Haier HSU18VH7 manual State1 State2 State3 Ts-1 Ts+2 Ts+3

Page 8
3.2.4

Air conditioner

Edition: 10070808

 

 

 

State1

State2

State3

Ts-1

Ts

Ts+2

Ts+3

Warm start (preventing cold wind when heating running begins, applicable to fan-coil model))

When heating running begins, indoor fan will conduct the following fan control: If the temperature of indoor coil pipe is 23, start lower wind speed; If the temperature of indoor coil pipe is 38or the running time of compressor4 minutes, turn to setting wind speed.

3.2.5 Control of indoor fan under heating OFF state (applicable to fan-coil model) Under heating state, the compressor will cease; if the indoor coil pipe’s temperature Tp23, indoor fan will run in lower wind speed.

3.2.6 Defrosting control (applicable to fan-coil model) Defrosting beginning condition:

a.After the state of Tp-Tr<16is continued for 5 minutes, the accumulated running time of the compressor exceeds 45 minutes, the continuous running time of the compressor exceeds 20 minutes;

b.The accumulated running time of the compressor exceeds 3 hours, the continuous running time of the compressor exceeds 20 minutes, indoor unit’s Tp <38;

c.The continuous running time of the compressor exceeds 20 minutes, the temperature of indoor coil pipe decreases 1every 6 minutes, which lasts for more than 3 times, indoor unit’s Tp <38;

d.When the indoor unit is in the state of overload protection and the outdoor unit ceases, when the rerunning time of outdoor unit exceeds10 minutes, the

accumulated running time of the compressor exceeds 45 minutes, the continuous running time of the compressor is over 20 minutes, and Tp <38 .

Defrosting will begin if one of the above conditions is met.

Defrosting finishing condition:

If the defrosting time exceeds 9 (for 12 models)or 7 (for 07,09 models) minutes,the original heating state will be resumed;

- 6 -

Image 8
Contents Domestic Air conditioner Contents General information HSU18VH7 ~43 Basic Function Introduction to electrical control functions State1 State2 State3 Ts-1 Ts+2 Ts+3 OFF Ts+2 Ts+1 1 hours 6hours Hour Ts SleepOFF thour PCB 10070808 Table for Wrong Codes 10070808 10070808 10070808 Air conditioner Indoor unit 10070808 10070808 10070808 Wiring Diagram Indoor Unit Outdoor Unit RKΩ RKΩ HSU18VH7 Circuit Diagram