AIR FOR COMBUSTION AND VENTILATION

Continued

VENTILATION AIR

Ventilation Air From Inside Building

This fresh air would come from an adjoining unconfined space. When ventilating to an adjoining unconfined space, you must pro- vide two permanent openings: one within 12" of the ceiling and one within 12" of the floor on the wall connecting the two spaces (see options 1 and 2, Figure 4). You can also remove door into adjoining room (see op- tion 3, Figure 4). Follow the National Fuel

Ventilation

 

Grills

Or

into Adjoining

Remove

Room,

Door into

Option 1

Adjoining

 

Room,

 

Option 3

12"

Ventilation Grills

Into Adjoining Room,

Option 2

Gas Code NFPA 54/ANS Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

WARNING: Rework work- sheet, adding the space of the adjoining unconfined space. The combined spaces must have enough fresh air to supply all appliances in both spaces.

12"

Figure 4 - Ventilation Air from Inside Building Shown with Optional Mantel

Ventilation Air From Outdoors

Provide extra fresh air by using ventilation grills or ducts. You must provide two per- manent openings: one within 12" of the ceiling and one within 12" of the floor. Connect these items directly to the outdoors or spaces open to the outdoors. These spaces include attics and crawl spaces. Follow the National Fuel Gas Code NFPA 54/ANS Z223.1, Section 5.3, Air for Combustion and Ventilation for required size of ventilation grills or ducts.

IMPORTANT: Do not provide openings for inlet or outlet air into attic if attic has a thermostat-controlled power vent. Heated air entering the attic will activate the power vent.

Ventilated

Outlet Attic

Air

Outlet

 

Air

To Attic

 

To

Crawl

Space

Inlet

Air

Inlet Air

 

Ventilated

 

 

Crawl Space

 

 

Figure 5 - Ventilation Air from Outdoors Shown with Optional Mantel

104060

7

Image 7
Contents What to do if YOU Smell GAS VENT-FREE Natural GASCompact Classic Hearth Fireplace Safety InformationLocal Codes Product Identification FeaturesUnpacking Assembling Hood AssemblyInstalling Log Assembling FireplaceConfined and Unconfined Space AIR for Combustion and VentilationProviding Adequate Ventilation Unusually Tight ConstructionDetermining FRESH-AIR Flow for Fireplace Location AIR for Combustion VentilationDetermining if You Have a Confined or Unconfined Space Ventilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors Locating Fireplace InstallationInstallation Items Check GAS TypeRough Opening for Installing in Wall BUILT-IN Fireplace InstallationMantel Clearances for Built-In Installation Optional Mantel InstallationAssembling Brass Trim Brass trim shipped with mantel Installing Blower Accessory GA3400TRemoving Upper Louver Assembly Installing Blower AssemblyInstall the switch plate on the valve Extension Cord For Built-In InstallationAttaching Wood Base to Solid Floor Connecting to GAS SupplyInstallation Items Needed Connecting Fireplace to GAS SupplyPressure Testing Fireplace Gas Connections Pressure Testing Gas Supply Piping SystemChecking GAS Connections Operating Fireplace For Your Safety Read Before LightingLighting Instructions Operating Blower Manual Lighting ProcedureTo Turn OFF GAS To Appliance Thermostat Control OperationPilot Flame Pattern Inspecting BurnerBurner Flame Pattern Observed Problem Possible Cause Remedy TroubleshootingMaintenance, Gas leak. See Warning statement at Air Passageways Cleaning and MaintenanceCleaning Burner Injector Holder and Pilot AIR Inlet Hole CabinetVMH26TNA Illustrated Parts BreakdownDescription QTY Parts ListTechnical Service SpecificationsReplacement Parts Service HintsAccessories Warranty Information