5. FMG-3000 Magmeter Configuration

Whether using the FMG-3000 (frequency or 4-20 mA output) the wiring terminals located on the inside of the yellow cover are identical. All of the connections from the Magmeter to external equipment (Datalogger, Chart Recorder, Flow meter, etc.) are made at the large 4-position terminal connector.

When the cover is removed the wiring from the sensor can be seen connected to the smaller terminal block. These connections should always remain connected to prevent inadvertent damage or miswiring.

The terminals on the FMG-3000 Magmeter are designed for conductors from 16 AWG to 22 AWG.

 

 

Connect output cables to

JP2 is for factory use only.

 

 

this 4-terminal block.

MAKE NO CONNECTIONS.

 

 

 

 

This blue jumper must be in place for the magmeter to operate correctly.

JP2

 

Blue

4

Brown

3

Black

Red

2

Yellow

1

White

Not used

 

The factory connects

the sensor cable to the terminals inside the yellow cover.

WARNING!

If the second conduit port is used, carefully drill the opening. (The plastic is too strong to be punched out.)

Secure the Magmeter in a vise to

 

prevent damage or injury.

The plastic inside the port is very

Set this blue jumper according to the pipe size.

½in. (DN15) ¾ in. (DN20) 1 in. (DN25) 1¼ in. (DN32) 1½ in. (DN40)

2 in. (DN50) 2½ in. (DN65) 5 in. (DN125) 6 in. (DN150) 10 in. (DN250) 12 in. (DN300)

External Earth Ground Terminal

thin. Do not allow the drill to

penetrate too deeply and damage

the Magmeter wiring.

3 in.

(DN80)

 

4 in.

(DN100)

Flow

8 in.

(DN200)

 

FP-LTC

Liquid tight connector (one supplied)

Use the yellow decal to mark the direction of flow on the pipe

Flow

Sensor grounding ring

Important:

The directional arrow on the body of the sensor must be pointed DOWNSTREAM.

The FLOW arrow decal can be placed directly on the pipe to identify the direction of fl ow.

Use a cable gland or a liquid tight connector to seal the cable ports from water intrusion.

The yellow housing may be reversed to align the conduit ports as required.

If the Magmeter is installed on a vertical pipe, the conduit ports should be turned to point downward. This will prevent condensation from being channeled into the enclosure.

Use plumber's tape or a suitable sealant on cable ports.

4

Image 6
Contents User’sGuide Internet e-mail info@omega.com Servicing North America Quick Start Guide TopicSpecifications Installation Pipe fittings Selecting a LocationFMG-3000 Magmeter Configuration Make no ConnectionsGeneral Installation and Grounding Tips Sensor conditioningGrounding Type Wiring the FMG-3001 and FMG-3101 with Frequency outputPipe Size Fitting SCH 80 Iron Saddle on SCH 80 PipeSCH 80 PVC Saddles for SCH 80 PVC Pipe SCH 80 PVC Tees for SCH 80 PVC PipeSCH 80 PVC Tees for SCH 80 Cpvc Pipe SCH 80 PVC Saddles for SCH 40 PVC PipePolypropylene Fittings DIN/ISO ,BS, Ansi Pvdf Fittings DIN/ISO ,BS, AnsiStainless Steel Weldolets on SCH 40 Pipe Carbon Steel Tees on SCH 40 PipeStainless Steel Tees on SCH 40 Pipe Carbon Steel Weldolets on SCH 40 PipeCopper Tees Fitting on Copper Pipe SCH K Bronze and Copper Tees and BrazoletsBronze Tees on SCH 40 Pipe Copper Tees Fitting on Copper Pipe SCH LTroubleshooting with the RED and Blue lights MaintenanceSymptom Possible Cause Possible Solution TroubleshootingOmegamag with Frequency Output Replacement Parts and AccessoriesOrdering Information Omegamag with 4-20 mA Loop OutputWARRANTY/DISCLAIMER OMEGA…Of Course