5. FMG-3000 Magmeter Configuration
Whether using the
When the cover is removed the wiring from the sensor can be seen connected to the smaller terminal block. These connections should always remain connected to prevent inadvertent damage or miswiring.
The terminals on the
|
| Connect output cables to |
JP2 is for factory use only. |
| |
| this | |
MAKE NO CONNECTIONS. |
| |
|
|
|
This blue jumper must be in place for the magmeter to operate correctly.
JP2
| Blue | |
4 | Brown | |
3 | Black | |
Red | ||
2 | ||
Yellow | ||
1 | White | |
Not used | ||
|
The factory connects
the sensor cable to the terminals inside the yellow cover.
WARNING!
If the second conduit port is used, carefully drill the opening. (The plastic is too strong to be punched out.)
• | Secure the Magmeter in a vise to |
| prevent damage or injury. |
• | The plastic inside the port is very |
Set this blue jumper according to the pipe size.
½in. (DN15) ¾ in. (DN20) 1 in. (DN25) 1¼ in. (DN32) 1½ in. (DN40)
2 in. (DN50) 2½ in. (DN65) 5 in. (DN125) 6 in. (DN150) 10 in. (DN250) 12 in. (DN300)
External Earth Ground Terminal
thin. Do not allow the drill to |
penetrate too deeply and damage |
the Magmeter wiring. |
3 in. | (DN80) |
|
4 in. | (DN100) | Flow |
8 in. | (DN200) |
|
FP-LTC
Liquid tight connector (one supplied)
Use the yellow decal to mark the direction of flow on the pipe
Flow
Sensor grounding ring
Important:
•The directional arrow on the body of the sensor must be pointed DOWNSTREAM.
•The FLOW arrow decal can be placed directly on the pipe to identify the direction of fl ow.
•Use a cable gland or a liquid tight connector to seal the cable ports from water intrusion.
•The yellow housing may be reversed to align the conduit ports as required.
•If the Magmeter is installed on a vertical pipe, the conduit ports should be turned to point downward. This will prevent condensation from being channeled into the enclosure.
•Use plumber's tape or a suitable sealant on cable ports.
4