Panasonic Indoor Unit Outdoor Unit CS-E9NKUAW CS-E12NKUAW CU-E9NKUA CU-E12NKUA Safety Precautions

Page 3

1. Safety Precautions

šRead the following “SAFETY PRECAUTIONS” carefully before perform any servicing.

šElectrical work must be installed or serviced by a licensed electrician. Be sure to use the correct rating of the power plug and main circuit for the model installed.

šThe caution items stated here must be followed because these important contents are related to safety. The meaning of each indication used is as below. Incorrect installation or servicing due to ignoring of the instruction will cause harm or damage, and the seriousness is classified by the following indications.

WARNING

CAUTION

This indication shows the possibility of causing death or serious injury

This indication shows the possibility of causing injury or damage to properties.

šThe items to be followed are classified by the symbols:

This symbol denotes item that is PROHIBITED from doing.

šCarry out test run to confirm that no abnormality occurs after the servicing. Then, explain to user the operation, care and maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.

WARNING

1.Do not modify the machine, part, material during repairing service.

2.If wiring unit is supplied as repairing part, do not repair or connect the wire even only partial wire break. Exchange the whole wiring unit.

3.Do not wrench the fasten terminal. Pull it out or insert it straightly.

4.Engage authorized dealer or specialist for installation and servicing. If installation of servicing done by the user is defective, it will cause water leakage, electrical shock or fire.

5.Install according to this installation instructions strictly. If installation is defective, it will cause water leakage, electric shock or fire.

6.Use the attached accessories parts and specified parts for installation and servicing. Otherwise, it will cause the set to fall, water leakage, fire or electrical shock.

7.Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly done, the set will drop and cause injury.

8.For electrical work, follow the local national wiring standard, regulation and the installation instruction. An independent circuit and single outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.

9.This equipment is strongly recommended to be installed with Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD). Otherwise, it may cause electrical shock and fire in case equipment breakdown or insulation breakdown.

10.Do not use joint cable for indoor/outdoor connection cable. Use the specified indoor/outdoor connection cable, refer to installation instruction CONNECT THE CABLE TO THE INDOOR UNIT and connect tightly for indoor/outdoor connection. Clamp the cable so that no external force will be acted on the terminal. If connecting or fixing is not perfect, it will cause heat up or fire at the connection.

11.Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will cause heat-up or fire at the connection point of terminal, fire or electrical shock.

12.When install or relocate air conditioner, do not let any substance other than the specified refrigerant, eg. air etc. mix into refrigeration cycle (piping). (Mixing of air etc. will cause abnormal high pressure in refrigeration cycle and result in explosion, injury etc.).

13.Do not install outdoor unit near handrail of veranda. When installing air-conditioner unit at veranda of high rise building, child may climb up to outdoor unit and cross over the handrail and causing accident.

14.This equipment must be properly earthed. Earth line must not be connected to gas pipe, water pipe, earth of lightning rod and telephone. Otherwise, it may cause electrical shock in case equipment breakdown or insulation breakdown.

15.Keep away from small children, the thin film may cling to nose and mouth and prevent breathing.

16.Do not use unspecified cord, modified cord, joint cord or extension cord for power supply cord. Do not share the single outlet with other electrical appliances. Poor contact, poor insulation or over current will cause electrical shock or fire.

17.Tighten the flare nut with torque wrench according to specified method. If the flare nut is over-tightened, after a long period, the flare may break and cause refrigerant gas leakage.

18.For R410A models, when connecting the piping, do not use any existing (R22) pipes and flares nuts. Using such same may cause abnormally high pressure in the refrigeration cycle (piping), and possibly result in explosion and injury. In case of using existing (R22) pipes during installation of R410A models, must carry out pump down properly to collect back the refrigerant and oil before installation new unit.

Thickness of copper pipes used with R410A must be more than 1/64". Never use copper pipes thinner than 1/64". It is desirable that the amount of residual oil is less than 0.0014 oz/32.8ft.

3

Image 3
Contents CS-E9NKUAW CU-E9NKUA CS-E12NKUAW CU-E12NKUA Exploded View and Replacement Parts List Safety Precautions Page CU-E9NKUA CU-E12NKUA ARI SpecificationType Propeller Fan Material Motor Type DC 8 poles DRY Bulb WET Bulb š Easy to use remote control š Quality Improvement FeaturesLocation of Controls and Components Indoor Unit Outdoor Unit Remote ControlIndoor Unit DimensionsOutdoor Unit Refrigeration Cycle Diagram Block Diagram Wiring Connection Diagram Outdoor Unit Electronic Circuit Diagram Outdoor Unit Main Printed Circuit Board Printed Circuit BoardPower Printed Circuit Board Indicator Printed Circuit Board Outdoor Unit Indoor Unit Installation InstructionIndoor/Outdoor Unit Installation Diagram Select the Best LocationTo Drill a Hole in the Wall and Install a Sleeve of Piping How to Fix Installation PlateIndoor Unit Installation Connect the Cable to the Indoor Unit Cutting and flaring the piping Wiring Stripping and connecting requirementConnect the Piping Install the Outdoor UnitEvacuation of the equipment Connecting the piping to outdoor multiConnect the Cable to the Outdoor Unit Basic Function Operation ControlBasic Rotation Speed rpm Indoor Fan Motor OperationOutdoor Fan Motor Operation Airflow DirectionVertical Airflow Quiet Operation Cooling Mode/Cooling Area of Dry Mode Quiet Operation HeatingHorizontal Airflow OFF Timer Control Powerful Mode OperationTimer Control On Timer ControlIndication Panel Heating Operation Operation Control For Multi Split ConnectionCooling operation Soft Dry OperationResidual Heat Removal Control Automatic OperationProtection Control For All Operations Protection ControlLow Pressure Prevention Control Gas Leakage Detection Outdoor Air Temperature ControlProtection Control For Cooling & Soft Dry Operation Compressor Overheating Prevention ControlProtection Control For Heating Operation Cooling Overload ControlFreeze Prevention Control Dew Prevention ControlOutdoor Air Temperature Control Auto Off/On Button Servicing ModeRemote Control Button Refrigeration Cycle System Troubleshooting GuidePage To Make a Diagnosis To Display Memorized Error Code Protective OperationBreakdown Self Diagnosis Function Self Diagnosis Function Three Digits Alphanumeric CodeError Code Table Page 16.4.1 H11 Indoor/Outdoor Abnormal Communication Self-diagnosis Method16.4.2 H12 Indoor/Outdoor Capacity Rank Mismatched 16.4.3 H14 Indoor Intake Air Temperature Sensor Abnormality 16.4.4 H15 Compressor Temperature Sensor Abnormality 16.4.5 H16 Outdoor Current Transformer Open Circuit 16.4.6 H19 Indoor Fan Motor DC Motor Mechanism Locked 16.4.7 H23 Indoor Pipe Temperature Sensor Abnormality 16.4.8 H27 Outdoor Air Temperature Sensor Abnormality 16.4.9 H28 Outdoor Pipe Temperature Sensor Abnormality Malfunction Decision Conditions Malfunction Decision Conditions 16.4.12 H33 Unspecified Voltage between Indoor and Outdoor 16.4.13 H36 Outdoor Gas Pipe Sensor Abnormality Malfunction Decision Conditions 16.4.15 H97 Outdoor Fan Motor DC Motor Mechanism Locked 16.4.16 H98 Indoor High Pressure Protection Malfunction Decision Conditions 16.4.18 F11 Indoor Pipe Temperature Sensor Abnormality Remark 16.4.19 F17 Indoor Standby Units Freezing Abnormality16.4.20 F90 Power Factor Correction Protection 16.4.21 F91 Refrigeration Cycle Abnormality 16.4.22 F93 Compressor Rotation Failure 16.4.23 F95 Cooling High Pressure Abnormality 16.4.24 F96 IPM Overheating 16.4.25 F97 Compressor Overheating 16.4.26 F98 Input Over Current Detection 16.4.27 F99 Output Over Current Detection To remove front grille Disassembly and Assembly InstructionsTo remove discharge grille Page Page Technical Data Operation CharacteristicsCS-E9NK CU-E9NK 139.500 139.000 Piping Length ft 600 Current 400 300 200 100 Page Page CS-E12NK CU-E12NK Page Page Page Exploded View and Replacement Parts List Chassis Complete Outdoor Unit Chassis Assy

Indoor Unit Outdoor Unit CS-E9NKUAW CS-E12NKUAW CU-E9NKUA CU-E12NKUA specifications

Panasonic has been a pioneer in the heating and cooling industry, and its range of air conditioners, particularly the CS-E9NKUAW and CS-E12NKUAW indoor units, paired with the CU-E9NKUA and CU-E12NKUA outdoor units, exemplify the brand's commitment to energy efficiency, advanced technologies, and user-friendly features.

These models deliver exceptional cooling and heating performance, making them suitable for various climates. One of the prominent features of these units is their Inverter technology, which ensures that the compressor can adjust its speed according to the desired temperature. This not only provides accurate temperature control but also results in lower energy consumption compared to non-inverter systems. Users can enjoy a consistent and comfortable indoor environment while keeping their electricity bills in check.

A key characteristic of the CS-E9NKUAW and CS-E12NKUAW units is their whisper-quiet operation. The low noise levels make them ideal for bedrooms, living rooms, or office spaces, providing comfort without disturbance. With a decorative design, these indoor units seamlessly blend into any interior, enhancing the aesthetic appeal of the space.

These Panasonic models are also equipped with advanced air purification systems. Utilizing a combination of nanoe™ technology, the air conditioners effectively reduce airborne bacteria, viruses, and allergens, ensuring cleaner and healthier indoor air quality. The air purification feature is complemented by a powerful filter system that captures dust and particulate matter, further enhancing the overall air quality.

The remote control feature allows users to operate the units with ease. With programmable timers and personalized settings, optimal comfort and convenience are just a click away. Additionally, the units are designed to be eco-friendly, adhering to strict environmental regulations and standards, thus promoting sustainability.

For installation, the outdoor units CU-E9NKUA and CU-E12NKUA are engineered to operate efficiently and quietly, accommodating various mounting options for flexible installation. The robust design enhances durability while minimizing maintenance needs, ensuring long-term reliability.

In summary, the Panasonic CS-E9NKUAW, CS-E12NKUAW indoor units, along with their CU-E9NKUA and CU-E12NKUA outdoor counterparts, embody a perfect blend of cutting-edge technology, user-centric features, and energy efficiency. They represent an excellent choice for consumers seeking comfort, convenience, and quality in their heating and cooling solutions.