.

 

 

 

 

 

 

 

 

 

Type

 

 

12 bit Accumulator

 

 

Sets the accumulator to indicate that this record entry is either the top (Upper

 

 

 

Upper 12 bits

 

 

 

 

 

 

 

 

12 bits) or bottom part (Lower 12 bits) of a 24 bit accumulator. Setting to 12

 

 

 

 

Lower 12 bits

 

 

 

 

 

 

 

 

bit Accumulator indicates that the whole accumulator is only 12 bits long.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Freeze Enable

 

 

Yes or No

 

 

No indicates that master requests for accumulator freeze does not cause

 

 

 

 

 

 

 

transfer of running count buffer to frozen count buffer, Yes otherwise.

 

 

 

 

 

 

 

 

 

Freeze-reset

 

 

Yes or No

 

 

No indicates that master requests for accumulator freeze with reset does not

 

Enabled

 

 

 

 

 

cause zeroing of the running count buffer, Yes otherwise.

 

 

 

 

 

 

 

 

 

Counting

 

 

Transition, Pulse

 

 

Pulse indicates that pulse counting method is used in providing values to the

 

Method

 

 

 

 

 

master station. Transition indicates that transition counting method is used in

 

 

 

 

 

 

 

providing values to the master station. Note that two transitions (changes of

 

 

 

 

 

 

 

state) of the accumulator input point is counted as a pulse.

 

 

 

 

 

 

 

 

 

Counter Source

 

 

Frozen buffer, Running

 

 

Indicates if the running or frozen buffer is used in providing values to the

 

 

 

buffer

 

 

 

 

 

 

 

 

master station.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Table 10 A016_ACC Table Fields

General

A016-1CG-1.00-2

Full

17

 

Image 29
Contents Custom ABB C3000/C0300 DPA Configuration GuideTrademark Notices Table of Contents Fatal Error Messages System Overview Xii List of FiguresCustom ABB C3000/C0300 DPA List of Tables Viii Purpose of this Guide About this GuideAdditional Documentation Overview Xii Name and Description of Tables Used Configuration TablesConfiguration Sequence C3000/C0300 A016COM Configuration Table Configuration the Port Configuration Table A016COMCharacter Times at the selected Baud Rate C3000/C0300 A016XRF Configuration Table Configuring the C3000/C0300 DPA A016XRF TableCustom ABB C3000/C0300 DPA A016LRU Table Fields Configuring the C3000/C0300 DPA A016LRU TableCustom ABB C3000/C0300 DPA A016GRP Table Fields Configuring the C3000/C0300 DPA A016GRP TableCustom ABB C3000/C0300 DPA Configuring the C3000/C0300 DPA A016SCAN Table A016SCAN Table Fields A016DI Table Fields Configuring the C3000/C0300 DPA A016DI TableCustom ABB C3000/C0300 DPA A016AI Table Fields Configuring the C3000/C0300 DPA A016AI TableGE Power Systems A016ACC Table Fields Configuration the C3000/C0300 DPA A016ACC TableGE Power Systems A016TC Table Fields Configuring the C3000/C0300 DPA A016TC TableCustom ABB C3000/C0300 DPA A016RL Table Fields Configuring the C3000/C0300 DPA A016RL TableGE Power Systems A016SP Table Fields Configuring the C3000/C0300 DPA A016SP TableGE Power Systems Appendix a Error Messages Remedy WhyERR 1102 Create Exchange FAIL, ERR= ERR 1100 WIN Open FAIL, ERR=ERR 1106 Error Attaching to Semaphore Why ERR 1104 Error creating message exchangeERR1200 Port TASK, Cant Open Port xx Why ERR1201 Port TASK, Cant Init PortERR 1400 Setpoint Task WIN Open ERR = ERR 1300 LRU Task WIN Open ERR =ERR 2000 Invalid Baud RATE, REC ERR 2001 Invalid PRE TX MARK, RECERR 2003 Invalid Comm Fail POINT, REC ERR 2002 Invalid Post TX SPACE, RECERR 2004 Invalid Comm Fail TIME, REC ERR 2005 Invalid XRF OFFSET, RECERR 2007 Invalid OFFSET/COUNT, REC ERR 2006 Invalid LRU COUNT, RECERR 2008 Duplicate LRU ADDRESS, REC ERR 2100 Invalid ADDRESS, RECERR 2200 Invalid LOCAL/REMOTE POINT, REC ERR 2101 Invalid OFFSET, RECERR 2201 Invalid Local STATE, REC ERR 2202 Invalid Freeze POINT, RECERR 2203 Invalid Freeze DURATION, REC ERR 2204 Invalid T/C TIMEOUT, RECERR 2206 Invalid Group OFFSET, REC ERR 2207 Invalid Group COUNT, RECERR 2301 Invalid Scan COUNT, REC ERR 2208 Invalid Group OFFSET/COUNT, RECERR 2300 Invalid Group NUMBER, REC ERR 2303 Invalid Scan OFFSET/COUNT, REC ERR 2302 Invalid Scan OFFSET, RECERR 2304 Invalid T/C COUNT, REC ERR 2305 Invalid T/C OFFSET, RECERR 2307 Invalid R/L COUNT, REC ERR 2306 Invalid T/C OFFSET/COUNT, RECERR 2308 Invalid R/L OFFSET, REC ERR 2309 Invalid R/L OFFSET/COUNT, RECERR 2311 Invalid S/P OFFSET, REC ERR 2310 Invalid S/P COUNT, RECERR 2312 Invalid S/P OFFSET/COUNT, REC ERR 2313 not Master ECHO, RECERR 2400 Invalid Section TYPE, REC ERR 2314 Invalid SOE Group Method RECERR 2401 Invalid Table OFFSET, REC ERR 2500 Invalid POINT, RECERR 2600 Invalid POINT, REC ERR 2501 Invalid OPTIONS, RECERR 2601 Invalid MODE, REC ERR 2602 Invalid RANGE, RECERR 2604 Invalid OFFSET, REC ERR 2603 Invalid DIVISOR, RECERR 2605 Invalid DEADBAND, REC ERR 2606 Invalid LIMIT, RECERR 2800 Invalid Point NUMBER, REC ERR 2700 Invalid POINT, RECERR 2701 Invalid OPTIONS, REC ERR 2802 Invalid Close DURATION, REC ERR 2801 Invalid Trip DURATION, RECERR 2803 Invalid Operation MODE, REC ERR 2900 Invalid Raise POINT, RECERR 2902 Invalid Raise INC DURATION, REC ERR 2901 Invalid Raise Base DURATION, RECERR 2903 Invalid Lower POINT, REC ERR 2904 Invalid Lower Base DURATION, RECERR 3000 Invalid Point NUMBER, REC ERR 2905 Invalid Lower INC DURATION, RECERR 3001 Invalid OPTIONS, REC ERR 3002 Invalid RANGE, RECERR 3003 Invalid DIVISOR, REC ERR 3006 Invalid Delay TIME, RECERR 3004 Invalid OFFSET, REC ERR 3005 Invalid Operate TIME, RECCustom ABB C3000/C0300 DPA

A016-1CG specifications

The GE A016-1CG is a cutting-edge product from General Electric, renowned for its innovative design and advanced features suitable for various industrial applications. This model exemplifies GE's commitment to integrating modern technology with strong engineering principles, resulting in a versatile and efficient option for users across multiple sectors.

One of the main features of the GE A016-1CG is its robust construction, designed to withstand rugged environments while maintaining optimal performance. The device is built using high-quality materials, ensuring longevity and reliability in demanding situations. Its modular design allows for easy maintenance and scalability, making it an ideal choice for companies looking to future-proof their operations.

In terms of technology, the A016-1CG incorporates state-of-the-art digital control systems. This allows for precise monitoring and management of operational parameters, enhancing efficiency and reducing the risk of downtime. The system’s user-friendly interface makes it easy for operators to access critical information and adjust settings on-the-fly, facilitating quick adaptation to changing operational demands.

Another significant characteristic of the GE A016-1CG is its energy efficiency. Designed with sustainability in mind, this model minimizes energy consumption while delivering high performance. Integrated energy-saving technologies allow users to reduce their carbon footprint and operational costs, making the A016-1CG not just a powerful tool, but also an environmentally conscious choice.

The A016-1CG is also equipped with advanced connectivity features. Its compatibility with IoT (Internet of Things) systems enables seamless integration into smart factory environments. This connectivity allows for real-time data collection and analysis, providing insights that can drive further efficiency and productivity.

Finally, the GE A016-1CG offers extensive customization options. This adaptability ensures that businesses can tailor the device to meet their specific needs and workflows, enhancing overall functionality. With comprehensive support and service options from General Electric, users can be assured of optimal performance and long-term satisfaction.

In conclusion, the GE A016-1CG stands out as a leading choice in its category, combining strength, advanced technology, energy efficiency, and customization to support varied industrial applications. Its focus on reliability and operational excellence makes it a significant asset for businesses looking to improve their productivity and efficiency.