Heat Controller RADS-51B manual Evaporator, Capillary Tube

Page 10

2.4.2 EVAPORATOR

1.Remove the cabinet.

2.Discharge the refrigerant by using a refrigerant recovery system.

3.Remove the air guide upper. (Refer to Section 2.2.1)

4.After discharging the refrigerant completely, unbraze the interconnecting tube at the condenser connections.

5.Remove the evaporator.

6.Re-install by referring to the procedures above.

2.4.3 CAPILLARY TUBE

1.Remove the cabinet.

2.Discharge the refrigerant by using a refrigerant recovery system.

3.Remove the air guide upper. (Refer to Section 2.2.1)

4.After discharging the refrigerant completely, unbraze the interconnecting tube of the capillary tube.

5.Remove the capillary tube.

6.Re-install by referring to the procedures above.

NOTES

Replacement of the refrigeration cycle.

1.When replacing the refrigerating cycle, be sure to discharge the refrigerant by using a refrigerant recovery system.

2.After discharging the unit completely, remove the desired components, and unbraze the pinch-off tubes.

3.Solder service valves into the pinch-off tube ports, leaving the valves open.

4.Solder the pinch-off tubes with service valves.

5.After completing the above procedures, the valve must be closed and left in place on the system for any subsequent procedures.

6.Evacuate as follows:

6-1. Connect the vacuum pump, as illustrated in figure 21A.

6-2. Start the vacuum pump. Slowly open manifold valves A and B with two full turns counter- clockwise and leave the valves closed.

The vacuum pump is now pulling through valves A and B up to valve C by means of manifold and the entire system.

CAUTION : If high vacuum equipment is used, just crack valves A and B for a few minutes, then open slowly with the two full turns counterclock-

wise. This will keep oil from foaming and being drawn into the vacuum pump.

6-3. Operate the vacuum pump for 20 to 30 min- utes, until 600 micron vacuum is obtained. Close valves A and B and observe vacuum gauge for a few minutes.

A rise in pressure would indicate a possible leak or moisture remaining in the system. With valves A and B closed, stop the vacuum pump.

6-4. Remove the hose from the vacuum pump and place it on the charging cylinder. See figure 23B. Open valve C.

Discharge the line at the manifold connection. 6-5. The system is now ready for final charging.

7.Recharge as follows:

7-1. Refrigeration cycle systems are charged from the high-side. If the total charge cannot be put in the high-side, the balance will be put in the suction line through the access valve which is installed as the system is opened.

7-2. Connect the charging cylinder as shown in fig- ure 21B. With valve C open, discharge the hose at the manifold connection.

7-3. Open valve A and allow the proper charge to enter the system. Valve B is still closed.

7-4. If more charge is required, the high-side will not take it. Close valve A.

7-5. With the unit running, open valve B and add the balance of the charge.

a.Do not add the liquid refrigerant to the low- side.

b.Watch the low-side gauge, allow pressure to rise to 30 lbs.

c.Turn off valve B and allow the pressure to drop.

d.Repeat steps b. and c. until the balance of the charge is in the system.

7-6. When the unit is operating correctly, use the pinch-off tool with the unit still running and clamp on the pinch-off tube. Using a tube cut- ter, cut the pinch-off tube about 2 inches from the pinch-off tool. Use sil-fos solder and solder the pinch-off tube closed. Turn off the unit, allow setting for a while and then test the leak- age of the pinch-off connection.

— 10—

Image 10
Contents +$7&21752//5,1& ORIFICE, Turbo FAN and FAN Preface Locations of Controls Safety PrecautionsInsulation Resistance Test Disassembly Instructions AIR Guide Upper AIR Handling PartsORIFICE, Turbo FAN and FAN AIR Guide Electrical PartsOverload Protector Thermistor CompressorCapacitor Control BoardRefrigerant Cycle Power CordCondenser Evaporator Capillary TubePulling Vacuum Select the Best Location HOW to InstallWindow Requirements Before Installation NOW Start InstallationSecure the Guide Panels Outside Troubleshooting Guide Piping System Condenser CoilsTroubleshooting Guide Unit is running but cooling is ineffectiveFails to Start Room AIR Conditioner Voltage Limits Replace if open. If the compressor temperature is Complaint Cause Remedy Circuit Diagram Exploded View Grille ASSEMBLY,FRONT +$7&21752//5,1&

RADS-51B specifications

The Heat Controller RADS-51B is a versatile and efficient heating and cooling solution designed for residential and commercial environments. With a focus on advanced technology and user convenience, this model stands out in the crowded HVAC marketplace.

One of the main features of the RADS-51B is its inverter-driven technology. This innovative approach allows the unit to adjust its cooling and heating output according to the immediate needs of the space. Unlike traditional systems that operate at a fixed speed, the inverter technology enables the RADS-51B to operate more efficiently, significantly reducing energy consumption and utility bills. This feature contributes to a more stable indoor environment by minimizing temperature fluctuations.

The RADS-51B is also equipped with a powerful dual-mode operation, which allows users to switch between heating and cooling modes effortlessly. This flexibility makes it ideal for regions that experience varied temperatures throughout the year. The unit’s heating capability even includes a low-temperature operation feature, which ensures reliable heating performance even in extreme cold conditions.

Another notable characteristic of the RADS-51B is its comprehensive digital display and remote control functionality. The user-friendly interface provides easy access to settings and temperature adjustments, allowing users to create customized heating and cooling schedules to suit their lifestyle. The remote control feature adds an extra layer of convenience, enabling adjustments from anywhere in the home or office.

In addition to efficiency and convenience, the RADS-51B prioritizes user comfort with its quiet operation. The design minimizes noise levels, ensuring that the unit operates in a discreet manner without disrupting daily activities.

Built with durability in mind, the RADS-51B features a robust construction designed to withstand the demands of continuous use. The materials are chosen for their resilience, ensuring a longer lifespan and fewer maintenance issues over time.

Environmentally conscious consumers will appreciate that the RADS-51B uses eco-friendly refrigerants, aligning with modern standards for energy-efficient and sustainable practices.

In summary, the Heat Controller RADS-51B combines advanced inverter technology, dual-mode operation, user-friendly controls, and quiet performance to deliver an exceptional indoor climate experience. Whether for residential or commercial applications, the RADS-51B stands as a reliable choice for effective heating and cooling solutions.