Air conditioner | Edition: 10070808 | |
|
|
|
State1
State2
State3
| Ts | Ts+2 | Ts+3 |
Warm start (preventing cold wind when heating running begins, applicable to
When heating running begins, indoor fan will conduct the following fan control: If the temperature of indoor coil pipe is ≥ 23℃, start lower wind speed; If the temperature of indoor coil pipe is ≥ 38℃ or the running time of compressor≥ 4 minutes, turn to setting wind speed.
3.2.5 Control of indoor fan under heating OFF state (applicable to
3.2.6 Defrosting control (applicable to
a.After the state of
b.The accumulated running time of the compressor exceeds 3 hours, the continuous running time of the compressor exceeds 20 minutes, indoor unit’s Tp <38℃;
c.The continuous running time of the compressor exceeds 20 minutes, the temperature of indoor coil pipe decreases 1℃ every 6 minutes, which lasts for more than 3 times, indoor unit’s Tp <38℃;
d.When the indoor unit is in the state of overload protection and the outdoor unit ceases, when the rerunning time of outdoor unit exceeds10 minutes, the
accumulated running time of the compressor exceeds 45 minutes, the continuous running time of the compressor is over 20 minutes, and Tp <38 ℃.
Defrosting will begin if one of the above conditions is met.
Defrosting finishing condition:
If the defrosting time exceeds 9 (for 12 models)or 7 (for 07,09 models) minutes,the original heating state will be resumed;
- 6 -