Chapter 10: Programming

Group 1 – Voltage,

Amp And Watt

Scale Settings

The EPM 5300P and 5200P full scales will already be programmed if the order specified current and voltage transformer ratios. The meter label indicates any full scale setup.

Programming Group 1 contains voltage, amperage and full scale power selection, along with scale factor selection and decimal point placement.

The user can re-scale without removing the EPM 5300P for calibration. The 5300P has been calibrated at standard levels in GROUP 2. Mathematically convert any full scale ratios to those calibrated levels. If a different current or voltage transformer is used, program the primary value of its ratio. If necessary, convert the ratio to a secondary value of five amps standard current (1 amp is a special order) and 120V or 75V nominal voltage (options L only).

Formulas:

Primary x 120V Primary x 75V Primary x 5A

Secondary Secondary Secondary

It may be necessary to convert the full scale to a larger unit. There is a resolution limitation for all full scales of 2000. If a display reading exceeds 2000, it may be unstable and subject to zeroing problems.

Example: The full scale for a CT ratio of 3000/5 should be 03.00 kA.

When changing a PT or CT full scale, calculate the new watts full scale and make any necessary changes. The watts full scale will not auto range.

EPM 5300 SERIES ADVANCED POWER METERS – INSTRUCTION MANUAL

10–73

Image 85
Contents GE Multilin EPM 5300 Power Metering System ChapterPage Table of Contents Programming 112 111113 114Table of Contents TOC-IV Single Phase System EPM 5300 Series Meters AC Power Measurement= E I cosΘ Power W in a single phase system isDelta Wye Three-Phase SystemPoly Phase System 1 Delta, 2 Wye Consumption WH = W ⋅ T Consumption, Demand and Poor Power FactorSin ω ⋅ t Waveform and HarmonicsMechanical Installation EPM 5300 Series Meters Mechanical InstallationInstallation with K-110 option for limited space conditions Port Mechanical Installation Connecting the Current Circuit EPM 5300 Series Meters Electrical InstallationFeet CT Connection Option 1 Isolating a CT Connection Reversal power readingHelpful Debugging Tools Connecting the Voltage Circuit Selecting the Voltage Fuses Externally fuse power supply with a slow-blow 3 Amp fuse Connection to the Main Power SupplyList of Connection Diagrams Electrical Connection InstallationLine Load Back View Line Back View B C Load Line B C Back View Load EPM 5300P-S Single Phase with CT and PT ConnectionLine EPM 5300P Relay Overview Relay, Protection and Pulse Output2 2 Relays & 1 KYZ Pulse Output -NL Option This section applies only to the -NL or -NL2 Relay OptionClose-up of the Relay and KYZ pulse output on the rear panel Standard Rate Table for Watts Standard Rate Table for Watts KYZ Pulse Outputs NL2 OptionKYZ Pulse Outputs NL2 Option RS-232C EPM 5300 Series Meters Communication InstallationRS-485 RS-485 Hookup Diagram 2 wire Half DuplexRS-485 Hookup Diagram 2 wire Half Duplex Closed Loop Connecting 4-Wire bus to RS-485 Port RS-485 Hookup Diagram 4 wire Full DuplexRS-485 Hookup Diagram 4 wire Full Duplex Detail View You may want to use a Modem Manager RS485-RS232 Converter Network of Instruments and Long Distance CommunicationProgramming the Modem Modem Connected to Computer Originate ModemModem Connected to the Device Remote Modem Debugging Communication Problems Tell modem to write the new settings to activate profileFreq EPM 5300 Series Meters Overview± Total KWH Total Kvah N/A on EPM 5200PEPM 5300P front panel with display and keypad Press Power to select the power category Accessing the Power FunctionsSequence Press PHASE/NEXT for the desired phase Accessing Voltage and Current PhasesDisplay blanks and indicates the %THD value momentarily Accessing %THD FunctionsViewing Individual Phase Indication for Power Functions Phase Accessing Max/Min ValuesUnprotected Reset Resetting ValuesTo reset the min of Amps a Repeat this procedure for each value you wish to resetPassword is Protected ResetPress Power once Resetting Hour ReadingsTime a password digit Appears While the questionTo view the setup of the LM1/LM2 set limits Accessing the LM1/LM2 Set LimitsTo access the set limit To locate readings that exceeded LimitVoltage Phase Reversal Voltage Phase Reversal and ImbalanceThis display indicates a Press and hold downEnter Programming Mode see Programming Section Access ModesPrint Operating Data Print Programming DataPrint Operating Data Press and hold PHASE/NEXTMiddle display Release both buttons Print Programming Data Step Press and hold PHASE/NEXT Accessing Firmware Version/LED TestEPM 5300 Series Meters Programming Overview General ProcedureGROUPS, Functions, and Switch Packs Switch PacksPoint from Function and Group level Programming Mode Data EntryPosition UP or Down Activates new data entry and enters or exits fromStandard Numeric Data Entry EPM 5200P EPM 5300 Series Meters EPM 5200PVA/HR EPM 5300P vs EPM 5200P vs EPM 5350PChecksum Error-Protective Self-Checking Algorithms EPM 5300 Series Meters Entering Programming ModeEntering Programming Mode Password EntryIf 3 is not already displayed Press Amps until 3 appears Flashes momentarily in middle displayRelay 1 Set-up / Time delay System Configuration see TableRelay 2 Set-up / Time delay Number of PhasesLower display indicates current Interval setting Enter Group Level of Programming Mode see ChpGroup 0, Function 0-The Integration Interval Press Amps to activate the GroupTo change the Meter Address Programming Group 0 Global Meter SetupGroup 0, Function 2 Baud Rate Group Function Pack Group 0, Function 3 System ConfigurationOpen Delta System Installation Programming Programming Group 0 Global Meter Setup Printing Option Modbus Plus CapabilityTo change the System Configuration Switch Settings Group 0, Function 3-Programming ProcedureRelay Mode Enter in Group 0, Function 4, Pack ‘p’, Segments C and D Programming StepsLI M IT S Relay 1 On to Off Delay Time To change Time DelaysRelay 1 Off to On Delay Time Relay 2 On to Off Delay TimeTo program Relay 2 To perform the KYZ Parameter Selection Group 0, Function 6-KYZ Parameter SelectionKYZ Parameters Enter Group Level of Programming Mode see Chp Applies to -NL2 Option only How to Use KYZ Pulse Value Table for MultiplicationKYZ Pulse Value Selection is Multiply by How to Use KYZ Pulse Value Table for DivisionTo change the KYZ pulse value Enter 2 for single phase/two wire Group 0, Function 7-Number of PhasesEnter Group Level of Programming Mode. Chapter Press Amps to activate the Group Appears in upper displayFormulas Group 1, Function Typical Full Scale Settings for VoltsVoltage Full Scale Group 1 Programming FormatPress Amps to activate Group Appears in upper display Press MAX/MIN/LIMITS until 1. appears in upper displayPress Volts to move decimal point Press Amps to store 10-76 Full Scale Settings for Amps To change the Full Scale SettingsPress Amps to begin Data Entry Sequence Entering the Scale Factor Decimal Point Selection StepScale Selection and Decimal Placement for Watts Display To change the scale factor setting for wattageEntering the Scale Factor Step 10-82 EPM 5300 Series Meters Programming Group 2 Meter Calibration Group 2 Programming Format Calibration RequirementsHigh End Calibration-Volts AN, BN, CN High End Calibration-Amps A, B, CTo change the calibration high end-Functions 0 Group 2, FunctionsGroup 2, Functions For Amps Low End Function11-87 11-88 LM1 and LM2 SET Limits EPM 5300 Series Meters Groups 4, 5 Set Limits RelaysTrip Relay Time Delays & Relay Mode V O L T S A M P S Group 4 Functions 0-3-LM1/LM2 Set LimitsGroup 4 Programming Format Group 4 Programming Format for Limit ConditionGroup 4 Functions Group 4 Example for FunctionGroup 5 Functions 0-7-LM1/LM2 Set Limits There are 3 switches to set with limitsGroup 5 Programming Format for Limit Condition Group 5 Functions Special CasesGroup 5 Example for Function Digit Up Digit Down 0120Group 6 Programming Format For THD Limit Conditions Group 6 LM1/LM2 Set LimitsGroup 6 Functions Digit Up Digit Down 012.0 Group 6-Example for FunctionGroup Limits or Relays Programming ProcedureLimits or Relays Programming Procedure Press Amps once to Disable the Limit12-100 Phase Imbalance Phase Reversal and Phase ImbalanceTrip Relay Level ENABLE/DISABLE To change the phase reversal setting Group 7, Function 0-Voltage Phase Reversal DetectionVoltage Phase Reversal Detection Voltage Phase Imbalance13-104 To change the percentage voltage phase imbalance Group 7, Function 1-Percentage Voltage Phase ImbalanceMiddle and lower displays indicate new settings Exiting Programming Mode EPM 5300 Series Meters Exiting Programming ModePress Amps to exit from Function Level to Group Level Meter returns to Function LevelEPM 5300 Series Meters Programming Quick Reference Entering the Programming ModeData Entry Sequence Programming Groups Group 0 Global Meter SetupOn to OFF delay time OFF to on delay time Group 1 Full Scale SetupVolts Full Scale Currents Full Scale Power Full Scale Group 2 CalibrationGroup 3 Calibration Ratios Group 5 Power Function LimitsGroup 4 Volt/Current Limits Group 6 THD LimitsGroup 8 DC output Calibration Group 7 Imbalance/Reversal LimitsDetect Reversal Imbalance percent Limit ⎯ Scroll Groups 89L. Low-End Calibration 89H. High-End Calibration⎯ Scroll Functions ⎯ Scroll Packs15-116 EPM 5300 Series Meters Ethernet Option Ethernet Module AutoIP Ethernet Option SetupNetwork Configuration Network Port LoginARP on Unix Telnet to PortConfiguration Parameters Baud Rate