DSXH47GG
GE® 5.8 Cu. Ft. Extra-Large Capacity Frontload Gas Dryer
Dryer Exhausting Information – Metal Duct Only
For complete information, see installation instructions packed with your dryer.
Ducting Materials: For best performance, this dryer should be vented with 4” diameter all rigid metal exhaust duct. If rigid metal duct cannot be used, then
Exhaust Length Calculation:
1.Determine the number of 90° turns needed for your installation. If you exhaust to the side or bottom of dryer, add one turn.
2.The maximum length of 4’ rigid (aluminum or galvanized) duct which can be tolerated is shown in the table.
A turn of 45° or less may be ignored. Two 45° turns within the duct length should be treated as a 90° elbow.
A turn over 45° should be treated as a 90° elbow. Dryers must be exhausted to the outside.
Caution: For personal safety do not terminate exhaust into a chimney, under any enclosed house floor (crawl space), or into an attic, since the accumulated lint could create a fire hazard or moisture could cause damage. Never terminate the exhaust into a common duct or plenum with a kitchen exhaust, since the combination of lint and grease could create a fire hazard.
Exhaust ducts should be terminated in a dampered wall cap to prevent back drafts, bird nesting, etc. The wall cap must also be located at least 12" above the ground or any other obstruction with the opening pointed down.
For more information on venting kits and accessories, please call
|
|
|
|
| Best performance | |
|
| A |
|
| Maximum length of 4" | |
A |
|
| dia. rigid metal duct | |||
|
|
|
|
| Exhaust hood type | |
4 |
|
|
| |||
|
| B |
| Number |
|
|
|
|
|
| of | A | B |
Domestic | 90° | 4" | ||||
dryer models |
| turns | opening | opening | ||
|
|
|
| 0 | 90 ft. | 60 ft. |
7.0, 6.0 and 5.8 cu. ft. | 1 | 60 ft. | 45 ft. | |||
capacity models | 2 | 45 ft. | 35 ft. | |||
all gas dryers |
| 3 | 35 ft. | 25 ft. |
Specification Revised 5/09 | 360471 |