10 | GAS INSTRUCTIONS |
|
|
CONNECTING THE LIQUID PROPANE CYLINDER
WARNING: Make sure that the LP cylinder valve is closed. Close by turning valve clockwise.
DANGER
Do not use an open flame to check for gas leaks. Be sure there are no sparks or open flames in the area while you check for leaks. Sparks or flames will result in a fire or explosion that can cause serious bodily injury or death, and damage to property.
You will need: LP cylinder, a
1)Connect LP cylinder.
Some regulators push ON to connect, and pull OFF to disconnect, others have a nut that has a
A1) Screw regulator fitting onto tank turning
B1) Make sure regulator lever (b) is in the down/off position. Push regulator down on tank valve until regulator snaps into position.
C1) Make sure regulator lever is in the off position. Slide the collar of the regulator up (1). Push the regulator down onto the tank valve and maintain pressure. Slide collar closed (2). If regulator does not lock, repeat procedure.
2)Mix soap and water.
3)Turn on the cylinder valve.
A2) Turn cylinder valve clockwise.
B2) Move regulator lever
C2) Move regulator lever to the On position.
4)Check for leaks by wetting the fitting with the
the
5)When leak checking is complete, turn gas supply off at the source and rinse connections with water.
A1 | A2 |
| a) |
B1 | B2 |
| b) |
C1 | C2 |
| 1. |
| 2. |
REMOVE CONTROL KNOBS & CONTROL PANEL FOR LEAK TESTING
You will need: Phillips screwdriver.
1)Remove control knobs.
2)Remove screw and washer from back of control panel with a Phillips screwdriver.
3)Tilt the back edge of the control panel up. Push in on the front edge to release locking tabs. Carefully pull control panel away from frame.
4)Disconnect the igniter wires from the ignition module.
5)Replace control panel when leak check is completed.
WWW.WEBER.COM®