AXIS Electrical Safety Kit A/B | Page 9 |
Install the Devices
•The electrical connections and conduit installations shall be made by a certified electrician and in compliance with local regulations.
•Risk of electric shock. The mains supply shall be disconnected during installation.
•Keep the wires short but do not stretch them. Short wires give better surge protection than long wires.
•The ground wire should be as short as possible and have as large cross section as possible. Attach the ground wire to a suitable grounding point, for example an earth stake.
1.Snap on the fuse, surge protector and terminal blocks on the DIN rail. See Hardware Overview, on page 6 and the examples on page 10. Make sure that the positions correspond to the slots in the device cover.
See the User Guide provided with the surveillance cabinet for more information about the device cover.
2.Connect the devices according to the connection diagram. See page 7. Use a cable of minimum 2.5 mm2 (AWG 14) for incoming mains voltage.
3.Secure the cables. Use 2.8 Nm (25
4.Attach the device cover to the cabinet base according to the instructions provided with the surveillance cabinet.