Enerco MH170FAVT operating instructions Operating Precautions, Safety Precautions

Page 3

OPERATING PRECAUTIONS

This is a propane, direct-fired, forced air heater. It's intended use is primarily temporary heating of buildings under construction, alteration or repair.

Propane is heavier than air. If propane leaks from a connection or fitting, it sinks to the floor, collecting there with the surrounding air, forming a potentially explosive mixture. Obviously, propane leaks should be avoided, so set up the propane supply with utmost care. Read enclosed Odor Fade and Propane Sheet for additional information about detecting propane leaks. Leak check new connections or reconnections with a soap and water solution and follow all connection instructions herein. Also, ask your propane dealer for advice on the propane application and supply installation and ask him to check it if there are any questions.

This heater was designed and certified for use as a construction heater in accordance with ANSI Standard Z83.7/CGA 2.14-2000. Check with your local fire safety authority if you have any questions about your applications. Other standards govern the use of fuel gases and heat producing products in specific applications. Your local authority can advise you about these.

Direct-Fired means that all of the combustion products enter the heated space. Even though this heater operates very close to 100 percent combustion efficiency, it still produces small amounts of carbon monoxide. Carbon monoxide (called CO) is toxic. We can tolerate small amounts but not a lot. CO can build up in a heated space and failure to provide adequate ventilation could result in death.

The symptoms of inadequate ventilation are:

headache

dizziness

burning eyes and nose

nausea

dry mouth or sore throat

So, be sure to follow advice about ventilation in these operating instructions.

Forced Air means that a blower or fan pushes the air through the heater. Proper combustion depends upon this air flow; therefore, the heater must not be revised, modified or operated with parts removed or missing. Likewise, safety systems must not be circumvented or modified in order to operate the heater.

When the heater is to be operated in the presence of other people the user is responsible for properly acquainting those present with the safety precautions and instructions, and of the hazards involved.

Figure 1

VENTILATION: Minimum openings required

 

Opening

Opening

Heater

near floor

near ceiling

Forced air (170 FAVT)

3 ft2

3 ft2

 

 

 

SAFETY PRECAUTIONS

1.Check the heater thoroughly for damage. DO NOT operate a damaged heater.

2.DO NOT modify the heater or operate a heater which has been modified from its original condition.

3.Use only propane gas.

4.Use only VAPOR WITHDRAWAL propane supply. If there is any question about vapor withdrawal, ask your propane dealer.

5.Mount the propane cylinders vertically (shutoff valve up). Secure them from falling or being knocked over and protect them from damage.

6.Locate propane containers at least (USA) 7 ft. (2.13m), (Canada) 10 ft. (3m) from the heater and do not direct exhaust toward containers.

7.IMPORTANT Use only the hose and regulator assembly provided with the heater. Match the color stripe on the hangtag attached to the hose assembly with the color on the label located near the propane inlet fitting on the heater. Inspect hose assembly before each use of the heater. If there is excessive abrasion or wear, or hose is cut, replace with hose assembly listed on parts list before using heater.

8.For indoor use only. Area must be well ventilated. Figure 1. (also see "Operating Precautions").

9.If at any time gas odor is detected, IMMEDIATELY DISCONTINUE operation until the source of gas has been located and corrected. Read enclosed Odor fade and Propane Sheet for additional information about detecting propane leaks.

10.Install the heater such that it is not directly exposed to water spray, rain and/or dripping water.

11.Maintain minimum clearance from normal combustible material (like paper). Figure 2.

12.Due to the high surface and exhaust temperatures, adults and children must observe clearances to avoid burns or clothing ignition.

13.Operate only on a stable, level surface.

14.Do not use with duct work. Do not restrict inlet or exit.

15.Use only the electrical power specified. The electrical connection and grounding must comply with National Electrical Code - ANSI/NFPA 70 (USA) and CSA C22.1 Canadian Electrical Code, Part 1 (Canada).

16.Use only a properly grounded 3-prong receptacle or extension cord.

17.Do not move, handle or service while hot or burning.

18.Do not adjust the heater combustion tube elevation while heater is running or hot. Adjustments to elevation should only be made after the heater has cooled to touch.

19.Use only in accordance with local codes or, in the absence of local codes, with the Standard for the Storage and Handling of Liquefied Petroleum Gases ANSI/NFPA 58 and CSA B149.1, Natural Gas and Propane Installation Code.

Figure 2: MINIMUM CLEARANCE: From normal combustible materials

Clearance

Forced Air 170FAVT

 

 

From floor

0 ft

From outlet

6 ft

From sides

2 ft

From top

3 ft

 

Locate 10 ft. from canvas or plastic tarpaulins or similar

coverings and secure them

to prevent flapping or movement

 

 

Enerco Group, Inc. Force-Air Propane Construction Heater

3

Operating Instructions and Owner’s Manual

70176 Rev. C 4/07

 

Image 3
Contents FORCED-AIR Propane Construction Heater Contents SpecificationsGeneral Hazard Warning Safety Precautions Operating PrecautionsOdor Fade Warning Fuel GAS OdorOdor Fading no Odor Detected Operating Instructions Black RED Blue White Green Orange 170FAVT Wiring ChartHOW Much Heat do I REQUIRE? Btus PER Hour RequiredBTU Model #170FAVT Parts ListParts Ordering Information HeatstarHeater .MR Pièces DES Liste 170FAVT nº Modèle BESOIN? JE-AIS Chaleur Câblage DE Schéma 170FAVTCâblage DE Schéma Requis Heure PAR BTUEntreposage ET Entretien Contenances ET DimensionsPropane GAZ DE Bonbonnes DES EntreposageAucune Odorantes Substances AUX Relatif AvertissementRetenir Essentiels Points DéceléeFonctionnement Sécurité LAAU Liées Précautions 240 C 116 ..... Maximale Température DE Commande Spécifications Matières DES TableAvertissement Heatstar
Related manuals
Manual 8 pages 40.26 Kb

MH170FAVT specifications

The Enerco MH170FAVT is a high-performance portable propane heater designed for both indoor and outdoor applications. This versatile heater stands out with its impressive heating capacity, efficient operation, and user-friendly features, making it an ideal choice for numerous environments such as workshops, garages, construction sites, and even during outdoor events.

One of the primary features of the MH170FAVT is its powerful heating output, capable of delivering up to 170,000 BTUs. This significant heating capacity ensures that areas of up to 4,200 square feet can be effectively warmed, providing comfort in large spaces efficiently and quickly. The heater utilizes propane, a clean-burning fuel that not only contributes to a lower environmental footprint but also minimizes fuel costs over time.

The design of the Enerco MH170FAVT emphasizes portability and practicality. It is equipped with a durable metal housing that ensures robustness and longevity. The large, rugged wheels make it easy to transport the heater from one location to another, while the convenient carrying handle enhances its maneuverability.

This heater is also designed with safety in mind. It includes a built-in safety tip-over switch that automatically shuts off the heater if it tips over, preventing potential hazards. Additionally, the MH170FAVT features an adjustable heat level control that allows users to customize their heating needs quickly.

Furthermore, the heater incorporates a reliable ignition system that ensures quick starts, allowing users to heat their spaces without the fuss of complicated setups. The unit is also compatible with standard 20 lb propane tanks, making fuel replacement hassle-free and convenient.

The Enerco MH170FAVT's efficiency is complemented by its robust thermal output, ensuring that users can experience sustained warmth without excessive fuel consumption. Its thoughtful engineering and design not only enhance performance but also create an overall user-friendly experience.

Whether for industrial applications or recreational use, the Enerco MH170FAVT is a powerful and efficient heating solution that meets diverse heating demands. Its blend of safety, convenience, and portability allows it to stand out in the market, making it a trusted choice for anyone in need of reliable heating in various settings.