Trane 4TWB3 Electrical Connections, Defrost Control, Compressor Start UP, PIN Identification

Page 4

Installer’s Guide

10.The gas valve can now be opened. For a ball type gas valve, open the gas valve by removing the shut-off valve cap and turning the valve stem 1/4 turn counterclock- wise, using 1/4" Open End or Adjustable wrench. See Figure 4. For brass gas line service valve opening, follow 8 and 9 on page 3. See Figure 5.

11.The gas valve is now open for refrigerant flow. Replace valve stem cap to prevent leaks. Again, these caps MUST BE REPLACED to prevent leaks. Replace valve stem and pressure tap cap finger tight, then tighten an additional 1/6 turn. See Figure 4.

If refrigerant lines are longer than 15 feet and/or a different size than recommended, it will be necessary to adjust system refrigerant charge upon completion of installation. See page 6 or in the unit Service Facts.

E. ELECTRICAL CONNECTIONS

!WARNING

When installing or servicing this equipment, ALWAYS exercise basic safety precautions to avoid the possibility of electric shock.

1.Power wiring and grounding of equipment must comply with local codes.

2.Power supply must agree with equipment nameplate.

3.Install a separate disconnect switch at the outdoor unit.

4.Ground the outdoor unit per local code requirements.

5.Provide flexible electrical conduit whenever vibration transmission may create a noise problem within the structure.

6.The use of color coded low voltage wire is recommended to simplify connections between the outdoor unit, the thermostat and the indoor unit.

Table 1 — NEC Class II Control Wiring

 

24 VOLTS

 

 

 

WIRE SIZE

 

MAX. WIRE LENGTH

 

 

 

18 AWG

 

150 FT

 

 

 

16 AWG

 

225 FT.

 

 

 

14 AWG

 

300 FT.

 

 

 

7.Table 1 defines maximum total length of low voltage wiring from outdoor unit, to indoor unit, and to thermostat.

8.Mount the indoor thermostat in accordance with instruc- tion included with the thermostat. Wire per appropriate hook-up diagram (included in these instructions).

F. DEFROST CONTROL

The demand defrost control measures heat pump outdoor ambient temperature with a sensor located outside the outdoor coil. A second sensor located on the outdoor coil is used to measure the coil temperature. The difference between the ambient and the colder coil temperature is the difference or delta-T measurement. This delta-T measurement is representative of the operating state and relative capacity of the heat pump system. By measuring the change in delta-T, we can determine the need for defrost. The coil sensor also serves to sense outdoor coil temperature for termination of the defrost cycle.

FAULT IDENTIFICATION

A fault condition is indicated by the flashing light on the defrost control inside the heat pump control box.

In normal operation, the defrost control light will flash once each second. If the light is flashing more than once per second or not at all, refer to the service manual for that unit.

PIN IDENTIFICATION (See Figure 6.)

1.TEST_COMMON (Shorting any of the other pins to this pin causes the function of the other pin to be executed. Leaving this pin open results in the normal mode of operation.)

2.TST = Test (Shorting TEST_COMMON to this pin speeds up all defrost board timings.)

3.FRC_DFT = Forced Defrost (Short TEST_COMMON to this pin for two [2] seconds to initiate a forced defrost. Remove the short after defrost initiates.)

6PIN IDENTIFICATION

 

TEST COMMON

FRC DFT

TST

DEFROST CONTROL CHECKOUT

Normal operation requires:

a.LED on board flashing 1 time/second.

b.24V AC between R & B.

c.24V AC between Y & B with unit operating.

d.Defrost initiation when FRC_DFT pin is shorted to TEST_COMMON pin.

If a defrost control problem is suspected, refer to the service information in control box.

!WARNING

Do NOT connect 24V AC to T1 (ODS-A) terminal. ODS-A thermistor WILL BE BLOWN.

G. COMPRESSOR START UP

After all electrical wiring is complete, SET THE THERMO-

STAT SYSTEM SWITCH IN THE OFF POSITION SO COMPRESSOR WILL NOT RUN, and apply power by closing the system main disconnect switch. This will activate the compressor sump heat (where used). Do not change the Thermostat System Switch until power has been applied for one (1) hour. Following this procedure will prevent potential compressor overload trip at the initial start-up.

H. OPERATIONAL AND

CHECKOUT PROCEDURES

Final phases of this installation are the unit Operational and Checkout Procedures which are found in this instruction on page 8. To obtain proper performance, all units must be operated and charge adjustments made in accordance with procedures found in the Service Facts and on page 6.

IMPORTANT:

Perform a final unit inspection to be sure that factory tubing has not shifted during shipment. Adjust tubing if necessary so tubes do not rub against each other when the unit runs. Also be sure that wiring connections are tight and wire routing is secure.

4

18-BC61D1-1

Image 4
Contents USE only R-410A Refrigerant and Approved POE Compressor OIL GeneralFT. Above Unit Unrestricted Installing Refrigerant Lines Service Valve OperationLiquid Line Service Valve Location and Preparation UnitGAS Line Ball Service Valve GAS Line Service ValveOperational Checkout Procedures Electrical ConnectionsDefrost Control Compressor Start UPTypical Field HOOK-UP Diagrams 410A Refrigerant Charging Chart Subcooling Charging in Cooling Above 55F OD AmbientSubcooling Charging below 55F OD Ambient in Heating only Liquid Design Subcooling ˚F Temp Liquid Gage Pressure PSI4TWB3 Outline Drawing Models BaseCheckout Procedure Mounting Hole Location

4TWB3 specifications

The Trane 4TWB3 is a high-efficiency, energy-efficient heat pump designed to offer premium heating and cooling solutions for residential applications. It is part of Trane's multi-stage comfort systems, ensuring optimal performance and energy savings throughout the year. One of the standout features of the 4TWB3 is its variable-speed technology. This allows the unit to operate at different speeds depending on the heating or cooling demand, providing precise temperature control while consuming less energy.

Another key characteristic of the 4TWB3 is its advanced refrigerant system. It uses R-410A refrigerant, which is environmentally friendly and contributes to better energy efficiency compared to older refrigerants. The system's enhanced coil design and modern compressor technology further improve heat transfer, enhancing overall performance.

The Trane 4TWB3 also incorporates an integrated comfort control system. This feature provides users with the ability to monitor and adjust their home’s climate settings conveniently, ensuring a consistently comfortable indoor environment. Additionally, the unit is equipped with Trane’s patented WeatherGuard II top, which helps protect the heat pump from harsh weather conditions, ensuring durability and longevity.

Noise reduction is another significant feature of the 4TWB3. With its acoustic insulation and quiet operation design, the unit operates at lower sound levels, ensuring peace and quiet in your home. The heat pump is also designed with a corrosion-resistant cabinet, which further extends its lifespan and reliability.

In terms of energy efficiency, the Trane 4TWB3 boasts impressive SEER (Seasonal Energy Efficiency Ratio) ratings, making it an economical option for homeowners looking to reduce their energy bills. Its energy-efficient design not only aligns with environmental standards but also qualifies for various rebates and incentives, making it a smart investment.

Installation and maintenance are simple with the 4TWB3, thanks to its user-friendly design and advanced diagnostics capabilities. These make troubleshooting straightforward for technicians, ensuring that any required service is efficient and minimally disruptive.

In summary, the Trane 4TWB3 heat pump combines advanced features, superior technology, and outstanding performance. With its focus on energy efficiency, quiet operation, and durability, it is an excellent choice for homeowners seeking reliable heating and cooling solutions.