Submittal Data

HBH Series

Heat Controller, Inc.

 

 

 

HBH Series 60Hz

 

 

Engineering Specifications

Page 2

 

General:

Furnish and install the HBH Series as indicated on the plans. Equipment shall be completely assembled, piped and internally wired. Capacities and characteristics as listed in the schedule and the specifications that follow.

Units shall be supplied completely factory built capable of operating over an entering water temperature range from 20° to 120°F (-6.7° to 48.9°C) as standard. Equivalent units from other manufacturers may be proposed provided approval to bid is given 10 days prior to bid closing. All equipment listed in this section must be rated and certified in accordance with Air-Conditioning, Heating and Refrigeration Institute/International Standards Organization (AHRI/ISO 13256-1). All equipment must be tested, investigated, and determined to comply with the requirements of the standards for Heating and Cooling Equipment UL-1995 for the United States and CAN/CSA-C22.2 NO.236 for Canada, by Intertek Testing Laboratories (ETL). The units shall have AHRI/ISO and ETL-US-C labels.

All units shall be fully quality tested by factory run testing under normal operating conditions as described herein. Quality control system shall automatically perform via computer: triple leak check, pressure tests, evacuation and accurately charge system, perform detailed heating and cooling mode tests, and quality cross check all operational and test conditions to pass/fail criteria. Detailed report card will ship with each unit displaying status for critical tests and components. Note: If unit fails on any cross check, it shall not be allowed to ship. Serial numbers will be recorded by factory and furnished to contractor on report card for ease of unit warranty status. Units tested without water flow are not acceptable.

Basic Construction:

Horizontal units shall have one of the following air flow arrangements: Left Return/Back Discharge, Left Return/Straight Discharge, Right Return/Back Discharge, Right Return/Straight Discharge as shown on the plans. Units can be field converted without requiring new panels or belts. Units that cannot be field converted shall not be acceptable.

If units with these arrangements are not used, the contractor is responsible for any extra costs incurred by other trades. All units must have a minimum of two access panels for serviceability of compressor compartment. Units having only one access panel to compressor/heat exchangers/expansion device/refrigerant piping shall not be acceptable.

Compressor section interior surfaces shall be lined with 1/2 inch (12.7mm) thick, 1-1/2 lb/ft3 (24 kg/m3) acoustic type glass fiber insulation. Air handling section interior surfaces shall be lined with 1/2 in (12.7mm) thick, 1-3/4 lb/ft3 (28 kg/m3) foil backed fiber insulation for ease of cleaning. Insulation placement shall be designed in a manner that will eliminate any exposed edges to prevent the introduction of glass fibers into the air stream. Units without foil faced insulation in the air handling section will not be accepted.

Horizontal heat pumps shall be fabricated from heavy gauge galvanized steel, with powder coat paint finish on front access panel. Color to be pewter. Both sides of the panel shall be painted for added protection.

Standard insulation must meet NFPA Fire Hazard Classification requirements 25/50 per ASTM E84, UL 723, CAN/ULC S102-M88 and NFPA 90A requirements; air erosion and mold growth limits of UL-181; stringent fungal resistance test per ASTM-C1071 and ASTM G21; and shall meet zero level bacteria growth per ASTM G22. Unit insulation must meet these stringent requirements or unit(s) will not be accepted.

Horizontal units to have discharge air duct collar and 1” (25.4mm) filter rails with 1” (25.4mm) filters factory installed and factory installed mounting brackets. If units with these factory installed provisions are not used, the contractor is responsible for any extra costs to field install these provisions, and/or the extra costs for his sub-contractor to install these provisions.

All units must have an insulated panel separating the fan compartment from the compressor compartment. Units with the compressor in the air stream are not acceptable. Units shall have a factory installed 1 inch (25.4mm) wide filter rails with filter removal from either side. Units shall have a 1 inch (25.4mm) thick throwaway type glass fiber filter. The contractor shall purchase one spare set of filters and replace factory shipped filters on completion of start-up. Filters shall be standard sizes. If units utilize non-standard filter sizes then the contractor shall provide 12 spare filters for each unit.

Cabinets shall have separate knockouts on front and sides for entrance of line voltage and low voltage control wiring. All factory- installed wiring passing through factory knockouts and openings shall be protected from sheet metal edges at openings by plastic ferrules. Supply and return water connections shall be copper FPT fittings, connections on both sides (installer to choose side and plug opposite) and shall be securely mounted flush to the cabinet side allowing for connection of a flexible hose without the use of a back- up wrench. Water connections that protrude through the cabinet or require the use of a backup wrench shall not be allowed. Water connections on only one side will not be accepted. All water connections and electrical knockouts must not interfere with the serviceability of unit. Contractor shall be responsible for any extra costs involved in the installation of units that do not have this feature. Contractor must ensure that units can be easily removed for servicing and coordinate locations of electrical conduit and lights with the electrical contractor.

23

Image 25
Contents Unit Designation Job Name Architect Engineer Contractor Fan Speed or Motor RPM/Turns Operating WeightCooling Capacity Heating CapacityPage Table of Contents Conversion Table to convert inch-pound English to S-I Metric Reference Calculations73,300 Btuh 90,500 BtuhWater Flow Based upon 12F rise in temp.......18 GPM 5 HP SelectionModel Nomenclature ASHRAE/AHRI/ISO 13256-1. English I-P Units Performance DataGround Loop Heat Pump LWT = 50 12 = 38F Antifreeze must be used Performance Data Selection NotesPD ft PsiHeating EAT 70F Performance Data HBH07210.4 113.0 Performance Data HBH09613.0 143.5 Performance Data HBH120Correction Tables HBH Performance DataWPD Antifreeze Correction TableHBH072 Standard Unit Blower Performance DataTable on Next HBH096 Standard UnitTable from Previous Blower Performance Data HBH120 Standard Unit4300 HBH120 Standard UnitHBH Physical Data Service Access HBH072-120 Dimensional DataElectrical Knockouts RLA LRA StandardSubmittal Data HBH Series Heat Controller, Inc HBH Series 60Hz Engineering Specifications General Fan and Motor Assembly Field Installed Options Hose Kit Assemblies Page 06/2012

60 HZR-410A, HBH 072 - 120 specifications

The Heat Controller HBH 072 - 120,60 HZR-410A is a state-of-the-art heat pump designed for energy-efficient heating and cooling. This unit promises to deliver exceptional performance, making it an ideal choice for both residential and commercial applications.

One of the standout features of the HBH model is its eco-friendly refrigerant, R-410A, which helps reduce environmental impact without sacrificing performance. This refrigerant has a lower Global Warming Potential (GWP) compared to traditional refrigerants, aligning with modern environmental standards and regulations.

Power and efficiency are key aspects of the HBH 072 - 120,60. This heat pump is capable of delivering significant heating and cooling capacities, making it suitable for a wide range of spaces. The unit is equipped with advanced inverter technology, which enables it to adjust the compressor speed based on the heating or cooling demand. This results in optimal energy consumption, leading to lower utility bills while ensuring comfort throughout the year.

The HBH model integrates a high-efficiency compressor that operates quietly, providing a comfortable indoor environment without the disruptive noise often associated with traditional systems. Additionally, the unit features multiple fan speeds and a programmable thermostat, allowing users to customize their comfort settings easily.

Another highlight of this heat pump is its robust construction and weather-resistant exterior, which ensures long-lasting durability in various climatic conditions. The unit includes a built-in filter system, making maintenance hassle-free and ensuring clean air circulation within the living space.

Moreover, the HBH 072 - 120,60 HZR-410A is designed for easy installation, minimizing the downtime during the setup process. Its compact design allows for flexible placement, fitting seamlessly into various spaces without compromising aesthetics.

Safety is also a priority with this model, as it is equipped with multiple safety features, including protection against overheating and short-circuits. These enhancements not only ensure reliable operation but also provide peace of mind to users.

In summary, the Heat Controller HBH 072 - 120,60 HZR-410A heat pump stands out for its energy efficiency, advanced technology, and user-friendly features. Its combination of comfort, reliability, and eco-conscious operation makes it a prime choice for those seeking an effective heating and cooling solution.